POSSIBLE MALFUNCTIONS AND THEIR ELIMINATION

Problem

Possible reasons

Elimination

The fan will not start.

No power supply.

Check the mains switch. Check the electrical connections 

against the wiring diagram. 

Jammed motor.

Carefully check the fan impeller for possible seizure and 

eliminate it, if necessary. If the impeller is in order, replace 

the electric motor. 

The switching equipment 

activates upon fan start-up.

Short circuit in the fan or the electric circuit between 

the fan and the switching equipment.

Eliminate the cause of a short circuit. 

Excessive current consumption due to an overload in 

the electric mains.

Eliminate the cause of excessive current consumption. 

Improper fan starting method. 

Use a soft starter or frequency converter to start the motor 

(see "Asynchronous Electric Motor Starting Methods" 

in the "Connection to power mains" section)

Improper switching equipment.

Re-select the switching equipment in accordance with the 

current regulations and equipment specifications. 

The installed switching equipment is of poor quality 

or its actual performance falls short of the rated values 

stated by the manufacturer.

Re-select the switching equipment by choosing a unit 

which successfully passed commutation and load tests 

and has a technical compliance certificate. The selection 

should be limited to the top five foreign switching 

equipment manufacturers. 

The fan fails to reach the 

required rotation speed due to 

serious overheating of the fan 

motor.

Fan motor overloaded.

Eliminate the overload.

Improper fan starting method.

Use a soft starter or frequency converter to start the motor 

(see “Asynchronous Electric Motor Starting Methods” 

in the “Connection to power mains” section)

.

The fan motor runs at 

overload capacity with current 

consumption in excess of the 

rated value.

The fan supplies more air than expected upon motor 

capacity selection.

Measure network resistance. Throttle down the network 

(add aerodynamic resistance to the air duct network).

Wrong motor phasing. The impeller rotates in the 

opposite direction of the arrow on the fan casing.

If necessary, change the impeller rotation direction by 

changing the phase sequence on the electric motor 

terminals.

Air ducts clogged.

Clean the air duct or the impeller.

The fan supplies more air than 

expected.

The resistance values used during the ventilation 

network calculations are too conservative.

Check the air ducts for proper shape and cross section as 

well as for any dampers present.

The cross section of air ducts increased and their 

number reduced during the installation.

Throttle down the network (add aerodynamic resistance 

to the air duct network).

Wrong choice of the fan.

Replace the fan with a unit of proper standard size.

TROUBLESHOOTING 

Summary of Contents for VKPD

Page 1: ...USER S MANUAL VKPD Duct rectangular smoke extraction fan...

Page 2: ...language in any form without the prior written permission of the Company Safety requirements 2 Purpose 4 Delivery set 4 Designation key 4 Technical data 5 Design and operating principle 6 Mounting an...

Page 3: ...stallation and maintenance operations with wet hands Do not wash the unit with water Protect the electric parts of the unit against ingress of water Do not allow children to operate the unit The unit...

Page 4: ...BE INSTALLED AND CONNECTED ONLY BY PROPERLY QUALIFIED PERSONNEL AFTER THE APPROPRIATE BRIEFING THE CHOICE OF UNIT INSTALLATION LOCATION MUST PREVENT UNAUTHORIZED ACCESS BY UNATTENDED CHILDREN Duct re...

Page 5: ...315 2D 1 1 600x350 1 1 2880 2 4 3 400 VKPD 315 2 4D 1 1 0 25 600x350 1 1 0 25 2880 1440 355 4 1 230 VKPD 355 4E 0 37 700x400 0 37 1420 4 3 400 VKPD 355 4D 0 37 700x400 0 37 1420 4 6 3 400 VKPD 355 4...

Page 6: ...ot included in the delivery set ordered separately Model Dimensions mm Weight kg A A1 A2 B B1 B2 L H VKPD 250 500 520 540 300 320 340 680 557 40 VKPD 280 600 620 640 300 320 340 680 558 40 VKPD 315 60...

Page 7: ...the air duct It is recommended to suspend the fan to the ceiling using steel reinforcement and threaded rods or using perforated galvanized plates and connecting them to the fan flanges or to an auxi...

Page 8: ...depending on the wire type insulation length and installation method Connection of the unit to the fixed power supply network must be carried out in accordance with the current regulations Access to t...

Page 9: ...mechanism Soft start SS starting A soft starter gradually increases the voltage supplied to the motor from the initial to the rated value This starting system can be used to meet the following goals...

Page 10: ...the best case scenario an SS device may help reduce the in rush current to 250 of the motor rated current If this is insufficient an FC is necessary 2 The motor cannot start the mechanism with DOL st...

Page 11: ...ore starting maintenance works Clean the impeller blades with a soft cloth wetted in mild water detergent solution Avoid liquid dripping on the motor Wipe the fan surfaces dry after cleaning While cle...

Page 12: ...ompliance certificate The selection should be limited to the top five foreign switching equipment manufacturers The fan fails to reach the required rotation speed due to serious overheating of the fan...

Page 13: ...calculate the network parameters and select a matching fan The network resistance exceeds the design calculations Re arrange the ventilation network to decrease its aerodynamic resistance Wrong direct...

Page 14: ...and in the user s manual User s failure to ensure timely technical maintenance of the unit External damage to the unit casing excluding external modifications as required for installation and interna...

Page 15: ..._____________________________ unit is installed pursuant to the requirements stated in the present user s manual Installation Stamp Company name Address Phone Number Installation Technician s Full Nam...

Page 16: ...V228EN 01...

Reviews: