CAUTION: Risk of contact with hot surfaces. Can cause injury. The electronics housing,
humidifier components, fan motor, and some electrical components are extremely hot during
unit operation. Allow sufficient time for them to cool to a touch-safe temperature before
working within the unit cabinet. Use extreme caution and wear appropriate, OSHA-approved
PPE when working on or near hot components.
NOTICE
Risk of improper power-supply connection. Cancause equipment damage and loss of warranty coverage.
Prior to connecting any equipment to a mainor alternate power source (for example: back-up generator
systems) for start-up, commissioning, testing, or normal operation, ensure that these sources are correctly
adjusted to the nameplate voltage and frequency of all equipment to be connected. Ingeneral, power-source
voltages should be stabilized and regulated to within±10%of the load nameplate nominal voltage. Also, ensure
that no three-phase sources are single-phased at any time.
NOTE: Do not assume that the fan blades will not start to spin. If the motor is in a fault condition, it will
safely shut down. Once the fault condition is cleared, there are certain conditions in which the motor
will automatically resume operation.
EC-fan Fault Conditions
Fault
Condition
Reset Trigger
Description
Phase Failure
Automatic
One phase ismissing. Inthiscase the motorwill come toa stopandthenautomatically restart whenall phasesare
present.
Locked/Blocked
Rotor
Automatic
The rotorisblocked. Once the lockingmechanismhasbeenremoved, the motorwill automatically restart.
Hall Effect
SensorError
Manual
(Mains/Software)
The Hall Effect Sensorisusedtomonitorfanspeed. If there isa hall sensorcommunicationfailure withthe
electronics, the motorwill stop. Inthiscase there hastobe a manual restart (eitherwiththe mainspoweror
software).
MotorOver
Temperature
Manual
(Mains/Software)
The motorwill stopinthe event there isa motorovertemperature condition. Inthiscase there hastobe a manual
restart (eitherwiththe mainspowerorsoftware).
ElectronicsOver
Temperature
Manual
(Mains/Software)
The motorwill stopinthe event there isanelectronicsovertemperature condition. Inthiscase there hastobe a
manual restart (eitherwiththe mainspowerorsoftware).
Line
Under-Voltage
Automatic
Once the line voltage returnswithinpermittedoperatingrange, the fanwill automatically restart.
Table 11.1 EC-fan Fault Conditions
10 Maintenance
85
Summary of Contents for Liebert CW 038
Page 14: ...Vertiv Liebert CW Installer User Guide 14 Thispageintentionally left blank...
Page 22: ...Vertiv Liebert CW Installer User Guide 22 Thispageintentionally left blank...
Page 38: ...Vertiv Liebert CW Installer User Guide 38 Thispageintentionally left blank...
Page 80: ...Vertiv Liebert CW Installer User Guide 80 Thispageintentionally left blank...
Page 102: ...Vertiv Liebert CW Installer User Guide 102 Thispageintentionally left blank...
Page 108: ...Vertiv Liebert CW Installer User Guide 108 Thispageintentionally left blank...