Table A-1
Veritas 5150 Appliance technical specifications
(continued)
Veritas 5150 Appliance
Technical Specification
Specification: IEC-60320-C14 to IEC-60320-C13, 10A/250V,
Black, 4 ft
The IEC-60320-C14 plugs into a Power Distribution Unit.
The IEC-60320-C13 plugs into an appliance power supply.
Note:
If your power distribution unit is not compatible with
the IEC-60320-C14 plug, then Veritas recommends that
you purchase your power cable locally. Make sure the
power cable meets or exceed the indicated power rating.
See
on page 23.
AC power cable
50/60Hz
AC Frequency range
180 watts
Typical power consumption
400 watts
Maximum power consumption
180 watts (typical) - 614 BTU/hr
400 watts (maximum) - 1365 BTU/hr
System cooling requirement
(heat dissipation)
100 - 127 VAC
200 - 240 VAC
Operating voltage
90% +
Power conversion efficiency
70 dBA
Acoustic noise
See
“Environmental specifications”
on page 30.
Environmental specifications
The following table lists the environmental specifications for the Veritas 5150
Appliance.
Table A-2
Veritas 5150 Appliance environmental specifications
Veritas 5150 Appliance
Specification
ASHRAE A2 - from 10°C to 35°C with the maximum rate of
change not to exceed 10°C per hour
ASHRAE A3 - up to 40°C for up to 900 hours per year
ASHRAE A4 - up to 45°C for 90 hours per year
Operating temperature
30
Technical specifications and compliance standards