C h apter 5 U P S O peratin g In structions 4 9
L iebert E X S 30 kV A A n d 4 0 kV A U P S U ser M an ual
5. F inish setting up the sing le U P S param eters and check them
A cce ss the m ain m enu screen, pre ss the
or
key to select 'S tatus', and press the
key to
acce ss the interface show n in F ig ure 5 -3.
Figure 5-3 M ain m en u screen
C heck that the param eters containing input, bypass, battery voltage, frequency and phase are correct, and
then back to the Flow pag e.
6. A cce ss the flow page, press and hold the pow er button, then the LC D prom pt a dialog ue box , as show n in
F ig ure 5-4 . A fter selecting 'Y E S', the inverter execute s self-check and start-up. A fter the inverter runs
norm ally, the U P S w ill transfer to norm al m ode, and the run indicator w ill be solid on. S ee F igure 5 -5 for the
pow er flow page.
218.2V
50.0Hz
220.0V
49.9Hz
充电
563.8V
97%
200.0
分
8.2V
0Hz
0%
Confirm
Turn
on
local
INV?
No
Yes
Figure 5-4 Sw itch in g the U P S on
Figure 5-5 Flow page ap pears after in verter on