MAIN TECHNICAL PARAMETERS
The unit is designed for indoor application with the ambient temperature ranging from +1 °C up to +40 °C and relative humidity up
to 80%. The transported air temperature must be within -25 °C up to +50° C.
The unit is classified as a class I electric appliance.
Hazardous parts access and water ingress protection standard:
Unit motors - IP 44;
Unit assembly connected to air ducts - IP 22.
The unit design is regularly improved, so some models may slightly differ from those ones described in this manual.
595
397
96
105
212
404
164
UNIT OVERALL DIMENSIONS, MM
UNIT TECHNICAL DATA
Model
VUT 100 P mini
Speed
low
medium
high
Supply voltage, 50 Hz [V]
1 ~ 230
Power [W]
30
38
56
Total unit current [A]
0,18
0,23
0,34
Air capacity [m
3
/h]
57
78
106
RPM [min
-1
]
1300
1950
2500
Noise level, [dB(A)]
24
32
41
Max. transported air temperature [°C]
from -25 up to +50
Casing material
Zinc aluminium
Insulation
polyethylene foam 15 mm
Filter:
extract
G4
supply
G4
Connected air duct diameter [mm]
Ø125
Weight [kg]
13,0
Heat recovery efficiency [%]
from 65 up to 76
Heat exchanger type
Cross flow
Heat exchanger material
Plastic