Installation Drawings
Vertiv
| Liebert
®
EXM
™
Parallel Cabinet User Manual |
20
Figure 8
Outline drawing—300mm Liebert EXM Parallel Cabinet
34.3"
(872mm)
NOTES
1. All dimensions are in inches (mm).
2. 24" (610) minimum clearance above unit for air exhaust.
36" (914) front access required for service.
3. Keep cabinet within 15 degrees of vertical.
4. Top and bottom cable entry available through removable
access plates. Remove, punch to suit conduit size and replace.
5. Unit bottom is structurally adequate for forklift handling.
6. Control wiring and power wiring must be run in separate conduits.
7. Copper cables only are recommended.
8. All wiring is to be in accordance with national and local electrical codes.
FRONT
DETAIL A
TOP VIEW
BOTTOM VIEW
RIGHT SIDE VIEW
FRONT VIEW
EXM12010A
Rev. 3
Leveler
Cable Entry Area
10" x 15.7"
(254mm x 399mm)
See
Detail A
39.1" (993mm)
Cable Entry Area
10" x 11.8"
(254mm x 300mm)
Cable Entry Area
8.3" x 7.9"
(211mm x 201mm)
8.6" (218mm)
34.3"
(872mm)
12.1
(300mm)
11.8"
(300mm)