![Vents AOE 12 User Manual Download Page 10](http://html1.mh-extra.com/html/vents/aoe-12/aoe-12_user-manual_1002602010.webp)
10
Unit name
Rated circuit breaker trip current [A]
Number of conductors and cross section [mm
2
]
АОЕ-9
20
5х2,5
АОЕ-12
25
5х2,5
АОЕ-15
31,5
5х4,0
АОЕ-18
40
5х6,0
АОЕ-24
50
5х10,0
АОЕ-30
63
5х10,0
Enabling access to the unit terminal blocks:
1. Remove four screws from the terminal box lid.
2. Remove the lid.
1.
2.
RT1
RT1 TK1 TK1
L1
L2
L3
N
PE
TK2 TK2
L
N
RT1
RT1 TK1 TK1
1L1
1L2
1L3
2L1
2L2
2L3
TK2 TK2
L
N
N
PE
Install the jumper for
connection of TK1 and TK2 in
series
Install the jumper for
connection of TK1 and TK2 in
series
Terminals for
connection to the
control circuit
X1
in the control circuit
Terminals for
connection to the
control circuit
Terminals for
connection to the
contactor circuit
Terminals for
connection to the
contactor circuit
X1
in the control circuit
X3
Fan
X2
Heater
X2
Heater
TERMINAL BLOCKS INSIDE OF THE TERMINAL BOX
Terminal block X1 (in the control circuit):
RT1 – temperature sensor;
TK1 – self-resettable thermal switch (normally closed contact), response tempe50 °C;
TK2 – manually resettable thermal switch (normally closed contact), response tempe90 °C;
Connect the thermal switch contacts in series to the circuit of the starter (contactor) actuating coil that starts the unit or the heater. In
case of overheating one of the contacts gets broken and switches the starter actuating coil off to cut power off and stop the motor.
Terminal block X2 (heaters):
L1, L2, L3 – phases (for AOE 9,12,15);
1L1, 1L2, 1L3, 2L1, 2L2, 2L3 – phases (for AOE 18,24,30);
N – neutral;
PE – protecting grounding.
Terminal block X3 (fan):
L – phase;
N – neutral.
The fan, the heaters, the thermal switch and the temperature sensor are mounted on side of the unit, refer to the wiring diagram in page
11.