Timer Mode
Description
Timer Light
mode 1
Timed dwell and
switch off
The timer starts timing when the
actual temperature is within 1 °C
of the setpoint. At the end of the
timing period, control switches
off (i.e. goes into Manual) to
allow cooling and 'End' flashes on
the display.
On while temperature is
reaching setpoint. On during
the timing period. Off from
the end of the timing period.
mode 2
Timed dwell and stay
on
The timer starts timing when the
actual temperature is within 1 °C
of the setpoint. At the end of the
timing period, control remains
on, maintaining the setpoint
temperature and 'End' flashes on
the display
On while temperature is
reaching setpoint. On during
the timing period. Off from
the end of the timing period.
mode 3, with SPrr off
Time from cold and
switch off
The timer starts timing
immediately. At the end of the
timing period, control switches
off (i.e. goes into Manual) to
allow cooling and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 3, with SPrr
active
Dwell from working
setpoint and switch
off
The timer starts timing when the
working setpoint is within 1 °C of
the setpoint. At the end of the
timing period, control switches
off (i.e. goes into Manual) to
allow cooling and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 4, with SPrr off
Time from cold and
stay on
The timer starts timing
immediately. At the end of the
timing period, control remains
on, maintaining the setpoint
temperature and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 4, with SPrr
active
Dwell from working
setpoint and stay on
The timer starts timing when the
working setpoint is within 1 °C of
the setpoint. At the end of the
timing period, control remains
on, maintaining the setpoint
temperature and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 5
Delayed switch on
The timer starts timing
immediately and control starts at
the end of the timing period.
There is no 'End' condition in this
mode.
On during the timing period.
Off from the end of the timing
period.
13
3.0 2132 Controller
Summary of Contents for CARBOLITE GERO SNF
Page 4: ...10 2 Power Settings 38 11 0 Specifications 39 11 1 Environment 39 4 ...
Page 20: ...3 0 2132 Controller 3 7 Navigation Diagram 20 ...
Page 28: ...6 0 Maintenance Power Consumption Measure the current drawn on each phase cir cuit 28 ...
Page 40: ......
Page 41: ...Notes Service Record Engineer Name Date Record of Work ...