Vertiv™ eSure™ Rectifier Module User Manual 

Proprietary and Confidential © 2022 Vertiv Group Corp. 

Table 1.2  

Maximum Input Current in 50Hz Input 

Nominal Input Voltage 

Input Voltage 

Input Current (Amperes) 

200 VAC / 250 VAC 

176 VAC 

6.16 

 

 

NOTE!

  

At 100% of full load with output adjusted to 58 volts DC as measured at the shelf output terminals. 

 

Table 1.3  

Typical Input Data in 60Hz Input 

Nominal 

Input Voltage 

Percent 

of Full Load 

Input Current 

(Amperes) 

Input 

VA 

Input 

Watts 

Power 

Factor % 

Efficiency 

% Heat 

Heat Dissipation 

BTU/Hr 

120 VAC

 

0.111 

11.14 

10.87 

0.976 

-- 

37.09 

25 

2.262 

271.16 

270.98 

0.999 

92.24 

71.76 

50 

4.515 

541.06 

540.93 

0.999 

92.37 

140.76 

75 

6.719 

803.38 

803.17 

0.999 

90.32 

265.18 

100 

 

 

 

 

 

 

110 

 

 

 

 

 

 

200 VAC 

0.095 

16.81 

10.37 

0.617 

-- 

35.38 

25 

1.351 

269.62 

268.36 

0.995 

92.77 

62.17 

50 

2.644 

528.83 

527.55 

0.998 

94.45 

95.74 

75 

3.975 

794.62 

793.52 

0.999 

94.23 

152.82 

100 

5.359 

1070.26 

1069.10 

0.999 

93.25 

242.50 

110 

5.555 

1109.39 

1108.06 

0.999 

92.97 

261.59 

208 VAC

 

0.096 

17.77 

10.31 

0.580 

-- 

35.17 

25 

1.299 

269.51 

268.01 

0.994 

93.26 

61.62 

50 

2.537 

527.85 

526.33 

0.997 

94.79 

93.65 

75 

3.814 

793.04 

791.76 

0.998 

94.48 

149.24 

100 

5.129 

1065.77 

1064.46 

0.999 

93.65 

230.49 

110 

5.329 

1107.26 

1105.76 

0.999 

93.19 

257.04 

220 VAC 

0.098 

18.99 

9.60 

0.506 

-- 

32.75 

25 

1.229 

269.65 

267.73 

0.993 

93.30 

61.17 

50 

2.398 

527.35 

525.42 

0.996 

94.94 

90.77 

75 

3.598 

791.54 

789.97 

0.998 

94.67 

143.62 

100 

4.832 

1062.30 

1060.71 

0.999 

93.94 

219.29 

110 

5.016 

1102.23 

1100.43 

0.998 

93.55 

242.15 

240 VAC 

0.109 

23.44 

12.29 

0.524 

-- 

41.94 

25 

1.130 

270.31 

267.41 

0.989 

93.53 

59.02 

50 

2.200 

527.88 

525.05 

0.997 

95.14 

86.99 

75 

3.290 

789.54 

787.32 

0.997 

95.09 

131.90 

100 

4.417 

1059.25 

1057.09 

0.998 

94.42 

201.38 

110 

4.581 

1098.85 

1096.42 

0.998 

94.11 

220.40 

 

Summary of Contents for eSure R48-1000e3

Page 1: ...eSure Rectifier Module User Manual Specification Number 1R481000e3 Model Number R48 1000e3...

Page 2: ...ally described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of Vertiv and contains confidential and proprietary...

Page 3: ...d Regulatory Statements v D clarations de S curit et de R glementation v 1 Introduction 1 1 1 Overview 1 1 2 Specifications 1 2 Operation 11 2 1 AC Input Protection Device Requirements Recommendations...

Page 4: ...jury if not avoided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards...

Page 5: ...nts used in this document are listed under Admonishments Used in this Document on page iv Safety and Regulatory Statements Refer to Section 4154 provided with your customer documentation for Safety an...

Page 6: ...Vertiv eSure Rectifier Module User Manual Proprietary and Confidential 2022 Vertiv Group Corp vi This page intentionally left blank...

Page 7: ...ate in the Constant Voltage Mode unless load increases to the point where the product of load current and output voltage is approximately 1000 W Constant Power Mode As load increases above approximate...

Page 8: ...ifier will not shut down Rather the rectifier limits its maximum output power to maintain the temperature of the power conversion circuit within design parameters Operation between 45 C 113 C and 75 C...

Page 9: ...s of load from no load to full load input voltage and input frequency at a constant ambient temperature The associated system controller may provide increased regulation b Dynamic Response time 200 mi...

Page 10: ...t Current Refer to Table 1 4 Efficiency Curve Refer to Figure 1 4 Table 1 1 Typical Input Data in 50Hz Input Nominal Input Voltage Percent of Full Load Input Current Amperes Input VA Input Watts Power...

Page 11: ...995 92 77 62 17 50 2 644 528 83 527 55 0 998 94 45 95 74 75 3 975 794 62 793 52 0 999 94 23 152 82 100 5 359 1070 26 1069 10 0 999 93 25 242 50 110 5 555 1109 39 1108 06 0 999 92 97 261 59 208 VAC 0...

Page 12: ...t 50 of full load and nominal input Percent of Full Load refers to percent of 18 69 amperes Table 1 4 Maximum Input Current in 60Hz Input Nominal Input Voltage Input Voltage Input Current Amperes 200...

Page 13: ...bution System TN TT IT NOTE The rectifier is recommended to be used in an environment with Pollution of Degree 2 or less Pollution Degree 2 applies where there is only non conductive pollution that mi...

Page 14: ...he rectifier can be plugged into or pulled out of a shelf while operating without damage or opening the fuse b Current Limiting The rectifier has a current limit function The current limit point can b...

Page 15: ...d This feature can be disabled via the controller allowing the fan to run at full speed regardless of temperature Paralleling Up to 16 rectifiers can be connected in parallel in one system Communicati...

Page 16: ...e Regulation Input Voltage Output Voltage Output Current Current Limit Setting Temperature Over Voltage Setting On Off Status Fault Alarms such as HVSD Fan Fail Protection Alarms such as Input Voltage...

Page 17: ...Green On Off No input voltage Internal input fuse open Flashing The rectifier is being identified by the controller Protection Yellow Off On AC input under over voltage PFC output under over voltage M...

Page 18: ...ctifier 2 5 Installing Rectifiers Rectifiers can be inserted or removed with power applied hot swappable NOTE Each rectifier module locks into a module mounting shelf by means of a latch located on th...

Page 19: ...ng Imbalance When multiple rectifiers are operating in parallel and the load is greater than 20 if the current sharing imbalance among them is greater than 5 check if the rectifier is properly seated...

Page 20: ...the fan Ventilation blocked inlet or outlet remove any object that may be blocking the inlet or outlet Ambient temperature too high or rectifier inlet too close to a heat source lower the ambient temp...

Page 21: ...regard any alarms associated with this system while this procedure is performed 2 On the rectifier to be removed loosen the captive screw on the rectifier s handle Pull the handle down out from the re...

Page 22: ...Vertiv eSure Rectifier Module User Manual Proprietary and Confidential 2022 Vertiv Group Corp 16 This page intentionally left blank...

Page 23: ...User Manual Proprietary and Confidential 2022 Vertiv Group Corp Connect with Vertiv on Social Media https www facebook com vertivI https www instagram com vertiv https www linkedin com company vertiv...

Page 24: ...or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibility and disclaims all liabili...

Reviews: