Verasys® 32 Point 24 VAC Application Controller Installation Instructions
27
Input and Output
Capabilities
Six Universal Inputs:
User-configurable, 3 available modes:
•
Voltage Input: 0 to 10 VDC
•
Current Sense Input: 4 to 20 mA
• Resistive
Inputs/Dry Contact Inputs
12 Binary Inputs:
Defined as Dry Contact maintained or Pulse Counter/Accumulator Mode
Four Configurable Outputs:
User-configurable, 2 available modes:
•
Analog Output: 0 to 10 VDC, 10 mA
•
Triac Output: 24 VAC, 0.5 A (Externally sourced powered)
One Utility Output Power Port (24~ OUT):
Ability to deliver 24 VAC
Four Binary Outputs (Relays):
Single-Pole, Single-Throw. Dry Contacts rated 240 VAC.
•
UL: 240 VAC 5A Resistive, 1.9 LA/11.1LRA, D300 Pilot Duty, 70°C/158°F (30,000 cycles)
•
IEC: 240 VAC 3A Resistive, 3A Inductive, Cos=0.6, -20 to 70°C (-4 to 158°F) (100,000
cycles)
One Binary Outputs (Relays):
Single-Pole, Double-Throw, Dry Contacts rated 240 VAC
•
UL: 240 VAC 5A Resistive, 1.9 LA/11.1LRA, D300 Pilot Duty, 70°C/158°F (30,000 cycles)
•
IEC: 240 VAC 3A Resistive, 3A Inductive, Cos=0.6, -20 to 70°C (-4 to 158°F)
(100,000 cycles)
One PWM Output Port:
5V, 12V, 15V selectable PWM output voltage, 10 mA (maximum)
continuous current, 100 Hz
Note:
Reference all relay commons to the same pole of the supply circuit.
Four Binary Outputs (Triacs):
Output: 24 VAC or 240 VAC, 0.5 A (externally powered).
Note:
Reference all triac commons to the same pole of the supply circuit.
Analog Input/Analog
Output Resolution and
Accuracy
Analog Input: 12-bit resolution Analog Output: 15-bit resolution, +/- 200 mV accuracy in 0 to
10 VDC applications
Terminations
Input/Output: Fixed Spade terminals
Sensor/System/Modbus: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks
Sensor Bus Tool Port: RJ-12 6-Pin Modular Jack
Field Install Option:
Input/Output: Fixed Solder terminals
Sensor/System/Modbus: 4-Wire and 3-Wire Pluggable Screw Terminal Blocks
Sensor Bus Tool Port: RJ-12 6-Pin Modular Jack
See Table 7 for Number of Cycles and Electrical Ratings
Mounting
Horizontal on single 35 mm DIN rail mount (preferred), or screw mount on flat surface with
three integral mounting clips on controller.
Mount the Verasys Controllers on a wall or DIN rail inside an enclosure (rated at least IP20).
Housing
Enclosure material: Polycarbonate LEXAN
®
SABIC EXL9330
Dimensions
(H x W x D)
220 mm x 125 mm x 58 mm (8.66 in. x 4.92 in. x 2.28 in.)
Weight
0.5 kg (1.1 lb)
Compliance
United States:
cULus Listed, File E107041, CCN PAZX, UL 916, Energy Management
Equipment
FCC Compliant to CRF47, Part 15, Subpart B, Class A
Canada:
cULus Listed, File E107041, CNN PAZX7 CAN/CSA C22.2 No.205, Signal
Equipment
Industry Canada Compliant, ICES-003
Europe:
Johnson Controls declares that this product is also in compliance with the essential
requirements and other relevant provisions of the EMC Directive and Declared as Electronic
Independently mounted control, suitable for DIN rain mounting. Intended to mount in remote
panel. Type 1.C (Micro-interruption), 330 V rated impulse voltage. 125°C ball pressure test.
Australia and New Zealand:
RCM Mark,
Australia/NZ Emissions Compliant
BACnet International:
BACnet Testing Laboratories (BTL) Protocol Revision 12 Listed
BACnet Advanced Application Controller (B-AAC)
Table 11: LC-VAC300x-0 (Part 2 of 2)