18
KAM
www.ventilation-system.com
Let us review three variations of a heavy start:
1. The feed line performance is barely sufficient or insufficient to maintain the induced current.
Typical symptoms:
Upon starting the circuit breakers at the system input are tripped; the lights, certain relays and contactors go off,
and the supply generator shuts down.
Solution:
In the best-case scenario an SS device may help reduce the in-rush current to 250 % of the motor rated current. If this is
insufficient, an FC is necessary.
2. The motor cannot start the mechanism with DOL starting.
Typical symptoms:
The motor fails to turn or “freezes” at certain speed which is maintained until actuation of the protection suite.
Solution:
This problem may not be solved with an SS device. The motor develops insufficient shaft torque. However, this problem can
be addressed by using an FC, but each case may be different.
3. The motor spins up the mechanism with authority, but fails to reach the rated rotation speed.
Typical symptoms:
The input automatic circuit breaker is tripped during spin-up. This often happens with heavy-weight fans with a
considerable rotation speed.
Solution:
Such problems may be addressed with an SS device, but not with 100 % certainty. The closer the motor speed to the rated
value during the actuation of the protective equipment, the higher the chances of success. The use of an FC in this case helps solve the
problem fundamentally.
Standard switching equipment (automatic circuit breakers, contactors and motor starters) is not designed to withstand
prolonged overloads normally causing the fan to shut down automatically DOL starting that continues for a long period of
time.
Using switching equipment with a higher maximum current rating renders the electric motor protection system less sensitive.
As a result the switching equipment will not be able to detect motor overload in time due to a high current sensing threshold.
Such problems as mentioned above can only be addressed by utilizing a soft starter or a frequency converter to start the fan.
COMMISSIONING
THE ORGANISATION RESPONSIBLE FOR THE COMMISSIONING SHALL BE RESPONSIBLE
FOR PROPER MOTOR PHASING AND STARTING PATTERN SELECTION.
• After fan starting make sure that the electric motor rotates properly without undue vibration and abnormal noise.
• Make sure that the fan impeller rotates in the direction marked by the arrow on the fan casing. If necessary, change the rotation
direction of the impeller by reversing the phase sequence (for a three-phase motor) or by rewiring according to the wiring diagram
located inside the terminal box (for a single-phase motor).
• Make sure that the fan energy consumption complies with the value given on the equipment nameplate and check the motor for
overheating.
• The phase current should be checked once the fan reaches the rated operating conditions.
• Do not switch the fan on and off several times without pauses as this may result in damage to the winding or insulation due to
overheating.
DURING STARTING THE IN-RUSH CURRENTS OF THE FAN MAY SEVERAL TIMES EXCEED
THE RATED VALUES.
SEE “ASYNCHRONOUS ELECTRIC MOTOR STARTING METHODS” IN THE “CONNECTION
TO POWER MAINS” SECTION
Summary of Contents for FFK 125
Page 1: ...USER S MANUAL KAM Chimney centrifugal fan ...
Page 25: ...25 www ventilation system com ...
Page 26: ...26 KAM www ventilation system com ...
Page 27: ...27 www ventilation system com ...
Page 28: ...V15EN 08 ...