COMMISSIONING

THE ORGANISATION RESPONSIBLE FOR THE COMMISSIONING SHALL BE RESPONSIBLE 

FOR PROPER MOTOR PHASING AND STARTING PATTERN SELECTION.

•  After fan starting make sure that the electric motor rotates properly without undue vibration and abnormal noise. 
•  Make sure that the fan impeller rotates in the direction marked by the arrow on the fan casing. If necessary, change the rotation 

direction of the impeller by reversing the phase sequence (for a three-phase motor) or by rewiring according to the wiring diagram 
located inside the terminal box (for a single-phase motor).

•  Make sure that the fan energy consumption complies with the value given on the equipment nameplate and check the motor for 

overheating.

•  The phase current should be checked once the fan reaches the rated operating conditions.
•  Do not switch the fan on and off several times without pauses as this may result in damage to the winding or insulation due to 

overheating. 

DURING STARTING THE IN-RUSH CURRENTS OF THE FAN MAY SEVERAL TIMES EXCEED 

THE RATED VALUES. 

SEE “ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS” IN THE “CONNECTION 

TO POWER MAINS” SECTION

Let us review three variations of a heavy start:

1. The feed line performance is barely sufficient or insufficient to maintain the induced current.

Typical symptoms: 

Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off, 

and the supply generator shuts down.

Solution: 

In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is 

insufficient, an FC is necessary.

2. The motor cannot start the mechanism with DOL starting.

Typical symptoms: 

The motor fails to turn or “freezes” at certain speed which is maintained until actuation of the protection suite.

Solution: 

This problem may not be solved with an SS device. The motor develops insufficient shaft torque. However, this problem can 

be addressed by using an FC, but each case may be different.

3. The motor spins up the mechanism with authority, but fails to reach the rated rotation speed.

Typical symptoms: 

The input automatic circuit breaker is tripped during spin-up. This often happens with heavy-weight fans with a 

considerable rotation speed.

Solution: 

Such problems may be addressed with an SS device, but not with 100 % certainty. The closer the motor speed to the rated 

value during the actuation of the protective equipment, the higher the chances of success. The use of an FC in this case helps solve the 
problem fundamentally.

Standard switching equipment (automatic circuit breakers, contactors and motor starters) is not designed to withstand 

prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of 

time.

Using switching equipment with a higher maximum current rating renders the electric motor protection system less sensitive. 

As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold.

Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan.

Summary of Contents for VKPD

Page 1: ...USER S MANUAL VKPD Duct rectangular smoke extraction fan...

Page 2: ...language in any form without the prior written permission of the Company Safety requirements 2 Purpose 4 Delivery set 4 Designation key 4 Technical data 5 Design and operating principle 6 Mounting an...

Page 3: ...stallation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit The unit...

Page 4: ...BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN Duct re...

Page 5: ...315 2D 1 1 600x350 1 1 2880 2 4 3 400 VKPD 315 2 4D 1 1 0 25 600x350 1 1 0 25 2880 1440 355 4 1 230 VKPD 355 4E 0 37 700x400 0 37 1420 4 3 400 VKPD 355 4D 0 37 700x400 0 37 1420 4 6 3 400 VKPD 355 4...

Page 6: ...ot included in the delivery set ordered separately Model Dimensions mm Weight kg A A1 A2 B B1 B2 L H VKPD 250 500 520 540 300 320 340 680 557 40 VKPD 280 600 620 640 300 320 340 680 558 40 VKPD 315 60...

Page 7: ...the air duct It is recommended to suspend the fan to the ceiling using steel reinforcement and threaded rods or using perforated galvanized plates and connecting them to the fan flanges or to an auxi...

Page 8: ...depending on the wire type insulation length and installation method Connection of the unit to the fixed power supply network must be carried out in accordance with the current regulations Access to t...

Page 9: ...mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals...

Page 10: ...the best case scenario an SS device may help reduce the in rush current to 250 of the motor rated current If this is insufficient an FC is necessary 2 The motor cannot start the mechanism with DOL st...

Page 11: ...ore starting maintenance works Clean the impeller blades with a soft cloth wetted in mild water detergent solution Avoid liquid dripping on the motor Wipe the fan surfaces dry after cleaning While cle...

Page 12: ...ompliance certificate The selection should be limited to the top five foreign switching equipment manufacturers The fan fails to reach the required rotation speed due to serious overheating of the fan...

Page 13: ...calculate the network parameters and select a matching fan The network resistance exceeds the design calculations Re arrange the ventilation network to decrease its aerodynamic resistance Wrong direct...

Page 14: ...and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the unit casing excluding external modifications as required for installation and interna...

Page 15: ..._____________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Nam...

Page 16: ...V228EN 01...

Reviews: