background image

4

CDVZ Series Direct Vent Gas Fireplace

20014621

Requirements  for  the  Commonwealth  of 

Massachusetts

All gas fitting and installation of this heater shall only be 

done by a licensed gas fitter or licensed plumber.
For all side wall horizontally vented gas fueled equipment 

installed in every dwelling, building or structure used in whole 

or in part for residential purposes, including those owned 

or operated by the Commonwealth and where the side wall 

exhaust vent termination is less than seven (7) feet above 

finished grade in the area of the venting, including but not 

limited to decks and porches, the following requirements 

shall be satisfied:

Installation of Carbon Monoxide Detectors

At the time of installation of the side wall horizontal vented 

gas fueled equipment, the installing plumber or gas fitter 

shall observe that a hard wired carbon monoxide detector 

with an alarm is installed on each additional level of the 

dwelling,  building  or  structure  served  by  the  side  wall 

horizontal  vented  gas  fueled  equipment.  It  shall  be  the 

responsibility of the property owner to secure the services 

of  qualified  licensed  professionals  for  the  installation  of 

hard wired carbon monoxide detectors.
In the event that the side wall horizontally vented gas fueled 

equipment is installed in a crawl space or an attic, the hard 

wired carbon monoxide detector with alarm and battery 

back-up may be installed on the next adjacent floor level.
In the event that the requirements of this subdivision can not 

be met at the time of completion of installation, the owner 

shall have a period of thirty (30) days to comply with the 

above requirements; provided, however, that during said 

thirty (30) day period, a battery operated carbon monoxide 

detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors

Each carbon monoxide detector as required in accordance 

with the above provisions shall comply with NFPA 720 and 

ANSI/UL 2034 listed and IAS certified.

Signage

A metal or plastic identification plate shall be permanently 

mounted to the exterior of the building at a minimum height 

of eight (8) feet above grade directly in line with the exhaust 

vent terminal for the horizontally vented gas fueled heating 

appliance or equipment. The sign shall read, in print size no 

less than one-half (1/2) inch in size, 

“GAS VENT DIRECTLY 

BELOW, KEEP CLEAR OF ALL OBSTRUCTIONS”.

Inspection

The state or local gas inspector of the side wall horizontally 

vented  gas  fueled  equipment  shall  not  approve  the 

installation unless, upon inspection, the inspector observes 

carbon  monoxide  detectors  and  signage  installed  in 

accordance with the provisions of 248 CMR 5.08(2)(a)1 

through 4.

Exemptions

The  following  equipment  is  exempt  from  248  CMR 

5.08(2)(a)1 through 4:

• 

The equipment listed in Chapter 10 entitled “Equipment 

Not Required To Be Vented” in the most current edition 

of NFPA 54 as adopted by the Board; and

• 

Product Approved side wall horizontally vented gas fueled 

equipment installed in a room or structure separate from 

the dwelling, building or structure used in whole or in 

part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided

When  the  manufacturer  of  Product Approved  side  wall 

horizontally  vented  gas  equipment  provides  a  venting 

system  design  or  venting  system  components  with  the 

equipment, the instructions provided by the manufacturer 

for installation of the equipment and the venting system 

shall include:

• 

Detailed instructions for the installation of the venting 

system  design  or  the  venting  system  components; 

and

• 

A complete parts list for the venting system design or 

venting system.

Gas Equipment Venting System NOT Provided

When the manufacturer of a Product Approved side wall 

horizontally vented gas fueled equipment does not provide 

the parts for venting the flue gases, but identifies “special 

venting  systems”,  the  following  requirements  shall  be 

satisfied by the manufacturer:

• 

The referenced “special venting system” instructions shall 

be included with the appliance or equipment installation 

instructions; and

• 

The  “special  venting  systems”  shall  be  Product 

Approved by the Board, and the instructions for that 

system shall include a parts list and detailed installation 

instructions.

A copy of all installation instructions for all Product Approved 

side  wall  horizontally  vented  gas  fueled  equipment,  all 

venting instructions, all parts lists for venting instructions, 

and/or  all  venting  design  instructions  shall  remain  with 

the  appliance  or  equipment  at  the  completion  of  the 

installation.

Installation & Operating Instructions

Summary of Contents for 36CDVZRRN

Page 1: ...ourneighbor sphone Follow the gas suppliers instructions If you cannot reach your gas supplier call the fire department WARNING IF THE INFORMATION IN THIS MANUAL IS NOT FOLLOWED E X A C T LY A F I R E...

Page 2: ...tion Assembling Vent Pipes 12 36CDVZR Venting How to Use the Vent Graph 13 Rear Wall Venting Applications Installation Exterior outside wall 7 20 from rear of unit 13 Rear Wall Vent Installation Flex...

Page 3: ...r wood panel extending the full width and depth of the fireplace 13 This fireplace requires adequate ventilation and combustion air to operate properly 14 Thisfireplacemustnotbeconnectedtoachimneyflue...

Page 4: ...tally vented gas fueled heating appliance or equipment The sign shall read in print size no lessthanone half 1 2 inchinsize GASVENTDIRECTLY BELOW KEEP CLEAR OF ALL OBSTRUCTIONS Inspection The state or...

Page 5: ...Gas Line Access Gas Line Access Low Voltage Electrical Access Electrical Access 33 838 mm C L Centerline of 7 Collar 856O 216 mm Low Voltage Access 1 6 35 mm 7 6 187 mm 856O 216 mm 3256 816 mm 14 356...

Page 6: ...ccess Low Voltage Electrical Access Electrical Access 33 838 mm 856O 216 mm Low Voltage Access 1 6 35 mm 7 6 187 mm 856O 216 mm 3256 816 mm 14 356 mm 10175 CDVT specs 1 06 8 203 mm 2 9 5 6 7 4 0 m m 4...

Page 7: ...01 sta Black Surround Face CFM170 DV Builder Front View O N M L K Side of Combustion Chamber CFM164a Mantel Mantel Leg FromSide Ref Leg Depth Ref of Comb Opening F 10 254 mm K 11 292 mm G 8 203 mm L...

Page 8: ...s yields a 5 8 16 mm thick drywall space Removing the standoff and having the tabs on the standoff face the rear of the unit yields a 3 4 19 mm drywall space Fig 5 NOTE Drywall must stop at standoffs...

Page 9: ...tallation and testing of any gas connection It is most convenient to bring the gas line in from the rear right side of the valve as this allows fan installation or removal without disconnecting the ga...

Page 10: ...l Black and red are line voltage to each plug on the receptacle FP1597 Fig 9 Electric receptacle FP1597 receptacle install 12 05 OUTSIDE INSIDE BACK OF UNIT Electric Receptacle Electric Receptacle Cov...

Page 11: ...let 3 91cm 3 91cm J Clearance to nonmechanical air supply inlet 6 15cm for appliances 10 000 6 15cm for appliances to building or the combustion air inlet to any Btuh 3kW 12 30cm for 10 000 Btuh 3kW 9...

Page 12: ...x vent Hose Clamp Apply High Tempera ture Sealant FP1471a Fig 12 Apply high temperature sealant to 4 and 7 pipes Outside Corner Inside Corner Termination Clearances Termination clearances for building...

Page 13: ...Exterior Outside Wall 7 178 mm to 20 508 mm From Rear of Unit With this application the following rigid pipe kits may be used 7 to 13 178 330 mm to outside wall 7TCRVT 13 to 20 330 305 mm to outside w...

Page 14: ...rough the exterior wall and frame as shown Noncombustible Walls Fig 17 Hole opening must be 7 190 mm in diameter STEP 2 Install interior firestop as shown in Figure 18 STEP 3 Remove telescoping collar...

Page 15: ...C L to Floor 2956O 749 mm Termination Flex Section Appliance Collars FP1473 Fig 20 Grasp the vent pipe close to the collar and bend to 45 angle Do not exceed 45 5 Insert the collar on the flex vent t...

Page 16: ...mm off the floor 24Z x 622 mm 13 20 330 508 mm 3 Proceed with Step 3 of Rear Wall Vent Application Exterior Outside Wall 20 to 32 508 813 mm from Rear of Unit section below Rear Wall Vent Application...

Page 17: ...means no vertical rise exists on this por tion of the vent assembly The maximum horizontal vent run is 20 ft 6 1 m when the vertical vent rise is 7 ft 2 3 m Fig 26 The maximum number of 90 elbows per...

Page 18: ...gh tab into outer casing Fig 30 8 CFM143 2 2 01 sta Ensure Pipes are Concentric CFM143a Fig 30 Always start vertical run with 7TCDV90 on 36CDVR unts 7TCDV90 STEP 3 Measure the horizontal length requir...

Page 19: ...ecommend a window well with adequate and proper drainage Ensure sidewall venting clearances are observed The maximum horizontal run with 24 vertical rise is 36 914 mm from the back of the fireplace to...

Page 20: ...l runs Example Maximum horizontal length 0 x 45 elbows 10 3 m 1 x 45 elbows 8 2 6 m 2 x 45 elbows 7 2 1 m 3 A minimum of an 8 vertical rise 4 Two sets of 45 elbows offsets within these vertical instal...

Page 21: ...nstallappropriatepipesectionsuntiltheventingisabove the flashing Fig 40 9 Install storm collar and seal around the pipe 10 Add additional vent lengths for proper height Fig 41 TWL101a Twist Lock Pipe...

Page 22: ...ons for a Direct Vent flue system Vertical dimension from the floor of the unit to the center of the horizontal vent pipe 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 3...

Page 23: ...se is 36 914 mm If a 90 elbow is used in the horizontal vent run level height maintained the maximum horizontal vent length is reduced by 36 914 mm This does not ap ply if the 90 elbows are used to in...

Page 24: ...fixed andinstallthehorizontalventsections Thesectionswhich go through the wall are packaged with the starter kit and can be cut to suit if necessary Fig 48 Sealing the gaps between the vent pipe and...

Page 25: ...the Sidewall Vent Graphforextendedhorizontalruniftheverticalriseexceeds 24 610 mm 1 Establish vent hole through the wall Page 14 Fig 17 2 Remove soil to a depth of approximately 16 406 mm below base...

Page 26: ...1 x 45 elbows 8 2 6 m 2 x 45 elbows 7 2 1 m A minimum of an 8 2 4 m vertical rise Max 10 3m Max Height 40 12m Min Height 756O 2 3m FP1244 through the roof max min dims 12 02 Pipe Straps Every 3 914mm...

Page 27: ...er height Fig 60 11 Apply high temperature sealant to 4 and 7 collars CFM110 Typical ceiling roof support 10 90 Typical Roof Support Application Typical Ceiling Sup port Application CFM110 Fig 58 Roof...

Page 28: ...tthebottom lift the window frame assembly up and away from the fireplace 6 To replace the window frame assembly reverse the procedure Glass Cleaning It is necessary to periodically clean glass During...

Page 29: ...er flames Compare them to the illustrations Figs 65 66 If the flame patterns appear abnormal contact a qualified service provider for service and adjustment Flame Characteristics L O H I FP390 FLAME A...

Page 30: ...ese instructions exactly B BEFORE LIGHTING smell all around the heater area for gas Be sure to smell next to the floor because some gas is heavier than air and will settle on the floor WHAT TO DO IF Y...

Page 31: ...air it call a qualified service technician Force or attempting repair may result in a fire or explosion D Do not use this appliance if any part has been under water Immediately call a qualified servic...

Page 32: ...er wire across terminals at wall switch if burner comes on replace defective wall switch If okay jumper wires across wall switch wires at valve if burner comes on wires are faulty or connections are b...

Page 33: ...FC111 Fig 70 Remove orifice from brass elbow AIR SHUTTER DJT Air Shutter Adjustment Screw LP Fully Open NG 1 8 Open FC112 Fig 71 Adjust air shutter 8 Install the new conversion orifice 9 Loosen the a...

Page 34: ...place with conversion orifice 3 Install the enclosed identification label F to the valve body where it can be easily seen Testing for Leaks 1 Apply gas to the system and light the pilot 2 With a soapy...

Page 35: ...ckup and cleaning and some may require adjustment If repair is necessary it should be performed by a qualified technician 1 Turn off pilot light at gas valve 2 Allow fireplace to cool if it has been o...

Page 36: ...0012251 1b Log Middle Assy 20012108 2 Hood 20010312 3 Burner Tube 20010333 4 Orifice Burner Natural not shown 72386 5a Orifice Pilot Natural not shown 10002268 5b Orifice Pilot Propane not shown 10002...

Page 37: ...Electrical Cord 6 ft 51865 18 Door Assy 20010207 19 Frame Window 20010320 20 Clamp Frame Window 10000949 21 Clean Face Panel 20014132 22 Valve Access Panel 20014134 23 Grommet 20010348 24 Wire Bushin...

Page 38: ...DVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe 30 pack 7TDVP48 30 Twist Lock Elbows 45 Elbow for Vertical Horizontal Offset 7TDV45 45 Elbow for Vertical Offsets 8 pack 7TDV45...

Page 39: ...ble Vent Length 7TDVP3564 8 Vent Pipe 4 pack 7TDVP8 4 12 Vent Pipe 4 pack 7TDVP12 4 24 Vent Pipe 4 pack 7TDVP24 4 36 Vent Pipe 7TDVP36 36 Vent Pipe 30 pack 7TDVP36 30 48 Vent Pipe 7TDVP48 48 Vent Pipe...

Page 40: ...T 4 4D24 3 6 36 Pipe Length galvanized 46DVA 36 903 4DT 36 4D36 3 6 48 Pipe Length galvanized 46DVA 48 902 4DT 48 4D48 4 6 81 2 Pipe Extension galvanized 46DVA 08A 4DT AJ 4 6 16 Pipe Extension galvani...

Page 41: ...the strips to the metal panels No further securing is required 3 Powertothefancanbesuppliedbypluggingthesupplied lead into a conveniently located wall socket or by using the receptacle in the bottom...

Page 42: ...42 CDVZ Series Direct Vent Gas Fireplace 20014621...

Page 43: ...he installation instructions The Limited Lifetime Warranty will also be void if the appliance is not operated and maintained according to the operating instructions supplied with the appliance and doe...

Page 44: ...63 36CDVZRRP 66 9 77 78 63 36CDVZTRN 57 76 76 5 63 36CDVZTRP 57 77 78 63 Based on CSA P 4 1 09 Based on CSA P 4 1 09 Recherchez dans la brochure les caract ristique de rendement nerg tique de foyer au...

Reviews: