5.0 Afterburner 2132 Controller
Timer Mode
Description
Timer Light
mode 1
Timed dwell and
switch off
The timer starts timing when the
actual temperature is within 1 °C
of the setpoint. At the end of the
timing period, control switches
off (i.e. goes into Manual) to
allow cooling and 'End' flashes on
the display.
On while temperature is
reaching setpoint. On during
the timing period. Off from
the end of the timing period.
mode 2
Timed dwell and stay
on
The timer starts timing when the
actual temperature is within 1 °C
of the setpoint. At the end of the
timing period, control remains
on, maintaining the setpoint
temperature and 'End' flashes on
the display
On while temperature is
reaching setpoint. On during
the timing period. Off from
the end of the timing period.
mode 3, with SPrr off
Time from cold and
switch off
The timer starts timing
immediately. At the end of the
timing period, control switches
off (i.e. goes into Manual) to
allow cooling and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 3, with SPrr
active
Dwell from working
setpoint and switch
off
The timer starts timing when the
working setpoint is within 1 °C of
the setpoint. At the end of the
timing period, control switches
off (i.e. goes into Manual) to
allow cooling and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 4, with SPrr off
Time from cold and
stay on
The timer starts timing
immediately. At the end of the
timing period, control remains
on, maintaining the setpoint
temperature and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 4, with SPrr
active
Dwell from working
setpoint and stay on
The timer starts timing when the
working setpoint is within 1 °C of
the setpoint. At the end of the
timing period, control remains
on, maintaining the setpoint
temperature and 'End' flashes on
the display.
On during the timing period.
Off from the end of the timing
period.
mode 5
Delayed switch on
The timer starts timing
immediately and control starts at
the end of the timing period.
There is no 'End' condition in this
mode.
On during the timing period.
Off from the end of the timing
period.
26
Summary of Contents for CARBOLITE GERO ABF 8/28
Page 11: ...Fig 14 Schematic for Mains Electrical Connections 11 3 0 Installation ...
Page 21: ...4 6 Navigation Diagram 21 4 0 2416 Controller ...
Page 33: ...5 7 Navigation Diagram 33 5 0 Afterburner 2132 Controller ...
Page 40: ...7 0 Operation Photo 3 5 40 ...