3. Fan maintenance (once a year).

Even regular technical maintenance may not completely prevent dirt accumulation in the fans which reduces the fan capacity and 

impairs supply air delivery into the premises. 

Clean the fans with rugs or a soft brush. Do not use water, aggressive solvents or sharp objects as they may damage the impeller.

4. Condensate drain check (once a year).

The condensate drain (line) may get clogged by dirt and dust particles contained in the exhaust air. Check the drain line operation by 

filling the drain pan under the unit with water, clean the U-trap  and the drain line, if necessary.

5. Fresh air supply duct check (twice a year).

The supply duct grille may get clogged with leaves and other objects reducing the unit performance and supply air delivery. Check the 

supply duct grill twice a year and clean it as required. 

6. Duct system check (every 5 years).

Even regular fulfilling of all the prescribed above maintenance operations may not completely prevent dirt accumulation in the air ducts 

which reduces the unit capacity. The air duct maintenance includes their periodic cleaning or replacement.

Fault 

Possible reasons

Fault handling

The fan does not start 

up during the unit 

start-up.

No power supply.

Make sure that the unit is properly connected to 

power mains and make any corrections, if necessary. 

Motor is jammed, the impeller are 

clogged. 

Turn the unit off. Troubleshoot the motor jam and 

the impeller clogging. Clean the blades. Restart the 

unit. 

Automatic switch 

tripping following the 

unit turning on.

Overcurrent resulted from short circuit 

in the electric circuit. 

Turn the unit off. Contact the service centre. 

Low air flow.

Low set fan speed.

Set higher speed. 

The filters, the fans or the heat 

exchanger are dirty. 

Clean or replace the filter, clean the fans and the 

heat exchanger.

The ventilation system components (air 

ducts, diffusers, louver shutters, grilles) 

are clogged or damaged. 

Clean or replace the ventilation system 

components, such as air ducts, diffusers, louver 

shutters, grilles. 

Low supply air 

temperature.

The extract filter is soiled.

Clean or replace the extract filter. 

The heat exchanger is frozen.

Check the heat exchanger condition. Turn the unit 

off and restart it after the freeze danger is no longer 

imminent. 

High noise, vibration.

The impeller(s) are soiled. 

Clean the impeller(s)

The fan or casing screw connection is 

too loose. 

Tighten the fan or casing screw connection against 

stop. 

No anti-vibration dampers. 

Install anti-vibration rubber mounts. 

Water leakage.

The drain pipe is clogged, damaged or 

wrong mounted.

Clean the drain line, if necessary. Check the drain 

line slant, inspect the U-trap   and make sure the 

drain line is equipped with frost protection.

Possible faults and troubleshooting

TROUBLESHOOTING

STORAGE AND TRANSPORTATION RULES

Store the unit in the manufacturer’s original packing box in a dry ventilated premise at the temperatures from  +5 °C up to +40 °C and 

relative humidity up to 80%.

Storage environment must not contain aggressive vapours and chemical mixtures provoking corrosion, insulation and sealing 

deformation.

Use hoist machinery  for handling and storage operations to prevent the unit damage.

Fulfil the handling requirements applicable for the applicable freight type. 

Transportation with any vehicle type is allowed provided that the unit is protected against  mechanical and weather damage.

Avoid any mechanical shocks and strokes during handling operations.

Summary of Contents for VUT 100 P mini

Page 1: ...USER S MANUAL VUT 100 P mini Heat recovery air handling unit ...

Page 2: ...al parameters 6 Design and operating logic 7 Mounting and set up 8 Condensate drain 8 Connection to power mains 9 Unit control 9 Maintenance 10 Troubleshooting 11 Storage and transportation rules 11 Manufacturer s warranty 12 Acceptance certificate 13 Seller s information 13 Mounting certificate 13 Warranty Card 14 ...

Page 3: ...e unit While transferring the unit control the user s manual must be turned over to the receiving operator Symbol legend used in the manual UNIT MOUNTING SAFETY PRECAUTIONS WARNING DO NOT The unit must be disconnected from the power supply prior to every installation or repair operation The unit must be grounded The unit must not be operated outside the temperature range stated in the user s manua...

Page 4: ...nit and do not put any objects on it OFF ON Disconnect the unit from power supply prior to maintenance Do not let children operate the unit Do not damage the power cable while operating the unit Do not put any objects on the power cable Keep combustible gases and inflammable products away of the unit Do not open the operating unit In case of unusual sounds smoke disconnect the unit from power supp...

Page 5: ...o warm up the clean supply air The unit is designed for wall mounting The unit is rated for continuous operation always connected to power mains Transported air must not contain any flammable or explosive mixtures evaporation of chemicals coarse dust soot and oil particles sticky substances fibrous materials pathogens or any other harmful substances Unit 1 item User s manual 1 item Speed switch 1 ...

Page 6: ...so some models may slightly differ from those ones described in this manual 595 397 96 105 212 404 164 UNIT OVERALL DIMENSIONS MM UNIT TECHNICAL DATA Model VUT 100 P mini Speed low medium high Supply voltage 50 Hz V 1 230 Power W 30 38 56 Total unit current A 0 18 0 23 0 34 Air capacity m3 h 57 78 106 RPM min 1 1300 1950 2500 Noise level dB A 24 32 41 Max transported air temperature C from 25 up t...

Page 7: ...r from outside and warms it up Heat recovery minimizes thermal energy losses energy demand and operating costs for air heating accordingly SUPPLY AIR EXTRACT AIR EXHAUST AIR INTAKE AIR Extract fan Drain pan Thermostat Heat exchanger fan UNIT OPERATING LOGIC TOP VIEW The freeze protection thermostat is installed in the exhaust air duct downstream of the heat exchanger In case of a freeze danger the...

Page 8: ...rmal noise install a flexible air duct instead of the flexible one Optionally the flexible connectors may also be used to prevent resonating CONDENSATE DRAINAGE The condensate drain pan has pipes for extracting the condensed fluid outside the unit Connect the pipe U trap not included in delivery package and sewage collection system with metal plastic or rubber connecting pipes and The pipe slope d...

Page 9: ...rminal marking The terminal marking is shown inside of the terminal box The unit terminal clamps are marked according to the marking on the wiring diagram Route the wires to the terminal box through the stepped grommet on the unit side panel to preserve the electrical protection class Connect the unit to power mains through the external automatic circuit breaker with magnetic trip integrated into ...

Page 10: ...emove four triangular screws 2 Remove the filter covers 3 Pull the filters downwards to remove 1 Undo four clips 2 Remove the service panel 3 Turn the retaining support to loosen and remove the heat exchanger HEAT EXCHANGER REMOVAL AS FOLLOWS DISCONNECT THE UNIT FROM POWER SUPPLY PRIOR TO MAINTENANCE DISCONNECT THE DRAIN PIPE PRIOR TO HEAT EXCHANGER MAINTENANCE 1 2 3 1 2 3 2 Heat exchanger mainten...

Page 11: ...Contact the service centre Low air flow Low set fan speed Set higher speed The filters the fans or the heat exchanger are dirty Clean or replace the filter clean the fans and the heat exchanger The ventilation system components air ducts diffusers louver shutters grilles are clogged or damaged Clean or replace the ventilation system components such as air ducts diffusers louver shutters grilles Lo...

Page 12: ...espective details stated on the unit packing and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the casing excluding external modifications of the unit as required for its installation and the internal components of the unit Alteration of the unit design or engineering changes of the unit Replacement and use of the unit assemblies parts an...

Page 13: ... the product with the requirements relating to electromagnetic compatibility was based on the following standards Quality Inspector s Stamp The heat recovery air handling unitVUT 100 P mini has been connected to power mains pursuant to the requirements stated in the present user s manual Company name Address Telephone Installation technician s full name Installation date Signature Shop name Addres...

Page 14: ..._______________________________________________________________________________________________ ______________________________________________________________________________________________________ ______________________________________________________________________________________________________ __________________________________________________________________________________________________...

Page 15: ...2013 V59EN 04 ...

Reviews: