Vertex ORUM II Installation, Operation, Maintenance, Parts Download Page 6

HP Fusible

(fuse)

Amps

max.

Volts

60hz / 1ph.

Cable (AWG) (115 / 230v)

0-30m

0-100’

31-60m

101-200’

61-90m

201-300’

¾

15

7.6 / 3.8

115/230

14 / 18

12 / 18

10 / 16

1

20

9.2 / 4.6

115/230

14 / 12

10 / 16

8 / 14

20

13.6 / 6.8

115/230

12 / 12

8 / 14

8 / 14

2

30

18 / 9

115/230

10 / 16

8 / 14

6 / 12

2.4

30

22 / 11

115/230

10 / 16

6 / 12

6 / 12

3

30

24 / 12

115/230

10 / 16

6 / 12

4 / 10

Voltaje

:

El voltaje al motor debe ser de +/- 10% del valor indicado en la placa de 

identificación del motor o éste puede sobrecalentarse provocando una 

sobrecarga, disparar protectores y reducir la vida de sus componentes. Si 

el voltaje es inferior al 90% o superior a 110% del voltaje nominal al estar 

el motor funcionando a máxima carga, consultar a la compañía eléctrica.

Conexión a tierra

:

Instale, conecte a tierra y cablee el motor según el código local o los 

requisitos del Código Eléctrico Nacional.  Conecte permanentemente el 

motor a tierra.  Use la terminal a tierra (verde) provista en el motor; use 

el tamaño y tipo de cable requerido por el código local.  Conecte la ter

-

minal de tierra del motor a la tierra de su red eléctrica.

Conecte un cable de cobre sólido Cal. 8 AWG al conector provisto en el 

motor y a todas las partes metálicas de la piscina, spa o tina de hidro

-

masaje y a todos los equipos eléctricos y tubería para el cableado que se 

encuentre a menos de 1.5 mts (5 pies) de la piscina, spa o tina de baño.

Motores de 2 voltajes

:

Algunos modelos de bomba pueden estar equipados con motores de 

doble voltaje.  En estos casos asegúrese que el instalador conecte su 

bomba al voltaje correspondiente a su instalación o sigue las instruc-

ciones proveidas en la placa de conexiones del motor para cambiarlo.

Cableado

:

La bomba debe estar permanentemente conectada al circuito. La tabla A

proporciona los tamaños correctos de cable y disyuntor para la bomba 

solamente. Si existen otros equipos o luces, etc. también conectados al 

mismo circuito, asegúrese de agregar sus cargas a las requeridas para la 

bomba antes de calcular los tamaños de cables y disyuntores.

 (Si no está 

seguro cómo hacer esto o si esto es confuso, consulte a un electricista).

 OPERACIÓN

 AVISO: 

NUNCA 

haga funcionar la bomba en seco. Puede dañar los se-

llos, causando fugas e inundaciones. Llene la bomba con agua (cebar) 

antes de arrancar el motor.

RIESGO DE EXPLOSIÓN

. Antes de retirar la tapa de la trampa:

1.  Apague la bomba y cierre las válvulas de seccionamiento de las 

tuberías de succión y descarga.

2.   Libere toda la presión de la bomba y el sistema de tuberías.

Riesgo de fuego y quemaduras:

  Para reducir el riesgo de incendio, no 

permita  hojas,  escombros  o  materias  extrañas  alrededor  del  motor. 

Para evitar quemaduras al manipular el motor, déjelo enfriar durante 20 

minutos antes de intentar trabajar en él. 

Cebado:

Libere toda la presión del filtro (vea su manual del propietario), la bomba 

y el sistema de tuberías. En un sistema de succión positiva (la fuente de 

agua más alta que la bomba), ésta se cebará sola cuando las válvulas de 

succión y descarga se abran; si no es así, desenrosque, quite la tapa de 

la trampa y llénela (cebe) con agua. No lubrique la junta de la tapa de 

la trampa; ésta contiene un lubricante interno permanente.  

NOTA:

  Si 

reemplaza la junta por una no lubricada, aplique un lubricante a base 

de silicón.

Inspeccione y limpie la junta, vuelva a colocar la tapa de la trampa y apri-

ete (sentido manecillas del reloj) solo con la mano (¡sin llaves!).  

La bomba debe cebar ahora. El tiempo dependerá de la altura de la suc

-

ción y la longitud horizontal de la tubería de succión.  Si la bomba no se 

ceba, asegúrese de que todas las válvulas estén abiertas, el extremo del 

tubo de succión esté sumergido, la altura sea menor a 2m (6½‘), y que no 

haya fugas en la tubería de succión y repita el procedimiento. Si continúa 

sin cebarse, consulte la sección 

Solución de Problemas

.

Voltage

:

Verify the voltage to the motor is /- 10% of motor nameplate or 

it can overheat causing overload, trip protectors and reduce the life of 

components. If voltage is below 90% or over 110% of the nominal volt

-

age when the motor is running at full load, consult the power company.

Ground connection (Grounding/Bonding)

:

Install, ground and wire the motor according to local code or the require

-

ments of the National Electrical Code. Permanently connect the motor 

to ground. Use the ground terminal (green) provided on the motor; use 

the size and type of cable required by the local code. Connect the ground 

terminal of the motor to the ground of the electrical service.

Connect a solid copper wire No. 8 AWG to the connector provided in the 

motor and to all the metal parts of the pool, spa or hot tub and to all the 

electrical equipment, metal pipe and conduit that is within 5 feet (1.5m) 

from the pool, spa or bath tub.

Dual Voltage motors

:

Some  pump  models  may  be  equipped  with  2-voltage  motors.  In  that 

case, the installer needs to make sure your pump is wired according to 

the available voltage.  To change it, instructions provided in the motor 

connections plate or corresponding label need to be followed.

Wiring

:

Pump must be permanently connected to the circuit. Table A provides 

correct cable and circuit breaker sizes for pump only. If other equipment 

or lights, etc. are connected to the same circuit, be sure to add these 

loads to those required for the pump before calculating wire sizes and 

circuit breakers

. (If in doubt, consult a licenced electrician).

 OPERATION

NOTICE: 

NEVER 

run the pump dry as you may damage the seals, causing 

leaks and floods. Fill the pump with water before starting the motor.

RISK OF EXPLOSION

. Before removing trap cover:

1.  Stop pump. Close shut-off valves in suction and discharge pipes.

2.   Release all pressure from pump and piping system.

Risk of fire and burns:

  To reduce the risk of fire, do not allow leaves, de

-

bris or foreign materials around the motor. To avoid burns when handling 

the motor, let it cool for 20 minutes before attempting to work on it.

Priming:

Release all pressure from the filter (see its owner’s manual), the pump 

and the piping system. In a positive suction system (when source of wa

-

ter is higher than the pump), it will prime itself when the suction and 

discharge valves are open; otherwise, unscrew, remove the trap cover 

and fill it (prime) with water. Do not lubricate the trap cover gasket; It 

contains a permanent internal lubricant. NOTE: If you replace the gasket 

with a non-lubricated one, apply a silicone-based lubricant.

Inspect and clean the gasket, replace the trap cover and tighten (clock

-

wise) only by hand (no wrenches!). 

The pump must prime now. Priming time will depend on vertical and hor

-

izontal lenght of pipe. If pump does not prime, make sure all valves are 

open, the end of the suction pipe is submerged, the lift height is less than 

6½’ (2m), and there are no leaks in the suction pipe.  Repeat the proce

-

dure. If pump still doesn’t prime, see the 

Troubleshooting Guide

 section.

Tabla (table) A

. Selección de Cable de Alimentación y Fusibles (Cable and Fuse sizing table)

-6-

Summary of Contents for ORUM II

Page 1: ...ervicio eventuales riesgos por el uso o manipulaci n indebidos y prolongar la vida til de la bomba This manual should be left with the end user of this pump Its use will reduce service calls eventual...

Page 2: ...or de Circuito con Falla a Tierra GFCI debe estar insta lado de modo que interrumpa totalmente la energ a a su equipo SAFETY Important safety instructions PRESERVE THIS MANUAL It contains important in...

Page 3: ...esional calificado que deber cumplir con todas las legislaciones nacionales estatales y c digos locales Estas instrucciones contienen informaci n para una variedad de tama os de bomba Siga las instruc...

Page 4: ...have been instructed on its use by a technician or a person responsible of their safety INSTALACION AVISO Solo personal calificado debe instalar esta bomba y su cableado El montaje de la bomba debe e...

Page 5: ...ned in place Suction outlets main drains per pump Install at least two main drains suction outlets hydraulically balanced and with approved covers as suction outlets for each circulation pump in the s...

Page 6: ...n llaves La bomba debe cebar ahora El tiempo depender de la altura de la suc ci n y la longitud horizontal de la tuber a de succi n Si la bomba no se ceba aseg rese de que todas las v lvulas est n abi...

Page 7: ...VAS DE DESEMPE O PERFORMANCE CURVES ALMACENAJE Y MANTENIMIENTO Su nueva bomba no requiere de mantenimiento regular salvo por la limpieza peri dica de la trampa de hojas Si nota una disminuci n en el r...

Page 8: ...s may not apply to you This warranty gives you specific legal rights and you may also have other rights which vary from state to state or country GUIA PARA LA IDENTIFICACION DE PROBLEMAS TROUBLE SHOOT...

Reviews: