UNIT MOUNTING

To attain the best performance of the unit and to minimise turbulence-induced air pressure losses while mounting connect a straight 

air duct section on both sides of the unit. 

Minimum straight air duct length: 

• 

equal to 1 air duct diameter on intake side.

• 

equal to 3 air duct diameters on outlet side. 

If the air ducts are not connected or the connected air ducts are too short, protect the unit parts from ingress of foreign objects by 

covering the spigots with a protecting grille or other protecting device with mesh width not more than 12.5 mm to prevent uncontrollable 

access to the fans. 

While installing the unit ensure convenient access for subsequent maintenance and repair. The unit must be mounted on an even 

wall. Mounting the unit to an uneven surface can lead to the unit casing distortion and operation disturbance.

Unit wall mounting

Fasteners for wall-mounting are not included into delivery set 

and need to be ordered separately. While selecting appropriate 

fasteners consider the material of the mounting surface as well 

as the weigh of the unit, refer technical data. For selection of the 

fasteners for unit mounting please refer to service technicians. 

Fix the wall mounting bracket at a required height and fix the unit 

on the hook.

Unit floor mounting

Install the unit on the pre-set floor supports, minimum 150 mm 

height, to ensure sufficient access for the drain pipe connection 

to the U-trap and for condensate drain system mounting. 

min 150 mm

Note: the mounting is shown for VUT/VUE 250 V(B) EC. 

MOUNTING AND WIRING OF THE HEATERS TO THE UNIT WITH A19 CONTROL PANEL

NKP and NKD electric heaters are not included in the delivery set of the air handling unit and are available as specially ordered 

accessory.

The heaters are rated for connection to 230V / 50 (60) Hz power supply. 

NKP and NKD heaters may be connected to the unit both as a single unit each or jointly. 

Prior to connecting the heater to the air handling unit remove the pre-installed plugs from the internal socket connectors. 

WARNING! 

• 

Do not remove the plugs before the heaters are connected to the air handling unit. 

• 

Make sure to cover the socket connector with the plugs after dismantling of the connecting cable. 

• 

If only one heater is connected, do not remove the plugs from the other socket connector that is not in use.  

• 

If the socket connectors are not covered with plugs for any reasons, the ventilation unit does not start during connection to 

power supply and the control panel displays DI1 and DI3 errors for NKP and DI1, DI3 and TE5 errors for NKD. Turn the unit 

off and cover the socket connectors with the plugs to troubleshoot the errors. 

Attach the NKP heater to the air duct connected to the intake air spigot. 
The electric heater is connected to the unit via a connecting cable with DB-9F socket connectors connected to the external socket 

connectors DB-9F on the unit and the heater. 

Attach the NKD heater to the air duct connected to the supply air spigot. Install the air temperature sensor TE5 in the supply air 

duct. Keep the minimum distance between the heater and the sensor 1 m. 

Connect the electric heater to the unit via a connecting cable with DB-15M socket connectors inserted to the DB-15F external 

socket connectors on the unit and the heater. 

Summary of Contents for VUE 200 B EC

Page 1: ...USER S MANUAL РУКОВОДСТВО ПОЛЬЗОВАТЕЛЯ HEAT HEAT AND ENERGY RECOVERY VENTILATION UNIT VUT VUE 200 V B EC VUT VUE 250 V B EC ...

Page 2: ...ereinafter the unit as mentioned in the Safety Requirements and Manufacturer s Warranty sections as well as in warnings and information blocks SAFETY REQUIREMENTS Read the user s manual carefully prior to installing and operating the unit Fulfil the user s manual requirements as well as the provisions of all the applicable local and national construction electrical and technical norms and standard...

Page 3: ... not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit Disconnect the unit from power mains prior to any technical maintenance Do not store any explosive or highly flammable substances in close proximity to the unit When the unit generates unusual sounds odour or emits smoke disconnect it from power supply and contact...

Page 4: ...IED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN Transported air must not contain any flammable or explosive mixtures evaporation of chemicals sticky substances fibrous materials coarse dust soot and oil particles or environments favourable for the formation of hazardous substances toxic substances dust pa...

Page 5: ... capacity m3 h 260 290 RPM min 1 2050 Noise level 3 m dB A 24 25 Transported air temperature C from 25 up to 60 Casing material painted steel Insulation 25 mm mineral wool 30 mm mineral wool Extract filter G3 G4 Supply filter G3 optional F8 G4 F7 Heat exchanger type counter flow Heat exchanger material polystyrene enthalpy membrane Connected air duct diameter mm Ø 125 Ø 125 Ø 160 Ø 160 Heat recove...

Page 6: ...nger Removable plates for filter maintenance A14 control panel Power cable with plug A11 or A19 control panel The unit casing is made of rigidly fixed panels The panels are made of painted steel sheet and galvanized steel sheet filled with heat and sound insulating layer of mineral wool between The front panel of the unit has removable plates to enable filter replacement Location of the service si...

Page 7: ...tract air from the room flows into the unit and is cleaned in the extract filter Then the air is moved through the heat exchanger and is exhausted outside with the extract fan Cold fresh air from outside flows into the unit where it is cleaned in the supply filter Then the air flows through the heat exchanger and is moved to the room with the supply fan Supply air is heated in the heat exchanger b...

Page 8: ...T AIR INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR INTAKE AIR SUPPLY AIR EXTRACT AIR EXHAUST AIR MOUNTING AND SET UP THE UNIT MUST BE MOUNTED BY A QUALIFIED EXPERT ONLY PROPERLY TRAINED AND HAVING THE REQUIRED TOOLS AND MATERIALS HUMIDITY SENSOR MOUNTING IN THE EXTRACT AIR DUCT ATTENTION The humidity sensor must be installed prior to unit mounting Mounting steps for the HV1 humidity sensor for th...

Page 9: ...Insert the humidity sensor on the mount Connect the humidity sensor contact socket to the contact socket with a cable from the control unit The contact socket is pre wired Вытяжной патрубок SERVICE SIDE CHANGE Unscrew the front panel on the service side and the back panel Remove the panels and change their positions Fix the panels with screws Note the service panel change is shown for VUT VUE 250 ...

Page 10: ...VUE 250 V B EC MOUNTING AND WIRING OF THE HEATERS TO THE UNIT WITH A19 CONTROL PANEL NKP and NKD electric heaters are not included in the delivery set of the air handling unit and are available as specially ordered accessory The heaters are rated for connection to 230V 50 60 Hz power supply NKP and NKD heaters may be connected to the unit both as a single unit each or jointly Prior to connecting t...

Page 11: ...d at the bottom of the unit Remove the plug from the hole open the service panel and install the drain pipe from the delivery set into the hole then connect the drain pipe to the sewage system using the SG 32 U trap kit available upon separate order While laying the hoses provide the slope downwards min 3 min 3 DRAIN HOSE U TRAP SEWAGE SYSTEM DRAIN PIPE Note installation of the drain pipe is shown...

Page 12: ...power supply for the units with A19 control panel only The control unit A19 enables connection of the heater s If the unit is connected to power supply before connection of the heater s the control panel displays the following errors DI1 and DI3 for NKP and DI1 DI3 and TE5 for NKD To troubleshoot the errors turn the unit off and restart it with the activated heater s Connection of extra external d...

Page 13: ...ded in the delivery set and is available as a specially ordered accessory Connection of the external supply air damper SM1 L N and exhaust air damper SM2 L N The air dampers and the electric actuator are not included in the delivery set and are available as specially ordered accessories For connection of the air dampers use an electric actuator of LF 230 BELIMO type rated for 230 V power voltage a...

Page 14: ...ectric actuators of the external air dampers SM1 L1 N SM2 L1 N 1 L 3 PE 4 nc 5 c 6 no 7 c 10 Gnd 11 Tx 12 Rx 13 U 2 N 8 SM L 9 SM N X1 PK fire alarm panel remove the jumper while connecting the contact External device NO contact CO2 sensor 230V 50 60 Hz XP QF 3 2 1 GND U 0 10V Humidity sensor HV2 5 U 6 0 10V 7 GND X2 VUT VUE 200 V B EC A11 14 A 13 B 12 Gnd 11 12V 10 no 9 c 8 no 7 6 5 c 3 PE 2 N 1 ...

Page 15: ...SB Type B VUT VUE 200 V B A14 VUT VUE 250 V B A14 The software enables editing the unit parameters Parameter Factory setting Control range Zero speed off 0 0 100 Low speed 40 0 100 Medium speed 70 0 100 High speed 100 0 100 Unit speed with the closed dry contact of the external control unit 100 0 100 Filter cleaning replacement interval 2160 3 months 0 10000 Humidity level 60 30 80 The list of the...

Page 16: ...unit Then remove the retaining clamps to pull the filters from the frames Rinse the filters with water and let these dry out After that reassemble the filters in the reverse orders and install to the unit Note access to the filters is shown for VUT VUE 250 V B EC 2 Heat exchanger maintenance once per year Some dust may accumulate on the heat exchanger block even in case of regular maintenance of t...

Page 17: ...rong installation of the drain system Clean the drainage system Check the drain line slope angle Make sure that the U trap is filled with water and the drain pipes are frost protected Displayed alarm indicator on the control panel Communication loss cable or wire breakdown between the control panel and the ventilation unit Check the power and connection cables and wires between the control panel a...

Page 18: ...usly dismounted by the user Mismatch of the unit model and the brand name with the information stated on the unit packing and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the unit casing excluding external modifications as required for installation and internal components caused by the user Redesign or engineering changes to the unit Rep...

Page 19: ...ceptance of the complete unit delivery with the user s manual The warranty terms are acknowledged and accepted Customer s Signature Seller s Stamp INSTALLATION CERTIFICATE Installation Company Stamp The unit has been connected to power mains pursuant to the requirements stated in the present user s manual Company Name Address Phone Number Installation Technician s Full Name Installation Date Signa...

Page 20: ...V106 5EN 01 ...

Reviews: