background image

38

57D0215

380IDV/490IDV Fireplace Insert

NOte ReGARDING VeNteD PRODuctS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
Any  residence  with  a  direct  vent  product  must  have  a  CO 

detector installed in the residence.
Installation  of  the  fireplace  or  vented  gas  log  in  the  State  of 

Massachusetts requires the damper to be permanently removed 

or welded in the fully open position.
In addition, a naturally vented gas log may not be installed in a 

bedroom or bathroom in the State of Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve. 

NOte ReGARDING VeNt FRee PRODuctS

This product must be installed by a licensed plumber or gas fitter 

when installed within the Commonwealth of Massachusetts.
In  addition,  vent  free  products  may  not  be  installed  in  a 

bedroom or bathroom regardless of size or type in the State of 

Massachusetts.
Flex line installation must not exceed 36 inches and must have 

a T shutoff valve.

cARBON MONOxIDe DetectOR RequIReMeNtS

(2) Revise  10.8.3  by  adding  the  following  additional 

requirements:
(a)  

For  all  side  wall  horizontally  vented  gas  fueled 

equipment installed in every dwelling, building or structure used 

in  whole  or  in  part  for  residential  purposes,  including  those 

owned or operated by the Commonwealth and where the side 

wall exhaust vent termination is less than seven (7) feet above 

finished  grade  in  the  area  of  the  venting,  including  but  not 

limited to decks and porches, the following requirements shall 

be satisfied:
1. 

Installation  of  carbon  monoxide  detectors. 

At  the  time 

of  installation  of  the  side  wall  horizontal  vented  gas  fueled 

equipment,  the  installing  plumber  or  gas  fitter  shall  observe 

that a hard wired carbon monoxide detector with an alarm and 

battery  back-up  is  installed  on  the  floor  level  where  the  gas 

equipment is to be installed. In addition, the installing plumber 

or gas fitter shall observe that a battery operated or hard wired 

carbon  monoxide  detector  with  an  alarm  is  installed  on  each 

additional level of the dwelling, building or structure served by 

the side wall horizontal vented gas fueled equipment. It shall be 

the responsibility of the property owner to secure the services of 

qualified licensed professionals for the installation of hard wired 

carbon monoxide detectors
 

a.  In the event that the side wall horizontally vented gas 

fueled equipment is installed in a crawl space or an attic, the 

hard  wired  carbon  monoxide  detector  with  alarm  and  battery 

back-up may be installed on the next adjacent floor level.
 

b.  In the event that the requirements of this subdivision 

can  not  be  met  at  the  time  of  completion  of  installation,  the 

owner shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said thirty 

(30) day period, a battery operated carbon monoxide detector 

with an alarm shall be installed.

Massachusetts Residents Only — Please read and follow these special requirements

2. 

Approved  carbon  Monoxide  Detectors.

 

Each  carbon 

monoxide detector as required in accordance with the above 

provisions shall comply with NFPA 720 and be ANSI/UL 2034 

listed and IAS certified.
3. 

Signage.

  A  metal  or  plastic  identification  plate  shall  be 

permanently  mounted  to  the  exterior  of  the  building  at  a 

minimum height of eight (8) feet above grade directly in line with 

the exhaust vent terminal for the horizontally vented gas fueled 

heating appliance or equipment. The sign shall read, in print size 

no less than one-half (1/2) inch in size, “GAS VENT DIRECTLY 

BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS.”
4. 

Inspection.

 The state or local gas inspector of the side wall 

horizontally vented gas fueled equipment shall not approve the 

installation  unless,  upon  inspection,  the  inspector  observes 

carbon monoxide detectors and signage installed in accordance 

with the provisions of 248 CMR 5.08(2)(a)1 through 4.
(b) 

exemptions:

 The following equipment is exempt from 248 

CMR 5.08(2)(a)1 through 4:
1. The equipment listed in Chapter 10 entitled "Equipment Not 

Required To Be Vented" in the most current edition of NFPA 54 

as adopted by the Board; and
2.  Product Approved  side  wall  horizontally  vented  gas  fueled 

equipment  installed  in  a  room  or  structure  separate  from  the 

dwelling,  building  or  structure  used  in  whole  or  in  part  for 

residential purposes.
(c)  

Manufacturer requirements — Gas equipment Venting 

System  Provided.

 

When  the  manufacturer  of  Product 

Approved side wall horizontally vented gas equipment provides 

a  venting  system  design  or  venting  system  components  with 

the equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system shall 

include:
1. Detailed instructions for the installation of the venting system 

design or the venting system components; and
2. A complete parts list for the venting system design or venting 

system.
(d) 

Manufacturer requirements — Gas equipment Venting 

System Not Provided. 

When the manufacturer of a Product 

Approved  side  wall  horizontally  vented  gas  fueled  equipment 

does  not  provide  the  parts  for  venting  the  flue  gases,  but 

identifies “special venting systems,” the following requirements 

shall be satisfied by the manufacturer:
1.  The  referenced  "special  venting  system"  instructions  shall 

be  included  with  the  appliance  or  equipment  installation 

instructions; and
2. The “special venting systems” shall be Product Approved by 

the Board, and the instructions for that system shall include a 

parts list and detailed installation instructions.
(e)  

A  copy  of  all  installation  instructions  for  all  Product 

Approved side wall horizontally vented gas fueled equipment, 

all  venting  instructions,  all  parts  lists  for  venting  instructions, 

and/or all venting design

Summary of Contents for 380IDVNV

Page 1: ...anual For assistance or additional information consult a qualified installer service agency or the gas supplier This appliance may be installed in an aftermarket permanently located manufactured home...

Page 2: ...ation 22 Door and Filigree Installation 24 Operating Instructions 25 What To Do If You Smell Gas 25 Lighting Pilot for the First Time 25 Lighting Pilot 26 Lighting Burner 27 To Turn Off Gas 27 Adjust...

Page 3: ...ified service person The glass door must be properly seated and sealed If this unit is not properly installed by a qualified service person with glass door prop erly seated and sealed combustion leaka...

Page 4: ...se appliances have been tested by CSA and found to comply with the established standards for DIRECT VENT GAS FIREPLACE HEATERS in the USA and Canada as follows LISTED VENTED GAS FIREPLACE HEATER TESTE...

Page 5: ...ocal codes Aftermarket Completion of sale not for purpose of resale from the manufacturer HIGH ELEVATIONS Input ratings are shown in BTU per hour and are certified without deration for elevations up t...

Page 6: ...zn 500 mm E 10C 264 mm 11Z x 292 mm F 29Z x 749 mm 33 838 mm G 15 zn 395 mm 17Z x 445 mm H 20C v 527 mm 22C v 578 mm I 21B 549 mm 23ZC zn 605 mm J 22C v 578 mm 24ZB zn 633 mm K 16B zn 414 mm 18B zn 4...

Page 7: ...s CodeANSI Z233 1 NFPA54 current edition the Uniform Mechanical Code current edi tion and Local Building Codes for specific installation requirements IMPORTANT Your direct vent insert was designed to...

Page 8: ...in this manual HEARTH REQUIREMENTS The insert must be installed on a noncombustible hearth extending a minimum of 12 from the fireplace opening local codes may require a larger hearth The hearth must...

Page 9: ...e of the large amount of heat this appliance pro duces when determining a location FP2624 insert placement Figure 5 Insert Placement For tight fits you may remove the manifold Refer to Remove the Mani...

Page 10: ...your room is well ventilated OPEN ALL WINDOWS DURING INITIAL BURN OFF CURING PHASE Burn your insert for at least six 6 hours on HIGH the first time you use it Place the fan in the OFF position during...

Page 11: ...nting system Installation of any component part not manufactured or approved by Vermont Castings Group Installation other than permitted by these instruc tions WARNING Failure to follow these instruct...

Page 12: ...just air shutter properly may lead to improper combustion which can create a safety hazard Consult your dealer or installer if you suspect an improperly adjusted air shutter WARNING High Temp Silicone...

Page 13: ...ero clearance fireplace FP2627 inlet exhaust reline Exhaust Inlet Recommended block off plate noncombustible metal Prevents odors from chimney entering room UL 127 Solid Fuel Z C Fire box Figure 9 Inl...

Page 14: ...h Flex Vent to Manifold 4 Attach flex vent to manifold Figure 11 Seal with silicone and attach with screws FP2631 pull excess vent Excess Flex Vent Chimney Slack in Flex Vent Manifold FP2632 Figure 12...

Page 15: ...ULATOR External Regual tor Vent Pointing Down 100 gal min Propane LP Supply Tank FP1930 Figure 14 External Regulator with Vent Pointing Down Propane LP Only CAUTION Use only new black iron or steel pi...

Page 16: ...Check your building codes for any special requirements for locating equipment shutoff valve to inserts Apply pipe joint sealant lightly to threads This will prevent excess sealant from going into pipe...

Page 17: ...sniffer 4 To adjust flame height turn HI LO knob to HI to get maximum pressure to burner Turn HI LO knob to LO to get minimum pressure 5 To check gas pressures at valve turn captured screw counter clo...

Page 18: ...l connections should only be per formed by a qualified licensed electrician Main power must be off when connecting to main electrical power supply or performing service All wiring shall be in complian...

Page 19: ...ver add additional logs or embellishments such as pine cones or vermiculite to the heater Only use the logs supplied with the unit Failure to position the parts in accordance with diagrams below or to...

Page 20: ...l left base log Figure 20 LG766 rockwool Left Front Log 2 LG768 Figure 20 6 Align holes in bottom of right base log 3 with two 2 to the right of rear log Figure 21 7 Align hole in bottom left center l...

Page 21: ...5 Right Center Log 5 LG771 Figure 23 9 Place one end of right top log 6 on cutout of right base log Align opposite end on right center log Figure 24 10 Lay top Y log 7 across rear log and center logs...

Page 22: ...4 attach eyebrow Surround Screws Eyebrow Figure 26 KT1334 KT1335 install surround Insert Hooks KT1335 Figure 27 3 Install glass frame cover by aligning four 4 hooks on back of glass frame cover with t...

Page 23: ...634 install beveled surround Beveled Surround Screws FP2634 Installing On Off switch 1 After installing surround disconnect the on off switch from wires leading from heater 2 Insert switch into hole i...

Page 24: ...shoulder screws located on the bottom of the surround Figure 34 NOTICE Remove all fingerprints from facing with a 50 50 vinegar and water solution before lighting the heater Any fingerprints left on...

Page 25: ...ed service technician Force or attempted repair may result in a fire or explosion D Do not use this appliance if any part of it has been under water Immediately call a qualified service technician to...

Page 26: ...1 and 2 Lighting pilot Pilot Position Check for gas leaks in each of the following locations Pipe from the gas supply line connection to the gas valve Burner connections Field made joints gas shutoff...

Page 27: ...urner Depress and turn the knob counterclockwise to the ON position It will take less than four 4 seconds for the burner to ignite Pilot position Depress and turn knob to pilot position to keep burner...

Page 28: ...ion at sea level The burner on Natural Gas models may be adjusted for high altitude as follows To increase air mixture open the shutter more This will reduce soot formation Figure 36 To decrease air m...

Page 29: ...2 Carefully remove broken glass 3 Slide new glass frame back down onto insert and fasten two latches Figure 38 FP2639 remove glass Latches FP2639 Figure 38 Glass Frame Removal Glass Frame WARNING HOT...

Page 30: ...film on the glass This is a temporary problem You should clean the glass after the first two weeks of use After that you should clean the glass no more than two or three times a season Use a mild glas...

Page 31: ...ely before cleaning Logs reach high tempera tures Make sure clearances to combustibles leave enough room for maintenance and service Carefully reassemble and reseal insert properly after any cleaning...

Page 32: ...f exces sive sooting is found heater must be adjusted Contact dealer where you bought heater 4 Clean burner and burner ports Figure 42 5 Replace log set and rock wool per instructions on Pages 19 21 R...

Page 33: ...connections are good but there is no spark 2 Check for spark arcing from the elec trode to pilot Adjust and retighten 1 Check for proper connection of ther mocouple to rear of valve 2 Bleed line Cont...

Page 34: ...1D0203 White Hi Temp FP1946 blower wiring diagram Blower Snap Disc Variable Speed Control Hi Temp Hi Temp OFF ON 1 2 110 115 V AC Blower Plug Black White Green Blower Motor FP1946 NOTE Unplug power co...

Page 35: ...57D0215 380IDV 490IDV Fireplace Insert 35 REPLACEMENT PARTS 1 2 3 4 6 5 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 570016 IDV parts...

Page 36: ...0163 48D0163 48D0163 48D0163 17 Hex Bushing 1 2 x 3 8 1 57D0007 57D0007 57D0007 57D0007 18 Nipple 3 8 x 1 50 1 P1012 P1012 P1012 P1012 19 Disk Bracket 1 26D3320 26D3320 26D3320 26D3320 20 Rear Log 1 1...

Page 37: ...57D0215 380IDV 490IDV Fireplace Insert 37...

Page 38: ...ly with the above requirements provided however that during said thirty 30 day period a battery operated carbon monoxide detector with an alarm shall be installed Massachusetts Residents Only Please r...

Page 39: ...Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and does not extend to 1 firebox burner...

Page 40: ...ochure les caract ristique de rendement nerg tique de foyer au gaz nerguide Selon CSA P 4 1 09 Efficiency Ratings Model EnerGuide Ratings Fireplace Efficiency 380IDVNV 69 6 380IDVPV 66 2 490IDVNV 69 8...

Reviews: