VUT/VUE 250 V/H mini A12/A1
www.ventilation-system.com
Service side change is shown by the example of the VUT/VUE 250 V mini A12/A1 air handling unit.
The procedure of the service side changing for VUT/VUE 250 H mini A12/A1 is carried out in the same manner.
CONDENSATE DRAINAGE SYSTEM CONNECTION (ONLY FOR THE VUT 250 V/H mini A12/A1 MODEL)
The VUE 250 V/H mini A12/A1 units are equipped with an enthalpy heat exchanger and don’t require condensate drainage.
The hole for the drain pipe is at the bottom of the unit. Remove the plug from the hole, open the service panel and install the drain pipe
from the delivery set into the hole, then connect the drain pipe to the sewage system using the SG-32 U-trap kit (available upon separate
order). The pipe slope downwards must be at least 3°.
Drain
pipe
Drain
hose
min 3
°
Sewage
system
Sewage pipe
Ø
32 mm
U-trap