background image

ZL0124-0E 

Page 18 of 20 

©2018 Veris Industries   USA 800.354.8556 or +1.503.598.4564  / [email protected] 0818 

 

Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Aerospond, Veris, and the Veris ‘V’ logo are trademarks or registered trademarks of  Veris Industries, L.L.C. in the USA and/or other countries.

Other companies’ trademarks are hereby acknowledged to belong to their respective owners.

TM

E50C1A Installation Guide

E50C1 REG.

R/W NV Format

Units

Scale

Range

Description

142

R/W NV UInt

%

1-99

Phase Loss Voltage Threshold in percent of system voltage (register 

134). Default is 10 (%). Any phase (as configured in register 130) 

that drops below this threshold triggers a Phase Loss alert - i.e. 

if the System voltage is set to 480 V L-L, the L-N voltage for each 

phase should be 277 V. When the threshold is set to 10%, if any 

phase drops more than 10% below 277 V, (less than 249 V), or 

if any L-L voltage drops more than 10% below 480 V (less than 

432 V) the corresponding phase loss alarm bit in register 146 will 

be true.   

Phase Loss Output

Note: The phases tested are determined by 

the System Type.

143

R/W NV UInt

%

1-99

Phase Loss Imbalance Threshold in Percent. Default is 25% phase 

to phase difference. For a 3-phase Y (3 + N) system type (40 in 

register 130), both Line to Neutral and Line to Line voltages are 

tested. In a 3-phase Δ System type (31 in register 130), only Line 

to Line voltages are examined. In a single split-phase (2 + N) 

system type (12 in register 130), just the line to neutral voltage 

are compared. 

144

R/W NV UInt

Wh

10000, 
1000, 
100, 
10

Wh (& VARh, if equipped with 

FDS) Energy per Pulse Output 

Contact Closure.  If the meter 

cannot find a pulse duration 

that will keep up with the max. 

system power (register 135), it 

will reject the new value. Try a 

larger value.

kWh Pulse Contacts

Note: The kWh pulse contact can keep up with a maximum power (Watts) of 

1800000 x Wh pulse weight ÷ contact closure duration (in mses)

145

R

NV UInt

ms

500, 
250, 
100, 
50, 
25, 
10

Pulse Contact Closure Duration 

in msec. Read-only. Set to the 

slowest duration that will keep 

up with the theoretical max. 

system power (register 135). 

The open time  ≥ the closure 

time, so the max. pulse rate 

(pulses per sec) is the inverse of 

double the pulse time.

146

R

UInt

Diagnostic Alert Bitmap. 1 = Active:
Bit 0:   Phase A Voltage out of range
Bit 1:   Phase B Voltage out of range
Bit 2:   Phase C Voltage out of range
Bit 3:   Phase A Current out of range
Bit 4:   Phase B Current out of range
Bit 5:   Phase C Current out of range
Bit 6:   Frequency out of the range of 45 – 65 Hz OR there is insufficient voltage to determine frequency.
Bit 7:   Reserved for future use 
Bit 8:   Phase Loss A
Bit 9:   Phase Loss B 
Bit 10: Phase Loss C 
Bit 11:  Low Power Factor on A with one or more phases having a PF less than 0.5 due to mis-wiring of phases
Bit 12:  Low Power Factor on B
Bit 13:  Low Power Factor on C
Bit 14:   Energy pulse output overrun error. The pulse outputs are unable to keep up with the total real power 

(registers 3 and 261/262). To fix, increase the pulse energy register (register 144) and reset the energy 

accumulators (see reset register 129).

Bit 15:  Energy pulse output configuration error (present pulse energy setting may not keep up with the 

theoretical max. system power; see register 135). To fix, increase the pulse energy (register 144).

147

R

NV UInt

0-32767

Count of Energy Accumulator resets

148

R

UInt

Reserved (returns 0)

151

R/W

UInt

1-32767

Reserved (returns 0)

Modbus Point Map (cont.)

Summary of Contents for E50C1A

Page 1: ...nd if not installed and used in accordance with the instruction manual may cause harmful interference to radio communications This device complies with part 15 of the FCC Rules Operation is subject to...

Page 2: ...529 IP40 front display IP20 meter Display Characteristics Back lit blue LCD Terminal Block Screw Torque 0 37 to 0 44 ft lb 0 5 to 0 6 N m Terminal Block Wire Size 24 to 14 AWG 0 2 to 2 1 mm2 Rail T35...

Page 3: ...Installation Guide Table of Contents Dimensions 4 Data Outputs 4 Product Diagram 5 Display Screen Diagram 5 Installation 6 Supported SystemTypes 7 Wiring Symbols 7 Wiring 8 Control Power 9 Quick Setu...

Page 4: ...VerisIndustries L L C intheUSAand orothercountries Othercompanies trademarksareherebyacknowledgedtobelongtotheirrespectiveowners TM E50C1A Installation Guide Dimensions 4 2 107mm 3 6 91mm 1 5 39mm 2 3...

Page 5: ...ndicator RS 485EquippedUnitsOnly TransmitData ReceiveData ReceiveDataError LCDScreen Buttons Up Select Right Next Down Select Left Back kWh 1234 5 Alarm Energy Two5 characterrows ofdisplaytext Toprowa...

Page 6: ...35 mm DIN rail or screw mounted to the interior surface of the enclosure A DINRailMounting 1 Attach the mounting clips to the underside of the housing by sliding them into the slots from the inside Th...

Page 7: ...r System Type will display as on the User Interface or as QNAN in the Modbus registers CTs Voltage Connections SystemType Phase Loss Measurements Wiring Diagram Number of wires Qty ID Qty ID Type Modb...

Page 8: ...TnoPT UseSystemType11 2L UseSystemType12 2L 1n UseSystemType 31 3L UseSystemType10 1L 1n Wiring RISK OF ELECTRIC SHOCK OR PERMANENT EQUIPMENT DAMAGE CT terminals are referenced to the meter s neutral...

Page 9: ...L L Outputto meetmeterinputrequirements DCControlPowerfrom125Vdcto300Vdc ULandCEmax FuseRecommendations Keep the fuses close to the power source obey local and national code requirements For selecting...

Page 10: ...ect the parameter screen you want to set 6 After you set the parameters you want use or to select the next Setup screen or to exit the Setup screens return to SETUP B ToEnterModbuscommunicationparamet...

Page 11: ...powered and no phase loss alarm conditions are present All pulse outputs and communication circuits are only intended to be connected to non hazardous circuits SELV or Class 2 Do not connect to hazar...

Page 12: ...KWh Accumulated Real Energy Ph SETUP ALERT RESET Back Display nOnE if no alerts To Setup Setup Meter Reset Data Phase Loss A B C Low Power Factor A B C Frequency Out of Range A Current Over Range Vol...

Page 13: ...00 SYSTM 3L 1n 3L 2L 1n 2L 1L 1n Back To SETUP Back Back Back S COM To Setup p 2 SPLOS Next S PT Set Potential Transfomer Ratio RATIO Potential transformer step down is RATIO 1 Default is 1 1 No PT in...

Page 14: ...the selection if it cannot find a pulse duration that will allow the pulse output to keep up with Theoretical Maximum System Power see S_PWR screen When moving up to a larger energy the meter will jum...

Page 15: ...47 k pull down to Shield RS 485 signal ground Wire the RS 485 bus as a daisy chain from device to device without any stubs Use 120 termination resistors at each end of the bus not included Shield is...

Page 16: ...status 0x00 if the reset system is used bytes5 ID string Veris Industries E50xx Power Meter Full Data Set or Veris Industries E50xx Power Meter RESET SYSTEM RUNNING RSVersion x xxx last 2 bytes CRC 0x...

Page 17: ...atio of 2 1 The default is 100 1 00 1 which is with no PT attached Set this value before setting the system voltage below 134 R W NV UInt 82 32000 SystemVoltage This voltage is line to line except for...

Page 18: ...nd a pulse duration that will keep up with the max system power register 135 it will reject the new value Try a larger value kWh Pulse Contacts Note The kWh pulse contact can keep up with a maximum po...

Page 19: ...nge Description 152 R W NV UInt 0 32767 Power Up Counter 153 R NV UInt 0 32767 Output Configuration E50C1 always returns 0 154 R UInt Reserved returns 0 Floating Point Data 257 258 R NV Float kWh Real...

Page 20: ...ct connection to the same service PT polarity and adequate powering See theWiring Diagrams section for more information Cannot communicate with power meter from a remote personal computer Power meter...

Reviews: