Vertex GP6 Instruction Manual Download Page 17

17

of the rubber boot vent adapter is capped off. Lastly, make sure
there is no damage to the blower.

3. Condensate  drains from two locations on the blower assembly as

shown in figure 17. A condensate hose must be secured to form a
"trap" as shown in figure 17 for these condensate drain connections.
These two hoses may be connected together. The hose(s) should
be routed to a suitable drain. A fitting that may be used to join the
two hoses from the blower assembly is included in a supplied kit.

FIGURE 17.

4. Make sure there is no packing material in the inlet or discharge

of the blower.

5. Make sure that the plastic tubing is still attached from the air

pressure switch to the port on the blower housing. Make sure
the plastic tubing is not folded anywhere between the pressure
switch and the blower housing.

6. Make sure the ON/OFF switch is in the OFF position and that

the outer harness is connected from the blower control box to
the connector on the bottom side of the gas valve.

7. If the outer harness is not factory installed, make sure the ON/

OFF switch is in the OFF position and then connect the outer
harness from the blower control box to the connector on the
bottom side of the gas valve.

8. Do not plug in power cord until vent system is completely installed.

The Power Vent operates on 110 -120 Vac. therefore a grounded
outlet must be within reach of the 6 foot (1.8 m) flexible power
cord supplied with the vent (See Figure 1). The power cord
supplied may be used on a unit only where local codes permit.
If local codes do not permit use of flexible power supply cord:

A. Make sure the unit is unplugged  from the wall outlet. Remove

the plastic top cap. Remove screws and open panel on the
front of the control box on the blower.

B. Cut the flexible power cord, leaving enough to be able to make

connections. Remove the strain relief fitting from the box.

C. Install a suitable conduit fitting inside the enclosure.

D. Splice field wiring into existing wiring using code authorized

method (wire nuts, etc).

E. Be certain that neutral and line connections are not reversed

when making these connections.

F.

Ground heater properly.  This water heater must be grounded in
accordance with the National Electrical Code NFPA 70 and/or
local codes.  These must be followed in all cases.

The water heater must be connected to a grounded metal,
permanent wiring system; or an equipment grounding
conductor must be run with the circuit conductors and
connected to the equipment grounding terminal or lead on
the water heater, see Figure 19.

G. Close the panel on the control box. Make sure that the access

panel is secured shut.

9. The blower discharge boot is made to accept only straight sections

of 2" pipe. To start off with an elbow, a short section of the furnished
pipe, a minimum of 2 inches, must be cut and glued into the end of
the elbow that will mount on the discharge boot.

INSTALLATION OF VENT SYSTEM

Before beginning installation of piping system thoroughly read the
section of this manual VENT PIPE PREPARATION.

If you are installing your system so that it vents through roof, please
refer to section  titled INSTALLATION OF VERTICAL VENT SYSTEM.

VENT TERMINAL INSTALLATION, SIDEWALL

1. Install the vent terminal by using the cover plate as a template to

mark the hole for the vent pipe to pass through the wall.  BEWARE
OF CONCEALED WIRING AND PIPING INSIDE THE WALL.

2. If the Vent Terminal is being installed on the outside of a finished wall, it

may be easier to mark both the inside and outside wall. Align the holes
by drilling a hole through the center of the template from the inside
through to the outside. The template can now be positioned on the
outside wall using the drilled hole as a centering point for the template.

3. A)  MASONRY SIDE WALLS

Chisel an opening approximately one half inch larger than the
marked circle.

B)  WOODEN SIDE WALLS
Drill a pilot  hole approximately one quarter inch outside of the marked
circle. This pilot hole is used as a starting point for a saws-all or sabre
saw blade. Cut around the marked circle staying approximately one
quarter inch outside of the line. (This will allow the vent to easily slide
through the opening.  The resulting gap will be covered up by the
Vent Terminal cover plate.) Repeat this step on inside wall if necessary.

SEQUENCE OF INSTALLATIONS, FIGURE 18

Cut a length of PVC pipe about 3.5 inches longer than the wall thickness at
the opening. Glue the vent terminal to this section of pipe. Slide the wall
plate over the pipe to stop against the vent terminal. Place a bead of caulking
(not supplied) around the gap between the pipe and cover plate. Apply
enough to fill some of the gap between the pipe and wall. Place some of
the caulking on the back of the plate to hold it against the wall after installation.
If the vent pipe is installed up to the wall, with a coupling on the end against
the wall opening, the pipe with the vent terminal can be prepared for gluing
before inserting through the wall. Slide the pipe through the wall and insert
into the coupling on the other side of the wall, making sure that the vent
terminal ends up pointed in the correct position, see Figure 18.

VENT TERMINATION - FIGURE 18.

Summary of Contents for GP6

Page 1: ...HOT SURFACE IGNITION NOT FOR USE IN MANUFACTURED MOBILE HOMES ALL TECHNICAL AND WARRANTY QUESTIONS SHOULD BE DIRECTED TO THE LOCAL DEALER FROM WHOM THE WATER HEATER WAS PURCHASED IF YOU ARE UNSUCCESS...

Page 2: ...onal Fuel Gas Code as it relates to the installation of gas fired water heaters The qualified installer must also be familiar with the design features of water heaters and have a thorough understandin...

Page 3: ...3 GENERAL SAFETY...

Page 4: ...4 GENERAL SAFETY...

Page 5: ...are going to put the water heater Correct combustion vent action and vent pipe installation are very important in preventing death from possible carbon monoxide poisoning and fires see Figures 1 and 2...

Page 6: ...ontrol Y Control Harness AA Motor Blower CC Condensate Fitting 4 Places Shown D D Plastic Top E E On Off Switch GET TO KNOW YOUR WATER HEATER GAS MODELS A Vent Pipe B Anode C Hot Water Outlet D Outlet...

Page 7: ...an others These include the elderly children the infirm or physically mentally handicapped If anyone using hot water in your home fits into one of these groups or if there is a local code or state law...

Page 8: ...n locations where leakage may result in property damage even with the use of a drain pan piped to a drain However unanticipated damage can be reduced or prevented by a leak detector or water shut off...

Page 9: ...xceeds the Energy Policy Act standards with respect to insulation and standby loss requirements making an insulation blanket unnecessary Should you choose to apply an insulation blanket to this heater...

Page 10: ...with the outdoors or spaces crawl or attic that freely communicate with the outdoors 1 When directly communicating with the outdoors each opening shall have a minimum free area of 1 square inch per 4...

Page 11: ...ride water softener salt waxes and process chemicals are typical compounds which are potentially corrosive Do not store products of this sort near the heater Also air which is brought in contact with...

Page 12: ...installed directly into the fitting of the water heater designed for the relief valve Position the valve downward and provide tubing so that any discharge will exit only within 6 inches 15 2 cm above...

Page 13: ...water solution not a match or open flame Rinse off soapy solution and wipe dry When installed at elevations above 2 000 feet 610 meters for standard modelsor4 500feet 1 370m forhighaltitudemodels inp...

Page 14: ...stant flow is obtained This will let air out of the water heater and the piping 4 Check all water piping and connections for leaks Repair as needed VENT PIPE ASSEMBLY There are three parts of the vent...

Page 15: ...d twenty eight 128 feet of 4 inch pipe as listed in Table 1 TABLE1 Number of 2 Maximum 3 Maximum 4 Maximum 90 Elbows Pipe Feet Pipe Feet Pipe Feet 1 20 60 120 2 15 55 112 3 10 50 104 4 45 96 5 40 88 6...

Page 16: ...of the unit see figure 16 and from two places on the blower assembly see figure 17 Condensate from this water heater is mildly acidic Please note that some local codes require that condensate is treat...

Page 17: ...connected to the equipment grounding terminal or lead on the water heater see Figure 19 G Close the panel on the control box Make sure that the access panel is secured shut 9 The blower discharge boot...

Page 18: ...AUTION LABEL ALL WIRES PRIOR TO DISCONNECTION WHEN SERVICING CONTROLS WIRING ERRORS CAN CAUSE IMPROPER AND DANGEROUS OPERATION VERIFY PROPER OPERATION AFTER SERVICING POWER VENT WIRING SCHEMATIC FIGUR...

Page 19: ...ON INSTALLATION OF VERTICAL VENT SYSTEM A proper flashing or BOOT should be used to seal the pipe where it exits the roof The total vent system should not exceed the equivalent feet of pipe as listed...

Page 20: ...r tight to prevent any combustion gases escaping into the room If the plug is not securely tightened remove and reinstall using Teflon tape on the threads Once installed along with the rest of the ven...

Page 21: ...e system Air leaks will allow flue gas by products to disseminate into the room creating an unsafe environment and could cause illness asphyxiation and or even death FIGURE 24 Typical Installation for...

Page 22: ...2 cm and above PRIMER It is recommended that Tetrahydrofuran THF be used to prepare the surfaces of pipe and fittings for solvent welding Do not use water rags gasoline or any other substitutes for cl...

Page 23: ...make a second mark as the primer and cement will most likely destroy your first one Apply primer to the surface of the pipe and fitting socket with a natural bristlebrush Thisprocesssoftensandprepares...

Page 24: ...nd HOTTER buttons together and holding for 1 second Then press the COOLER button until the WARM indicator light appears 2 Set the ON OFF switch on the blower control box to the OFF position 3 Turn off...

Page 25: ...allation of thevalves Beforechangingthefactorysettingonthethermostat readthe TemperatureRegulation sectioninthismanual seeFigure26 Never allow small children to use a hot water tap or to draw their ow...

Page 26: ...rod and the water The most common complaint associated with the anode rod is one of a rotten egg smell in the hot water The smell is a result of four factors which must all be present for the odor to...

Page 27: ...DAMAGE Contact a qualified installer or service agency to replace a flooded water heater Do not attempt to repair the unit It must be replaced At least once a year a visual inspection should be made o...

Page 28: ...the temperature pressure relief valve discharge line and 2 that the water discharge will not cause any property damage as the water may be extremely hot see Figure 28 If after manually operating the...

Page 29: ...ose connections or the relief valve DO NOT replace the water heater until a full inspection of all possible water sources is made and necessary corrective steps taken Leakage from other appliances wat...

Page 30: ...ire Screen 4 36 Wall Plate 4 37 Flexible Tubing 38 Reducing Hose Barb Tee REPAIR PARTS LIST Not Shown Optional Now that you have purchased this water heater should a need ever exist for repair parts o...

Page 31: ...ed Error in the hot surface igniter circuit 1 Check that all wiring is correct and secure 2 Replace hot surface igniter System in lockout 1 Gas supply is off or too low to operate 2 Hot surface ignite...

Page 32: ...tch condensation see Figure 1 Improperly sealed hot or cold supply connections relief valve drain valve or thermostat threads Check for leaks at all condensate points See Figure 1 Also see LEAK CHECKP...

Page 33: ...33 NOTES...

Page 34: ...34 NOTES...

Page 35: ...of it in a modified form or any attempt to repair tank leaks or parts will void this warranty SERVICE AND LABOR RESPONSIBILITY UNDER THIS LIMITED WARRANTY THE WARRANTOR WILL PROVIDE ONLY A REPLACEMEN...

Page 36: ...36...

Reviews: