background image

Vertiv™ NetSure™ IPE Series Rectifier Installation and User Manual 

 12 

Figure 11:  

Securing the Rectifier to the Pole at the Top 

 

 

Figure 12:  

Securing the Rectifier to the Pole at the Bottom 

 

M8 Bolts (2 places)

P/N 26011153

Torque to 13 to 16 Nm

(115 to 141 in-lbs).

Pole Mount Band

P/N 63126330

Torque to 5.0 Nm (44.3 in-lbs).

 Mounting Bracket (Big)

P/N 63240BPY

Summary of Contents for 02131111

Page 1: ...NetSure IPE Series Rectifier Installation and User Manual Specification Number 02131111 Model Number R48 2000C...

Page 2: ...procedures not specifically described in this document The products covered by this instruction manual are manufactured and or sold by Vertiv This document is the property of Vertiv and contains confi...

Page 3: ...cal Connections 15 3 1 Important Safety Instructions 15 3 2 Wiring Considerations 15 3 3 Frame Ground Connection 15 3 4 Customer Wiring to Terminal Blocks Located Inside Rectifier Case 16 3 4 1 Genera...

Page 4: ...Vertiv NetSure IPE Series Rectifier Installation and User Manual iv 6 2 Troubleshooting 24 6 2 1 Rectifier Current Sharing Imbalance 24 6 3 Repair 24 7 DC Power Outdoor Enclosure Service Contacts 26...

Page 5: ...ided ANSI OSHA This admonition is not used for situations that pose a risk only to equipment data or service even if such use appears to be permitted in some of the applicable standards OSHA ALERT Ale...

Page 6: ...rk to be performed Voltages AC Input Voltages DANGER This system may operate from AC input voltage capable of producing fatal electrical shock AC input power must be completely disconnected from the b...

Page 7: ...Do not work on LIVE parts If required to work or operate live parts obtain appropriate Energized Work Permits as required by the local authority per NFPA 70E Standard for Electrical Safety in the Wor...

Page 8: ...stor is necessary Read and follow wrist strap manufacturer s instructions outlining use of a specific wrist strap 3 Do not touch traces or components on equipment containing static sensitive component...

Page 9: ...ut at derated output power levels Constant Voltage Mode For any initial output voltage setting from 42 VDC to 58 VDC factory set at 54 VDC output voltage remains constant regardless of load This is th...

Page 10: ...ture of 50 C 122 F or below The rectifier continuously monitors the ambient temperature surrounding the power conversion circuit If this temperature for any reason such as a high ambient temperature i...

Page 11: ...rature 6 Regulation a Static Steady state regulation is 0 6 as controlled within the rectifier for any and all combinations of load from 5 to 100 load input voltage and input frequency at a constant a...

Page 12: ...rrent Amperes Input VA Input Watts Power Factor Efficiency Heat Dissipation BTU Hr 208 0 0 747 156 234 13 4 0 080 45 654 25 2 559 534 2 514 9 0 960 90 901 159 854 50 4 850 1012 9 992 3 0 979 93 979 20...

Page 13: ...506 1974 8 1961 7 0 994 94 720 353 405 110 10 460 2171 1 2159 6 0 995 94 679 392 108 240 0 1 031 248 9 13 0 0 050 0 000 44 494 25 2 376 575 8 517 3 0 907 91 333 152 975 50 4 241 1020 7 989 2 0 969 94...

Page 14: ...C 122 F to 75 C 167 F with derating output c Temperature Coefficient 0 02 per degrees Celsius 2 Storage Ambient Temperature Range 40 C 40 F to 70 C 158 F 3 Relative Humidity This rectifier is capable...

Page 15: ...the middle of rectifier 7 High Voltage Category per UL60950 III 8 Power Distribution System TN TT IT 9 EMI RFI Suppression a The rectifier conforms to the requirements of FCC rules Part 15 Class B for...

Page 16: ...The rectifier then restarts and a HVSD restart timer starts factory set at 5 minutes If output voltage again exceeds the high voltage shutdown value before the HVSD restart timer expires the rectifie...

Page 17: ...pecifications Dimensions and Weight Refer to Figure 7 Figure 7 Overall Dimensions and Weight Front View Bottom View Top View Left Side View Right Side View Rear View Notes 1 Dimensions are in inches 2...

Page 18: ...en the pole mount band to the pole The pole mount band accommodates poles from 6 to 12 in diameter Refer to Figure 8 3 Install mounting brackets to the rear panel of the rectifier with the supplied ha...

Page 19: ...ing Brackets to the Rectifier Figure 10 Installing the Connect Bend Bracket to the Rectifier Optional M6 X 20 Bolts 4 GB9074_13 88_M6X20_SL Torque to 2 8 to 4 8 Nm 24 78 to 42 48 in Ibs M6 X 12 Bolts...

Page 20: ...e 11 Securing the Rectifier to the Pole at the Top Figure 12 Securing the Rectifier to the Pole at the Bottom M8 Bolts 2 places P N 26011153 Torque to 13 to 16 Nm 115 to 141 in lbs Pole Mount Band P N...

Page 21: ...r panel of the rectifier Refer to Figure 14 3 Secure the connect band bracket to the rectifier with the supplied M6 bolts optional Refer to Figure 15 4 Secure the rectifier to the wall using the wall...

Page 22: ...Connect Bend Brackets to the Rectifier Optional Figure 16 Securing the Rectifier to the Wall M6 X 20 Bolts 4 GB9074_13 88_M6X20_SL Torque to 2 8 to 4 8 Nm 24 78 to 42 48 in Ibs M6 X 12 Bolts 4 P N 260...

Page 23: ...operation in countries where the NEC is not recognized follow applicable codes 3 3 Frame Ground Connection For grounding requirements refer to the current edition of the American National Standards I...

Page 24: ...sealing pin onto the unused cable gland See Figure 21 3 4 2 Procedure 1 Strip cord insulation as required Refer to Figure 18 Refer also to Figure 25 2 Install the ferrule or ring lug as required Refer...

Page 25: ...previous page SJOOW 600V 6AWG 2 C Sealing cable adapter provide maximum cable diameter is 18 mm to 25 mm 0 71 inch to 1 inch SJOOW 300V 12AWG 3 C Sealing cable adapter provided maximum cable diameter...

Page 26: ...er about 22 mm and rotate the cover clockwise 180 around the M6 screw Refer to Figure 19 Figure 19 Unscrew the Cable Access Cover and Rotate the Cable Access Cover Clockwise 180 Around the M6 Screw 5...

Page 27: ...ng for specific wire instructions External Alarm and Control Connections See External Alarm and Control Connections on page 21 AC Input and AC Input Equipment Grounding Connections See Nominal 120 VAC...

Page 28: ...ated in Figure 23 Figure 23 Tighten All of the Cable Gland Caps as Required and Torque as Indicated 9 Rotate the cable access cover counterclockwise 180 around the M6 screw Install the screws previous...

Page 29: ...he mating connector Maximum wire size is 22 AWG See Figure 25 See also Customer Wiring to Terminal Blocks Located Inside Rectifier Case starting on page 16 3 5 2 Contact Ratings UL CSA Rating NOTE To...

Page 30: ...ssociated with J4 1 Terminal CAN on the Alarm Connector CAN_L associated with J4 2 3 6 Nominal 120 VAC 208 VAC 220 VAC 230 VAC 240 VAC Input and AC Input Equipment Grounding Connections The rectifier...

Page 31: ...determined by site requirements Figure 25 Customer Wiring Location Diagram 3 9 Paralleling Rectifiers for Redundancy DO NOT EXCEED THE LOAD RATING OF A SINGLE RECTIFIER To parallel rectifiers connect...

Page 32: ...r 6 Troubleshooting and Repair 6 1 Contact Information Refer to DC Power Outdoor Enclosure Service Contacts on page 26 for support contact information 6 2 Troubleshooting 6 2 1 Rectifier Current Shari...

Page 33: ...Vertiv NetSure IPE Series Rectifier Installation and User Manual 25 This page intentionally left blank...

Page 34: ...ing and purchase orders for spare parts including but not limited to breakers cables fuses rectifier fans misc breaker and fuse panels enclosure fans doors and switches etc Phone 1 800 800 1280 option...

Page 35: ...IPE Series Rectifier Installation and User Manual Connect with Vertiv on Social Media https www facebook com vertivI https www instagram com vertiv https www linkedin com company vertiv https www twit...

Page 36: ...are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness here Vertiv Group Corp assumes no responsibilit...

Reviews: