Symptom
Possible Cause
Check or Remedy
Reheat will not operate; contactornot
pullingin
Control not calling
forheat
Check monitorstatus.
Reheat safety stat
open
JumperbetweenterminalsP34-1 andP34-2. If reheat operates, safety isopen. Remove
jumper. Replace safety.
Reheat not operating, contactor
pullingin
Heaterburnedout
Turnoff powerandcheck heatercontinuity withOhmmeter.
Table 10.4 Reheat troubleshooting