Vent-Axia Lo-Carbon VA100 SELV LHTP Installation And Wiring Instructions Download Page 6

 

1. 

Select and follow the appropriate wiring diagram. (Fig. 2 or 3) 

2. 

Check all connections have been made correctly and ensure all terminal 
connections and cable clamps are securely fastened. 

3. 

Ensure the impeller rotates and is free from obstructions. 

4. 

DO NOT TEST THE FAN WITHOUT THE GRILLE SECURELY FASTENED.  
THIS COULD POTENTIALLY CAUSE DAMAGE TO THE SHUTTER 
MECHANISM. 

 

C. SETUP 
 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT 
MUST BE ISOLATED FROM THE POWER SUPPLY DURING THE 
INSTALLATION / OR MAINTENANCE. 

 

SPEED SETTING (Fig. 4): 

The fan has two speed settings for different installation requirements: 
 

1) 

High speed – for ducted installations: Replace jumper. 

2) 

Normal speed – for wall/window installations: Remove jumper. 

TIMER ADJUSTMENT (LT/XT/LHTP/XHTP MODELS) 

BEFORE ADJUSTING THE TIMER, SWITCH OFF THE MAINS SUPPLY. TIMER 
SHOULD ONLY BE ADJUSTED BEFORE OR DURING INSTALLATION. 

 
1. 

Remove the fan grille. The controller is factory set at 15 minutes 
approx. The overrun time period can be adjusted from approximately 
3-30 minutes by altering the adjuster on the control PCB. 

2. 

To REDUCE the operating time, use a small screwdriver to turn the 
adjuster Fig.4. ANTI-CLOCKWISE.  

3. 

To INCREASE the operating time, use a small screwdriver to turn the 
adjuster Fig.4. CLOCKWISE. 

4. 

Replace the fan grille. 

 

HUMIDITY SET-POINT ADJUSTMENT (LHTP/XHTP MODELS ONLY) 

BEFORE ADJUSTING THE CONTROLLER, SWITCH OFF THE MAINS SUPPLY. 
HUMIDISTAT SHOULD ONLY BE ADJUSTED BEFORE OR DURING 
INSTALLATION. 

 

1. 

Remove the fan grille. The controller is factory set to switch on at 
about 70% RH. The humidity set point can be adjusted from 65-
95%RH by altering the adjuster on the control PCB. 

2. 

To LOWER the set-point use a small screwdriver to turn the adjuster 
Fig.4. ANTI-CLOCKWISE. This makes the controller MORE sensitive.  

3. 

To RAISE the set-point use a small screwdriver to turn the adjuster 
Fig.4. CLOCKWISE. This makes the controller LESS sensitive.  

4. 

Replace the fan grille. 

Summary of Contents for Lo-Carbon VA100 SELV LHTP

Page 1: ...0 49A XP 44 16 15A LT 45 90 50A XT 44 16 16A LHTP 43 60 64A XHTP PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS VA100 Lo Carbon SELV RANGE IPX7 FAN UNITS 12V...

Page 2: ......

Page 3: ...nsure that the air replacement is adequate for both the fan and the fuel burning appliance G The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of...

Page 4: ...cubicle or enclosure It must be sited away from direct sources of water spray and out of reach 1 5m of a person using a fixed bath or shower 2 Site away from direct sources of heat Ambient temperature...

Page 5: ...diameter hole in the glass 2 Fit spacers as required behind the fan back plate engaging the locating pips in the corner holes 3 Place the fan spigot through the hole in the glass from the inside with...

Page 6: ...ATION 1 Remove the fan grille The controller is factory set at 15 minutes approx The overrun time period can be adjusted from approximately 3 30 minutes by altering the adjuster on the control PCB 2 T...

Page 7: ...ill return to the auto humidity sensing mode once the pullcord is switched into the off position The LED indicator light will only activate if the PULLCORD is in the ON position LED INDICATOR LIGHT OP...

Page 8: ...LP XP LHTP XHTP if the Timer is not used Fig 1 N L 1 Phase Supply 220 240V 50Hz FUSE Switched Fused Spur 3A LS 12V 0V Controller Fan 12V D C SELV Supply N L LS LS N L 2 1 3 N LS 12V 0V Controller Fan...

Page 9: ...t 65 95 RH Overrun timer adjustment 1 30min SPEED SETTING The fan has two speed settings for different installation requirements High speed for ducted installations Replace jumper Normal speed for wal...

Page 10: ...ol Factor Control Typology CTRL Typology Control Factor CTRL 1 00 1 00 0 95 0 65 0 95 0 65 Control Typology Manual Control Manual Control Clock Control Local Demand Control Clock Control Local Demand...

Page 11: ...Notes...

Page 12: ...ective the product will be repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Ha...

Reviews: