Vent-Axia LoWatt HR204 User, Installation & Servicing Instructions Download Page 11

11

6.0 Installation Requirements

N

L

1
2

1

2

3

4

5

6

7

8

Normal

Boost

1

2

3

4

5

4

5

6

ON

Remove bottom cover panel

to access the fan speed

settings & condensate connection.

The condensate

outlets

are marked

on the

wall template.

Wall template

Mains

lead

Cable

clamp &

grommet

for

mains

lead

Fuse

Fit fused double

pole isolator

Fit

3 Amp

fuse

Rear exit for

condensate

Cable clips for

accessories lead

FRONT

UP

Knock out

for side exit 

condensate

Wall template

 

HR204 &

HR205 

(with cooker hood)

Whole House Ventilation System

Exhaust

Out

Fresh Air

In

Hot Stale

Air In

Warm Air

Out

Minimum

Top

Clearance

200mm

Part No. 372706

98mm

Cooker Hood

Bottom of

MVHR Unit

Bottom of

Cooker Hood

Top of
MVHR

Unit

Bottom of
Mounting

Brackets

4 Fixing Holes

(Key Holes)

Use one

hole each side

Bottom

Fixing Hole

Back Case

Condensate Hole

Side Case Knock

Out Condensate Hole

Minimum Side

Clearance 1mm

Minimum Side

Clearance 1mm

Bottom Condensate

Pipe Exit (HR204 On

ly)

Minimum Bottom Clearance

100mm

(HR204 Model)

Minimum Side

Clearance

24mm

(HR205c)

Minimum Side

Clearance

5mm

(HR204)

MVHR

Side

Minimum Side

Clearance

24mm

(HR205c)

Minimum Side

Clearance

5mm

(HR204)

MVHR

Side

All dimensions

in mm

Minimum Top

Clearance

for servicing

200

Minimum

Side

Clearance

5

Minimum

Side

Clearance

5

Clearances

HR204

Minimum Bottom

Clearance

100

Minimum

Front

Clearance

for

servicing

250

280

Clearances

HR205

Minimum

Side

Clearance

(MVHR)

24

Minimum

Side

Clearance

(MVHR)

24

Minimum

Top Clearance

for servicing

200

300

Minimum

Front

Clearance

for servicing

250

Minimum Bottom

Clearance from Hob

700

Minimum

Side

Clearance
(C.Hood)

1

Measure Minimum
Bottom Clearance

700mm

From Hob

(HR205c Model)

Mains
Cable
Outlet

Top view of unit

Fig. 9

6.4

System controls

6.5

Electrical supply

1. External wiring must be correctly earthed ,
polarised and in accordance with the current

I.E.E. Regulations

.

2. The mains supply must be 220-240V ~ 50Hz
fused at 3 Amps.

6.6

Condensate drain

1. The condensate pipe should have a
continuous fall of 10° (1 in 6) with as much of the
condensate pipe as possible run inside the
property to avoid freezing. The pipe should also
incorporate a trap with a minimum height of
75mm or similar device to prevent a return of
foul air from the waste pipe. See Fig. 

.

11

The LoWatt HR204 has three condensate outlet

positions; rear, bottom and left hand side.

Cable

clamp &

grommet

for

accessories

lead

See page 8 for a list of optional controls. 
These are used to switch the LoWatt HR204 
from normal speed to boost speed.

Note: The method of connection to the 
mains supply must facilitate complete 
electrical isolation of the appliance. 
Connection may be via a fused double pole 
isolator with a contact separation of at least 
3mm in all poles and supplying the LoWatt 
HR204 and its controls only. The LoWatt 
HR204 is not designed to be fitted with a 
plug.

Summary of Contents for LoWatt HR204

Page 1: ...Please leave these instructions with the user Whole House Ventilation System with Heat Recovery User Installation Servicing Instructions LoWatt HR204 ABC...

Page 2: ...ation 3 0 General Layout 4 0 Technical Data 5 0 Appliance Operation 6 0 Installation Requirements 7 0 Installation 8 0 Wiring Diagrams 9 0 Commissioning 10 0 Maintenance 11 0 Changing Components 12 0...

Page 3: ...nd phase complies with the rating label 5 The LoWatt HR204 should only be used in conjunction with the appropriate Vent Axia accessories 6 When the LoWatt HR204 is used to remove air from a room conta...

Page 4: ...st Out Fresh Air In Hot Stale Air In Warm Air Out Applicable only to products installed and used in the United Kingdom For details of the Guarantee outside of the United Kingdom contact your local sup...

Page 5: ...upplied out to dry rooms 1 2 8 10 9 11 15 6 7 14 4 13 5 12 Fig 2 3 1 Heat exchanger 2 Fan fresh air in 3 Rating label 4 Fuse 5 Speed select PCB 6 Accessory switch connection 7 Dip switch for speed sel...

Page 6: ...ed 6 10 13 21 35 56 75 Duct connections Condensate connection Electrical supply External fuse rating Internal fuse rating Filtration Appliance must be connected to an earthed supply Fig 4 SAP Appendix...

Page 7: ...5 The unit has six speeds One of the lowest five can be selected for normal speed One of the top 3 can be selected for boost speed The performance curve chart gives the ventilation rates at each fan s...

Page 8: ...boost Switch NBSW N m or al Bo t os Humidity Sensor HS6 Normal boost Pull Cord Switch PCSW CMSM control TIM2 timer The LoWatt HR204 can only be connected to external controls with an uncommitted rela...

Page 9: ...ents must also be sited away from other flue terminals ventilators etc on the outside of the dwelling In addition there shall be adequate ventilation of the kitchen when a cooker hood is used at the s...

Page 10: ...drawn back into the house 2 The duct work system should be sized and installed to minimise the pressure loss along it 3 Using larger diameter pipes and keeping the number of bends and fittings used t...

Page 11: ...Minimum Front Clearance for servicing 250 280 Clearances HR205 Minimum Side Clearance MVHR 24 Minimum Side Clearance MVHR 24 Minimum Top Clearance for servicing 200 300 Minimum Front Clearance for se...

Page 12: ...200 Minimum Side Clearance 5 Minimum Side Clearance 5 Clearances HR204 Minimum Bottom Clearance 100 Minimum Front Clearance for servicing 250 280 Clearances HR205c Minimum Side Clearance MVHR 24 Minim...

Page 13: ...y until it discharges into the drain Fig 11 Remove bottom cover panel to access the fan speed settings condensate connection Condensate rear exit shown Side View Front Rear Condensate drain 15mm Rear...

Page 14: ...set to the appropriate speed as determined by air flow required and duct system pressure see page 7 2 To change the speed settings of the fans change the position of the dip switches on the PCB The 5...

Page 15: ...al Boost Switch NBSW or Pull Switch PCSW Common Boost Normal L Fan air out Fan air in SPEED SELECT 1 2 L N 1 2 3 4 5 6 7 8 Normal Boost 1 2 3 4 5 4 5 6 ON MOTOR CONTROL A B MOTOR SUPPLY A B 220 240V 5...

Page 16: ...MOTOR SUPPLY A B 220 240V 50Hz MOTOR B CONTROL P C B MOTOR A CONTROL P C B CHASSIS N 16 8 0 Wiring Diagrams Fig 14 LoWatt HR204 Wiring CMSM controller CMSM Controller L N L Live in Neutral in Live to...

Page 17: ...0 Wiring Diagrams 1 2 Fig 15 L Fan air out Fan air in SPEED SELECT 1 2 L N 1 2 3 4 5 6 7 8 Normal Boost 1 2 3 4 5 4 5 6 ON MOTOR CONTROL A B MOTOR SUPPLY A B 220 240V 50Hz MOTOR B CONTROL P C B MOTOR...

Page 18: ...d adjust until the system is correctly balanced Note If the flow rates have been achieved with all the louvres nearly closed it may be possible to reduce the fan speed and re adjust the louvre setting...

Page 19: ...seal Fig 17 The following cleaning and disinfection routine should be conducted every 6 months to maintain the efficiency and hygiene of the unit It should be carried out by a suitably qualified pers...

Page 20: ...PPLIANCE Fig 18 4 Make a note of the connections between PCBs and motors 5 Disconnect the motor cables mains cable and boost switch cable Remove chassis and PCBs completely 6 Replace PCBs as necessary...

Page 21: ...e to the fan 5 Remove the bracket and re fit to the new fan 6 Re assemble with the new fan in reverse order ensuring the cable does not foul the fan motor Check the electrical installation for earth c...

Page 22: ...uit and Resistance to Earth Ensure all external controls are operating and are set to normal running Ensure that a mains electrical supply is available to the unit Refer to diagrams below to identify...

Page 23: ...problem drive PCB Replace fan drive PCBs NO YES Did this solve the problem Replace fans FINISH If the either fan does not rotate check the entire system and unit for correct installation Check all du...

Page 24: ...372737 Heat exchanger seals 4 off 372739 Outer door cover assembly Optional extras 370254 Humidity sensor HS6 370495 Normal boost switch NBSW 370278 Normal boost pull cord switch PCSW 2 3 4 5 6 7 8 9...

Reviews: