Advanced manual
30
Name of element / connection point
Symbol
Wire type
Section [mm
2
]
cooling device start input
E1
[2]
2x0,75
refrigerating unit start input – I stage
E2.1
[2]
2x0,75
cooling device analog control signal (valve)
Y2
[1]
3x0,75
RRG frequency converter
U1
[1] [2]
3x1,5 / 4x1,5
RRG alarm switch
via Modbus
[3]
UTP 2x2
RRG start input
RRG speed reference input
recirculation damper actuator
Y3
[1]
3x0,75
cross-
fl
ow bypass actuator
Y4
[1]
3x0,75
CWHW analog controlled valve
Y5
[1]
3x0,75
AHU alarm
E4
[2]
2x0,75
HMI OPTIMA
N3
[3]
UTP 2x2
supply elements
pressure control - primary
fi
lter, supply
1S1H
[2]
2x0,75
pressure control - primary
fi
lter, supply
1S2H
[2]
2x0,75
pressure control - compression monitoring for HE-Module
1S3H
[2]
2x0,75
supply frequency converter
1U1
[1] [2] [3]
Table A
UTP 2x2
intake damper actuator
1Y1
[2]
3x0,75
exhaust elements
pressure control - primary
fi
lter, exhaust
2S1H
[2]
3x0,75
exhaust frequency converter
2U1
[1] [2] [3]
Table A
UTP 2x2
outlet damper actuator
2Y1
[2]
3x0,75
Table A
Motor rated
power
Motor rated
current
Frequency
converter fuse
Cable
powering
FC
Cable
powering
motor
Cable powering the control
box
Rated current of the
control box
[kW]
[A]
[mm
2
]
[mm
2
]
[mm
2
]
[A]
3~230V / 50Hz
~230V / 50Hz
Supply
Sup-Exh
Supply
Sup-Exh
0,55
2,5
gG10
3x1,5
4x1
3x1,5
3 x Table C
14
Table B
0,75
3,0
gG10
3x1,5
4x1,5
3x2,5
14
1,1
4,5
gG10
3x1,5
4x1,5
3x2,5
17
1,5
6,0
gG20
3x2,5
4x1,5
3x4
17
2,2
8,0
gG20
3x2,5
4x1,5
3x4
20
3~400V / 50Hz
3~400V / 50Hz
3,0
6,0
gG16
4x2,5
4x2,5
5x4
5 x Table C
8 / 7,5 / 13
Table B
4,0
8,0
gG16
4x2,5
4x2,5
5x4
10 / 9,5 / 15
5,5
11,0
gG20
4x2,5
4x2,5
5x4
13 / 12,5 / 18
7,5
15,0
gG20
4x2,5
4x2,5
5x6
18 / 16,5 / 22
11,0
21,0
gG25
4x4
4x4
5x6
23 / 22,5 / 28