E50C1A Installation Guide

The meter has a number of different possible system wiring configurations (see Wiring Diagrams, page 5). To configure the meter, 
set the System Type via the User Interface or Modbus register 130  (if so equipped). The System Type tells the meter which of its 
current and voltage inputs are valid, which are to be ignored, and if neutral is connected. Setting the correct System Type prevents 
unwanted energy accumulation on unused inputs, selects the formula to calculate the Theoretical Maximum System Power, 
and determines which phase loss algorithm is to be used. The phase loss algorithm is configured as a percent of the Line-to-Line 
System Voltage (except when in System Type 10) and also calculates the expected Line to Neutral voltages for system types that  
have Neutral (12 & 40).

Values that are not valid in a particular System Type will display as “----” on the User Interface or as QNAN in the Modbus registers.

CTs

Voltage Connections

System Type

Phase Loss Measurements

Wiring 

Diagram

Number 

of wires

Qty

ID

Qty

ID

Type

Modbus 

Register 130

User Interface: 

SETUP>S SYS

VLL

VLN

Balance

Diagram 

number

Single-Phase Wiring
2

1

A

2

A, N

L-N

10

1L + 1n

AN

1

2

1

A

2

A, B

L-L

11

2L

AB

2

3

2

A, B

3

A, B, N

L-L with N 12

2L + 1n

AB

AN, BN

AN-BN

3

Three-Phase Wiring
3

3

A, B, C 3

A, B, C

Delta

31

3L

AB, BC, CA

AB-BC-CA

4

4

3

A, B, C 4

A, B, C, N Grounded 

Wye

40

3L + 1n

AB, BC, CA

AN, BN, CN AN-BN-CN & 

AB-BC-CA

5, 6

Supported System 
Types

To avoid distortion, use parallel wires for control power and voltage inputs. 

The following symbols are used in the wiring diagrams on the following pages.

Symbol

Description

Voltage Disconnect Switch

Fuse (installer is responsible for ensuring compliance with local requirements. No 

fuses are included with the meter.)

Earth ground

X2

X1

Current Transducer

Potential Transformer

Protection containing a voltage disconnect switch with a fuse or disconnect circuit 

breaker. The protection device must be rated for the available short-circuit current at 

the connection point.

•  This product is designed only for use with E683 Series current transducers (CTs).

•  DO NOT USE CURRENT OUTPUT (e.g. 5A) CTs ON THIS PRODUCT.

Failure to follow these instructions can result in equipment damage.

NOTICE

RISK OF EQUIPMENT DAMAGE

Wiring Symbols

Summary of Contents for E50C1A

Page 1: ...nd if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to...

Page 2: ...529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 AWG 0 2 to 2 1 mm2 Rail T35...

Page 3: ...Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setu...

Page 4: ...VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E50C1A Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3...

Page 5: ...ndicator RS 485EquippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back kWh 1234 5 Alarm Energy Two5 characterrows ofdisplaytext Toprowa...

Page 6: ...35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside Th...

Page 7: ...r System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modb...

Page 8: ...TnoPT UseSystemType11 2L UseSystemType12 2L 1n UseSystemType 31 3L UseSystemType10 1L 1n Wiring RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE CT terminals are referenced to the meter s neutral...

Page 9: ...L L Outputto meetmeterinputrequirements DCControlPowerfrom125Vdcto300Vdc ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For selecting...

Page 10: ...ect the parameter screen you want to set 6 After you set the parameters you want use or to select the next Setup screen or to exit the Setup screens return to SETUP B ToEnterModbuscommunicationparamet...

Page 11: ...powered and no phase loss alarm conditions are present All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect to hazar...

Page 12: ...KWh Accumulated Real Energy Ph SETUP ALERT RESET Back Display nOnE if no alerts To Setup Setup Meter Reset Data Phase Loss A B C Low Power Factor A B C Frequency Out of Range A Current Over Range Vol...

Page 13: ...00 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT in...

Page 14: ...the selection if it cannot find a pulse duration that will allow the pulse output to keep up with Theoretical Maximum System Power see S_PWR screen When moving up to a larger energy the meter will jum...

Page 15: ...47 k pull down to Shield RS 485 signal ground Wire the RS 485 bus as a daisy chain from device to device without any stubs Use 120 termination resistors at each end of the bus not included Shield is...

Page 16: ...status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power Meter Full Data Set or Veris Industries E50xx Power Meter RESET SYSTEM RUNNING RSVersion x xxx last 2 bytes CRC 0x...

Page 17: ...atio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV UInt 82 32000 SystemVoltage This voltage is line to line except for...

Page 18: ...nd a pulse duration that will keep up with the max system power register 135 it will reject the new value Try a larger value kWh Pulse Contacts Note The kWh pulse contact can keep up with a maximum po...

Page 19: ...nge Description 152 R W NV UInt 0 32767 Power Up Counter 153 R NV UInt 0 32767 Output Configuration E50C1 always returns 0 154 R UInt Reserved returns 0 Floating Point Data 257 258 R NV Float kWh Real...

Page 20: ...ct connection to the same service PT polarity and adequate powering See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter...

Reviews: