EN
VTS reserves the right to implement changes without prior notice
User’s Manual
12
PARAMETERS
DAMPERS
State of the intake / outlet dampers
▪
Closed
▪
Opened
Dampers
Closed
PARAMETERS
FANS
State of the fans
Fans status
– indicates which fans are currently running
▪
Stop – none
▪
Supply – only supply fan is running
▪
Exhaust – only exhaust fan is running
▪
Supply/Exhaust – both fans are running
Supply fan rate
– readout of control signal for the supply fan,
range 0..100%
Exhaust fan rate
– readout of control signal for the supply fan,
range 0..100%
Note!
Control signal for fans is transmitted via Modbus link to
the frequency converter.
Fan status
Stop
Supply fan rate
0%
Exhaust fan rate
0%
PARAMETERS
WATER HEATER
State of the water heater
Pump status
– state of the circulation pump
▪
Off
▪
On
Valve opening
– control signal for the 3-way valve, range
0..100% (corresponding to 0..10V hardware output)
Water heater
Pump status
Off
Valve opening
0%
PARAMETERS
ELECTRIC HEATER
Readout of the control signal for the electric heater, range
0..100% (corresponding to 0..10V hardware output)
Electric heater
0%
PARAMETERS
WATER COOLER
State of the water cooler
Pump status
– state of the circulation pump
▪
Off
▪
On
Valve opening
– control signal for the 3-way valve, range
0..100% (corresponding to 0..10V hardware output)
Water cooler
Pump status
Off
Valve opening
0%