Operations
16
06: Backup time setting
INTERFACE
SETTING
Sets the amount of backup time on battery mode for general outlets
before power is removed.
0-998
: setting the backup time in minutes from 0-998 in battery mode.
0
: When setting as “0”, the backup time will be only 10 seconds.
999
: When setting as “999”, the backup time setting will be disabled.
(default)
07: Battery total AH setting
INTERFACE
SETTING
Set up the battery total AH of the UPS. (unit: AH)
7-999: sets the total battery capacity from 7-999 in AH.
Please set the correct battery capacity if EBCs are connected.
Each GXT RT+ EBC adds 18 AH.
00: Exit setting
INTERFACE
SETTING
ESC
: Exit the setting menu.