6
UNIT TECHNICAL PARAMETERS
Model
АОЕ 9
АОЕ 12
АОЕ 15
АОЕ 18
АОЕ 24
АОЕ 30
Supply voltage, 50 Hz [V]
3 ~ 400
Max. fan power [W]
140
253
Fan current [A]
0,61
1,1
Electric heater power [kW]
9
12
15
18
24
30
Electric heater current [A]
13,0
17,3
21,7
26,0
34,6
43,3
Total unit power [kW]
9,14
12,14
15,14
18,25
24,25
30,25
Total unit current [A]
13,6
17,9
22,3
27,1
35,7
44,4
Air capacity [m
3
/h]
2300
4000
RPM [min
-1
]
1420
1480
Casing material
Painted steel
Noise level, 5 m, [dB(A)]
55
61
Ingress protection rate
IP 21
Weight [kg]
32
48
DESIGN AND OPERATING LOGIC
The unit is designed for indoor air heating by means of the electric heater and uniform air flow distribution with the fan and louvre
shutters.
The special unit design enables quick air heating in large premises due to high-efficient electric heater and a powerful fan. The electric
connections and control connections are performed in a terminal box at the side unit panel.
TERMINAL BOX
ELECTRIC HEATER
FAN
LOUVRE SHUTTERS
EMERGENCY THERMAL
SWITCH CAP
UNIT DESIGN