Vents VKPD User Manual Download Page 6

VKPD

6

www.ventilation-system.com

DESIGN AND OPERATING PRINCIPLE

The fan casing is made of galvanized steel.

For periodic inspections, inspection hatches are provided on the fan 
casing.
The electric motor is installed outside the air flow.
The impeller with backward curved blades made of heat-resisting 
steel.
To control the speed, the fan can be equipped with a frequency 
converter (not included in the delivery set, ordered separately)

Model

Dimensions [mm]

Weight 

[kg]

A

A1

A2

B

B1

B2

L

H

VKPD-250

500

520

540

300

320

340

680

557

40

VKPD-280

600

620

640

300

320

340

680

558

40

VKPD-315

600

620

640

350

370

390

680

624

56

VKPD-355

700

720

740

400

420

440

680

657

51

VKPD- 400

700

720

740

400

420

440

680

674

64

VKPD-450

800

820

840

500

520

540

800

772

85

VKPD-500

800

820

840

500

520

540

840

813

94

VKPD-560

900

920

940

600

620

640

840

959

96

VKPD-630

1000

1020

1040

700

720

740

1040

1050

125

VKPD-710

1200

1220

1240

800

820

840

1040

1255

171

L

H

ø 9

B 2

B 1

B

A 2

A 1

A

Summary of Contents for VKPD

Page 1: ...USER S MANUAL VKPD Duct rectangular smoke extraction fan...

Page 2: ...language in any form without the prior written permission of the Company Safety requirements 2 Purpose 4 Delivery set 4 Designation key 4 Technical data 5 Design and operating principle 6 Mounting an...

Page 3: ...stallation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit The unit...

Page 4: ...BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN Duct re...

Page 5: ...315 2D 1 1 600x350 1 1 2880 2 4 3 400 VKPD 315 2 4D 1 1 0 25 600x350 1 1 0 25 2880 1440 355 4 1 230 VKPD 355 4E 0 37 700x400 0 37 1420 4 3 400 VKPD 355 4D 0 37 700x400 0 37 1420 4 6 3 400 VKPD 355 4...

Page 6: ...ot included in the delivery set ordered separately Model Dimensions mm Weight kg A A1 A2 B B1 B2 L H VKPD 250 500 520 540 300 320 340 680 557 40 VKPD 280 600 620 640 300 320 340 680 558 40 VKPD 315 60...

Page 7: ...the air duct It is recommended to suspend the fan to the ceiling using steel reinforcement and threaded rods or using perforated galvanized plates and connecting them to the fan flanges or to an auxi...

Page 8: ...depending on the wire type insulation length and installation method Connection of the unit to the fixed power supply network must be carried out in accordance with the current regulations Access to t...

Page 9: ...mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals...

Page 10: ...the best case scenario an SS device may help reduce the in rush current to 250 of the motor rated current If this is insufficient an FC is necessary 2 The motor cannot start the mechanism with DOL st...

Page 11: ...ore starting maintenance works Clean the impeller blades with a soft cloth wetted in mild water detergent solution Avoid liquid dripping on the motor Wipe the fan surfaces dry after cleaning While cle...

Page 12: ...ompliance certificate The selection should be limited to the top five foreign switching equipment manufacturers The fan fails to reach the required rotation speed due to serious overheating of the fan...

Page 13: ...calculate the network parameters and select a matching fan The network resistance exceeds the design calculations Re arrange the ventilation network to decrease its aerodynamic resistance Wrong direct...

Page 14: ...and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the unit casing excluding external modifications as required for installation and interna...

Page 15: ..._____________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Nam...

Page 16: ...V228EN 01...