CBF LP 110 DC (Light) (TH/TP)
www.ventilation-system.com
The fan casing is made of galvanized steel. The fan casing includes an exhaust spigot with a back draft damper to prevent air back flow.
The terminal box comprises the terminals for wiring of the fan and is attached to the fan casing. The decorative grille is fixed to the casing
via the springs inserted in the hooks. The front panel is fixed via the grille slots. An electric motor with a centrifugal impeller with forward
curved blades is fastened inside of the casing.
The fan is equipped with a timer. After an external switch, e.g. a light switch is turned on, the fan turns on or switches to high speed after
countdown of a set turn-on delay time, adjustable from 0 to 3 minutes. After the fan is turned off it keeps running for a set turn-off delay
time, adjustable from 1 to 90 minutes and then reverts to the initial operation status.
Depending on the model, the fan is equipped with a light source (LED-lamp), humidity or motion sensors.
Motion sensor (TP)
Upon activation of the motion sensor the fan is turned on and switches to high speed. After no more motion is detected the fan keeps
operating for a set turn-off delay time period, adjustable from 1 to 90 minutes, and returns to its original state.
Humidity sensor (TH)
If the set humidity level in the room is exceeded from 50 % to 90 %, the fan turns on or switches to high speed. As the indoor humidity
level drops down the fan keeps operating for a set turn-off delay time period, adjustable from 1 to 90 minutes, and then returns to its
original state.
READ THE USER'S MANUAL BEFORE iNSTALLiNg THE UNiT.
The fan is a component part and is not designed for stand-alone operation.
The fan is designed for ceiling mounting and installation in the space between the joists (the distance between the joists is from 270 mm
to 470 mm) using a removable bracket or fixation holes in the fan casing.
The fan installation location must comply with local building codes for this type of product.
Check the fan for mechanical damages prior to mounting.
Before mounting make sure the casing does not contain any foreign objects (e.g. foil, paper).
While installing the unit ensure convenient access for subsequent maintenance and repair.
The minimum distance between the unit and the ceiling should be at least 5 mm.
L = 5mm (min)
L = 5mm (min)