WALL MOUNTING 

(WALL KIT SUPPLIED SEPARATELY – SEE ACCESSORIES ON PREVIOUS PAGE)

 

1. 

For wall mounting cut a 117mm diameter hole through the wall and insert 
the wall sleeve. Slope the sleeve slightly downwards away from the fan. Cut 
to length and cement both ends into position flush with the wall faces.  

2. 

Loosen the screw in the bottom of the grille and remove the front grille. Mark 
the screw centres through the holes in the fan back plate. Drill, plug and 
screw into position. Fix exterior grille into position with the louvres positioned 
downwards. (Note:- The grille must comply with the standard requirements 
of your country to prevent access to the fans impeller) 

3. 

Wire the fan as described in Section B-Wiring. Adjust any settings as 
required (see Section C-Setup). 

4. 

Replace the grille and tighten the retaining screw. 

5. 

After installation, ensure impeller rotates freely and the shutters can open. 

 
WINDOW MOUNTING 

(WINDOW KIT SUPPLIED SEPARATELY – SEE ACCESSORIES ABOVE)

  

   The following instructions are for 105-110mm holes only – using the 

254101A window mounting kit. For 110-140mm holes please use 
443234 window kit and refer to the supplied instructions.   

1.  

Cut a 105mm diameter hole in the glass. 

2.  

Fit spacers as required behind the fan back plate, engaging the locating pips 
in the corner holes. 

3.  

Place the fan spigot through the hole in the glass from the inside, with a 
gasket on each side of the glass. 

4.  

From the outside, place on the remaining spacer, with the locating pips 
facing outwards. For double-glazing and materials up to 40mm thick, one or 
more spacers may be discarded. 

5.  

Draw the assembly together with the threaded fixing ring. Do not over-
tighten. 

6.  

Fix the exterior grille in position, using the screws provided, with the louvres 
pointing downwards. 

 

AFTER INSTALLATION ENSURE IMPELLER ROTATES FREELY

 

 
B. WIRING.

 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING THE INSTALLATION / OR 
MAINTENANCE. 

 

IMPORTANT: The

 

Controller

 

MUST

 be surface mounted to allow air to freely 

circulate around the unit. When installed in a loft void it 

MUST

 

NOT

 be enclosed 

or covered with insulation. 
There are two methods of cable entry to the fan. If the side cable entry option is 
used, ensure the supplied grommet is used and maintains a good seal to prevent 
water ingress.  
The fan must be powered at all times to allow the shutter to work correctly. If there 
is a requirement to switch the fan via an external switch, this should be connected 
to the LS connection and not by switching L/N supply. 

Summary of Contents for Lo-Carbon VA100 SELV LHTP

Page 1: ...0 49A XP 44 16 15A LT 45 90 50A XT 44 16 16A LHTP 43 60 64A XHTP PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS VA100 Lo Carbon SELV RANGE IPX7 FAN UNITS 12V...

Page 2: ......

Page 3: ...nsure that the air replacement is adequate for both the fan and the fuel burning appliance G The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of...

Page 4: ...cubicle or enclosure It must be sited away from direct sources of water spray and out of reach 1 5m of a person using a fixed bath or shower 2 Site away from direct sources of heat Ambient temperature...

Page 5: ...diameter hole in the glass 2 Fit spacers as required behind the fan back plate engaging the locating pips in the corner holes 3 Place the fan spigot through the hole in the glass from the inside with...

Page 6: ...ATION 1 Remove the fan grille The controller is factory set at 15 minutes approx The overrun time period can be adjusted from approximately 3 30 minutes by altering the adjuster on the control PCB 2 T...

Page 7: ...ill return to the auto humidity sensing mode once the pullcord is switched into the off position The LED indicator light will only activate if the PULLCORD is in the ON position LED INDICATOR LIGHT OP...

Page 8: ...LP XP LHTP XHTP if the Timer is not used Fig 1 N L 1 Phase Supply 220 240V 50Hz FUSE Switched Fused Spur 3A LS 12V 0V Controller Fan 12V D C SELV Supply N L LS LS N L 2 1 3 N LS 12V 0V Controller Fan...

Page 9: ...t 65 95 RH Overrun timer adjustment 1 30min SPEED SETTING The fan has two speed settings for different installation requirements High speed for ducted installations Replace jumper Normal speed for wal...

Page 10: ...ol Factor Control Typology CTRL Typology Control Factor CTRL 1 00 1 00 0 95 0 65 0 95 0 65 Control Typology Manual Control Manual Control Clock Control Local Demand Control Clock Control Local Demand...

Page 11: ...Notes...

Page 12: ...ective the product will be repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Ha...

Reviews: