Ventam 85 Installation & Commissioning Instructions Download Page 5

Page 5 of 8 
© Ventam Systems Ltd 

  Turn fan back on 

– “Fans On” light should be lit on panel. 

  Repeat section 13.0 - Gas Proving part one 

– “Gas On” panel light will come on. 

  Repeat step 14.1 for each interlocked fan 

 
 
 
 
 

14.2  Gas Proving  

 

“Gas On” light should still be lit. 

 

Turn off  all gas appliances. 

  Depress emergency stop button on the front of panel 

– panel will indicate “Emergency Stop” 

AND  “Gas Off”. 

  Re-set  the  emergency  stop  button  on  the  front  of  the  panel,  repeat  step  13.0 

–  “Gas  On” 

panel light will come on.  

  Repeat step 14.2 for each additional emergency stop button fitted. 

 
 

14.3    Fan pressure switch Adjustments 

  Fan pressure switches can be adjusted to trip the gas valve at the required air flow rate.  As 

a guide, the fans should trip the valve if the fans are reduced to below 50% of full speed, but 
the ventilation system specifications for minimum flow rates must be followed.

 

  Typically, if the speed controller minimum is to be set at 50% of max fan speed, then the Fan 

pressure switch should be set to turn off the gas at 45%.

 

  Allow  a  tolerance  for  the  ventilation  system  to  settle  down  and  for  the  filters  to  become 

partially blocked etc.  If the speed controller is fitted with a minimum speed adjustment pot 
(on the rear of the speed controller board), ALWAYS set this to set the minimum speed that 
the fan will run and this will prevent user problems and premature fan failure.

 

  A typical installation requires that the fresh air supply flow is at 85% of the extraction air flow, 

and this can be allowed for in fan pressure switch adjustments to control minimum.

 

 

14.4   Using a current monitor to monitor the fan(s) 

  A  current  monitor  may  be  used  instead  of  a  fan  pressure  switch  to  check  that  the  fan  is 

operating.  The  current  monitor must  be  set  up  to  ensure  that  the gas  turns off  if  the fan  is 
turned down too low or turned off. Adjust the current monitor so that this happens and test it. 
As a guide, the fans should trip the valve if the fans are reduced to below 50% of full speed, 
but the ventilation system specifications for minimum flow rates must be followed.

 

  A typical installation requires that the fresh air supply flow is at 85% of the extraction air flow, 

and this can be allowed for in current monitor adjustments to control minimum.

 

  The  current  monitor  should  be  installed  so  that  the  volt  free  current  monitor  contact  is 

CLOSED when the fan is running. This contact must be connected into panel terminals 1+2 
OR 3+4.

 

 
 

14.3  Instruct site staff in correct system operation and instruct staff to clean filters 

regularly . 
Advise site staff NOT to  decrease fan(s) speed or gas valve will  NOTOPERATE!!!! 
Ask the user to start the fans, increase the fan speed etc to ensure the user is   
familiar with and understands system operation and that the system is installed for  
their safety.

Summary of Contents for 85

Page 1: ...e the main gas isolation valve has opened if the gas pressure subsequently falls below a pre set level 60 of line pressure or a fan is turned off the main gas valve will close Each time a fan is turned off OR an emergency stop is depressed OR the line gas pressure falls too low the system MUST BE GAS PROVED AGAIN 3 Ventam 85 Interlock Panel Location Install the Ventam 85 Interlock Panel adjacent t...

Page 2: ...ressure switch unit to the ductwork connector Pressure switch tubing must slope down continuously from the pressure switch to the ductwork to allow condensate to naturally drain from the pipe work to prevent blockages occurring Twists loops and kinks are not permitted in the pressure switch tubing The pressure switch unit location must allow 600mm clearance to the front and 150mm below for access ...

Page 3: ...l Install cables to suit the valve size between the Ventam 85 Control Panel and the Gas Valve Re set the Emergency Stop on the Control Panel by turning the button in the direction of the arrows on the button Ensure it is safe to start fan s Check all panel terminations are secure Use the correct tool and do not over tighten Ensure that the following factory installed terminal links are fitted if n...

Page 4: ...gency stop button panel will indicate Emergency Stop Re set additional emergency stop button on the front of panel Repeat step 11 7 for each additional emergency stop button fitted 12 0 Gas Proving check that gas cannot come on if fans are off Turn off one of the fans Fan s off lamp and Gas Off lamp will be lit Operate the Gas Power Switch by switching it to the right Depress the Start Gas Proving...

Page 5: ... the fan will run and this will prevent user problems and premature fan failure A typical installation requires that the fresh air supply flow is at 85 of the extraction air flow and this can be allowed for in fan pressure switch adjustments to control minimum 14 4 Using a current monitor to monitor the fan s A current monitor may be used instead of a fan pressure switch to check that the fan is o...

Page 6: ...w Sensor Status signal Air Flow 240vac signal to Isolation valve Plastic tubing Fan Extract fan isolator or speed controller Gas proving Valve Gas Flow Extract Duct VENTAM 85 CONTROL SYSTEM Air Flow pressure switch mounted adjacent to each fan Com N O ve ...

Page 7: ...x outlet plate adj to valve 6 Panel provides a switched 240Vac supply to operate the gas isolation valve 7 Panel should be mounted in an accessible position approx 1 6m AFFL One line diagram for electrical first fix Note 6 Note 2 Note 3 Note 3 Supply Air Fan Flow Sensor next to fan Canopy Extract Air Fan Flow Sensor next to fan Ventam Systems Ltd Unit D4 Seedbed Business Centre Vanguard Way Shoebu...

Page 8: ...rminals 3 Terminal 20 MUST NOT BE USED 4 Dungs gas pressure switch connections Terminal 2 normally open terminal 3 Common 5 Please phone 01702 382 307 if assistance is required L N E Incoming panel supply 240volt ac 2 3 N O C EXTRACT FAN PRESSURE SWITCH 2 3 N O C INLET FAN PRESSURE SWITCH ADDITIONAL EMERGENCY STOP BUTTON 3 2 C N O E GAS VALVE PRESSURE SWITCH E N L MAIN GAS VALVE 1 2 L N E GAS BYPA...

Reviews: