8
While installing the unit ensure convenient access for subsequent maintenance and repair. The unit is attached to the ceiling by
means of two brackets secured to the ceiling with screws and dowels and four triangular yokes (the brackets and yokes are included in
the delivery package), see Fig. 3.
The wall mounting option is also available. The unit can be mounted on a wall by means of a single bracket, see Fig. 3.
Fig. 3. Unit installation
Unit installation on vertical plane
Internally threaded boss for
triangular suspension yokes
Ceiling installation of the unit
While mounting the unit check the brackets
for uniform orientation.
MOUNTING AND SETUP
The absence of a drain pan in the unit enables its installation in any position provided unhindered access for maintenance.
For best unit performance connect a straight duct section at least 1 m long on both sides of the unit.
The unit spigots must be equipped with grates or other similar devices with the maximum cell diameter of 12 mm to prevent free
access to the fans.
Safety Precautions:
The unit must be mounted on a rigid and stable substructure. Make sure that the installation structure can sustain the weight of the unit.
Reinforce the installation area with beams etc. if required. Prior to installation make sure that the ambient conditions are suitable for the unit
operation. Prior to installation make sure that the casing does not contain any foreign objects such as wrapping film and paper.
If the abnormal noise is generated at the spiral duct connection point replace the spiral air duct with a flexible one to eliminate resonance.
The same effect may be achieved by using flexible connectors.
Control panel installation.
The wall-mounted control panel is installed as follows:
Use a screwdriver to carefully undo the clips in the lower part of the wall-mounted control panel through the access holes, Fig.
4.1.
Remove the back cover.
Disconnect the cable from the terminal block.
Lay the cable in the wall to the panel installation site.
Attach the panel back cover to the wall, Fig. 4.2.
Connect the cable to the terminal block.
Clip the wall-mounted panel fascia in place.