background image

Figure 2. High/Low Level Failsafe

(See Fig. 3 and 4)

SW1 

Position 1

SW1 

Position 2

Sensitivity

Off

Off

1 pF, High

Off

On

2 pF

On

Off

5 pF, Medium

On

On

10 pf, Low

SW1 

Position 3

SW1 

Position 4

Time 

Delay

Off

Off

1 second

Off

On

4 seconds

On

Off

8 seconds

On

On

15 seconds

Figure 3. Sensitivity Settings

Figure 4. Time Delay Settings

(See Fig. 2)

Figure 1. VRF-1000 Electronics

Failsafe Selection

High Level Failsafe Operation

·    DIP Switch SW1 position 5 is on.
·    If the electrical power fails, the relay turns off.  This indicates material

as if the tank were full.

Low Level Failsafe Operation

·    DIP Switch SW1 position 5 is off.
·    If the electrical power fails, the relay turns off.  This indicates material 

as if the tank were empty.

The output relay contacts are labeled in the un-powered alarm state.  The relay is energized
when the VRF-1000 is not alarmed.  This status may be opposite that of other Bindicator

®

brand units.  If the VRF-1000 is replacing an older Model RF-8000 or RF-9000 unit, 
connections will need to be opposite.  If a connection was made to NC1 terminal of the
RF8/9000, connect now to the NO1 terminal of the VRF-1000.  C1 and C2 connections
would remain the same.