6
4.0 Technical Data
Dimensions (mm)
Height
Width
Depth
Minimum clearances (mm)
Both sides
Above casing
Below casing
Front for servicing
Front in operation
Lift weight (kg)
Power consumption @ 0Pa (watts)
Suitable for
Ø
100mm circular ducts.
Suitable for
Ø
15mm pipe.
220-240V
~
50Hz
3 Amps
3.15 Amps
EU2
412
552
285
5
200
100
250
None
17
Speed 1
Speed 2
Speed 3
Speed 4
Speed 5
Speed 6
10
13
21
35
56
75
Duct connections
Condensate connection
Electrical supply
External fuse rating
Internal fuse rating
Filtration
Appliance must be connected to an earthed supply
Fig. 4
SAP Appendix Q Test Results
As tested and published by BRE (Building Research Establishment).
www.sap-appendixq.org.uk
Exhaust
terminal
configuration
Fan speed
setting
Total flow
supply rate (l/s)
Total exhaust
flow rate (l/s)
Specific fan
power (W/l/s)
Heat recovery
efficiency (%)
K 1
additional wet
room
K 2
additional wet
rooms
2
3
15.0
21.0
15.0
21.1
0.81
0.95
63
57
Fig. 3