Additional Emergency Stop Buttons 

Where there is more than one emergency exit, a normally closed emergency stop button should 
be located at each exit . Additional emergency stop buttons are wired in series to terminals 11 
and 12.  This is a 12VDC circuit.

 

Gas Isolation Valve 

The  Gas  Isolation  Valve  must  only  be  powered  from  the  Ventam  85  Interlock  Panel,  as  per 
supplied wiring diagrams and in accordance with Electrical and Gas Regulations.   
The main gas valve is rated at 240 VAC. 
The main gas valve must be fitted in an accessible location for future maintenance. 
The main Gas Isolation Valve must be fitted in the 

kitchen equipment

 gas supply pipe work. 

 
 

The  valve  is  connected  to  the  Ventam  85  Control  Panel  via  three  off  THREE  core  cables.  
(These are all Live, Neutral and Earth). 
The gas isolation valve is heavy.  Ensure that the gas pipe-work it is adequately supported. 

 

Fan Pressure switch(es). 

 

The Fan Pressure switch is mounted adjacent to and above the Fan. 
The Fan Pressure switch is connected to the Panel by a two-core cable (12VDC). 
The Fan Pressure switch is connected to the Fan ductwork by a flexible tube which is supplied 
with the switch.

 

The Fan Pressure switch senses the airflow and sends a “Fans On” signal to the Control Panel. 
The Fan pressure switch unit must be mounted vertically with tube connections at the bottom or 
the side and usually within one metre of the fan and in a dry, accessible location. 
The pressure switch should be located immediately above the fan.  Where this is not possible, 
the pressure switch must be mounted as high as practicable to allow the pressure switch tubing 
to slope down from the pressure switch unit to the ductwork connector.   
Pressure switch tubing must slope down continuously from the pressure switch to the ductwork 
to  allow  condensate  to  naturally  drain  from  the  pipe  work  to  prevent  blockages  occurring.  
Twists, loops and kinks are not permitted in the pressure switch tubing.   
The pressure switch unit location must allow 600mm clearance to the front and 150mm below 
for access and maintenance.  
DO  NOT  mount  the  pressure  switch  on  the  ductwork  or  transmitted  vibrations  may  cause 
unreliability and reduce the operating life of the unit.

 

 

 

Fan Pressure switch location

 

Consider the best location for mounting the unit AND for connecting the pipes from the pressure 
switch to the ductwork  
Mount the pressure switch(es). unit following above guide-lines. 

  The suction side of the fan is at a negative pressure.   Connect this side to the 

– ve pressure 

connection on the pressure switch. The switch will detect a differential pressure between the 
ductwork  negative  pressure  and  the  atmospheric  pressure.  This  differential  pressure  will 
close the switch. 

  At the pressure switch, the tube is connected to the push-fit connector on the bottom of the 

pressure switch. This connector is identified with a “―“  

  At  the  ductwork,  the  tube  is  connected  onto  the  push-fit  ductwork  connector  supplied  with 

the pressure switch. Cut the tubing to the required length. 

  The pressure switch connection should be as close as possible to the fan. 
  Use a digital pressure meter in the range of 0-2mbar to check the system pressure while the 

fan  is  running  at  full  speed  and  rotate  the  duct  connector  whilst  measuring  the  recorded 
negative pressure.  

  The arrow direction on the duct connector should oppose the airflow direction when fitted to 

the duct .  This normally provides the best pressure reading possible.  

  Pressure switch tubing  must be protected and secured to prevent damage. 

Summary of Contents for 85

Page 1: ...e the main gas isolation valve has opened if the gas pressure subsequently falls below a pre set level 60 of line pressure or a fan is turned off the main gas valve will close Each time a fan is turned off OR an emergency stop is depressed OR the line gas pressure falls too low the system MUST BE GAS PROVED AGAIN 3 Ventam 85 Interlock Panel Location Install the Ventam 85 Interlock Panel adjacent t...

Page 2: ...ressure switch unit to the ductwork connector Pressure switch tubing must slope down continuously from the pressure switch to the ductwork to allow condensate to naturally drain from the pipe work to prevent blockages occurring Twists loops and kinks are not permitted in the pressure switch tubing The pressure switch unit location must allow 600mm clearance to the front and 150mm below for access ...

Page 3: ...l Install cables to suit the valve size between the Ventam 85 Control Panel and the Gas Valve Re set the Emergency Stop on the Control Panel by turning the button in the direction of the arrows on the button Ensure it is safe to start fan s Check all panel terminations are secure Use the correct tool and do not over tighten Ensure that the following factory installed terminal links are fitted if n...

Page 4: ...gency stop button panel will indicate Emergency Stop Re set additional emergency stop button on the front of panel Repeat step 11 7 for each additional emergency stop button fitted 12 0 Gas Proving check that gas cannot come on if fans are off Turn off one of the fans Fan s off lamp and Gas Off lamp will be lit Operate the Gas Power Switch by switching it to the right Depress the Start Gas Proving...

Page 5: ... the fan will run and this will prevent user problems and premature fan failure A typical installation requires that the fresh air supply flow is at 85 of the extraction air flow and this can be allowed for in fan pressure switch adjustments to control minimum 14 4 Using a current monitor to monitor the fan s A current monitor may be used instead of a fan pressure switch to check that the fan is o...

Page 6: ...w Sensor Status signal Air Flow 240vac signal to Isolation valve Plastic tubing Fan Extract fan isolator or speed controller Gas proving Valve Gas Flow Extract Duct VENTAM 85 CONTROL SYSTEM Air Flow pressure switch mounted adjacent to each fan Com N O ve ...

Page 7: ...x outlet plate adj to valve 6 Panel provides a switched 240Vac supply to operate the gas isolation valve 7 Panel should be mounted in an accessible position approx 1 6m AFFL One line diagram for electrical first fix Note 6 Note 2 Note 3 Note 3 Supply Air Fan Flow Sensor next to fan Canopy Extract Air Fan Flow Sensor next to fan Ventam Systems Ltd Unit D4 Seedbed Business Centre Vanguard Way Shoebu...

Page 8: ...rminals 3 Terminal 20 MUST NOT BE USED 4 Dungs gas pressure switch connections Terminal 2 normally open terminal 3 Common 5 Please phone 01702 382 307 if assistance is required L N E Incoming panel supply 240volt ac 2 3 N O C EXTRACT FAN PRESSURE SWITCH 2 3 N O C INLET FAN PRESSURE SWITCH ADDITIONAL EMERGENCY STOP BUTTON 3 2 C N O E GAS VALVE PRESSURE SWITCH E N L MAIN GAS VALVE 1 2 L N E GAS BYPA...

Reviews: