Vent-Axia Lo-Carbon Quadra SELV Series Installation And Wiring Instructions Download Page 4

6. 

Remove the small Internal Cover that covers the Terminal Block in the top right corner (

fig 3

). 

7. 

Using the Fan Chassis as a template, carefully sliding the spigot into the Wall Liner, mark the 
fixing hole centres on the wall.  

8. 

Drill and plug the wall using the fixings provided. 

9. 

Feed the wiring through the hole near the Terminal Block (

fig.

4) and secure the Fan into 

position using the screws provided.  

10.  Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

11.  Replace the Internal Cover over the Terminal Block.  
12.  Ensure the Impeller (

fig.3

) rotates freely. 

13.  Replace the Front Cover Assembly and tighten the two screws. 
14.  Switch the mains power supply on and check the fan is operating correctly 

 

FLUSH MOUNTING (PANEL/CEILING)  

A Flush Mount Kit (439256) is required. 
1. 

Remove the Front Assembly by slackening 2 Cover Screws by 2 turns (

fig.2).

 Lift the front 

assembly away from the bottom edge then the top edge.  

2. 

Mark and cut a rectangular hole 225mm (w) x 255mm (h) through the panel ensuring that 
there is sufficient space for the product to be installed and that the optional Filter (

fig.3

) can 

be removed for maintenance.  

3. 

Remove the Back Box by removing the 4 screws. Replace it with the Frame from the 
Accessory Kit 439256. (

Fig 5

). 

4. 

Slide each Panel Clip in to the Chassis then pass each of the long Panel Clip Screws 
(supplied in the kit) fully through the flange of the Chassis and screw in to the Panel Clips 

(fig.6.) 

allowing enough space between the Panel Clip and the flange for the thickness of the 

panel (so that the clips can spring open behind the panel).

 

 

5. 

Set-up the appropriate speed selection and other features as outlined in 

Section B SETUP.

 

6. 

Remove the Internal Terminal Block Cover that covers the Terminal Block in the top right 
corner (

fig 3 & 4

). 

7. 

Attach the ducting to the Spigot and locate into the hole in the panel, ensuring the cable is 
fed into the Fan Chassis (

fig.

4) and the Panel Clips spring out behind the panel.  

8. 

Secure into position by carefully tightening the 4 Panel Clip Screws. 

IMPORTANT: If power 

tools are used, set them to the minimum torque setting or preferably use a manual 
screwdriver. Do not over tighten.

 

9. 

Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

10.  Replace the Internal Cover over the Terminal Block. 
11.  Ensure the Impeller rotates freely (

fig.3

). 

12.  Replace the Front Cover Assembly and tighten the two screws. 
13.  Switch the mains power supply on and check the fan is operating correctly. 
 

B. SETUP 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING INSTALLATION OR 
MAINTENANCE. 

 

 

With the Cover removed the humidity adjustment, overrun timer adjustment, speed selection 
switches and installation type switches are accessible in the bottom right corner of the product 
(

figs.4 & 7

). 

 
1. SELECTING THE CONSTANT TRICKLE SPEED (0, 6, 9 or 12 l/s) 

This will determine the speed at which the fan will run most of the time except when boost is 
activated by either the Pullcord, PIR, LS, or Relative Humidity Sensor.  

 

i. 

Slide one of the three switches marked as ‘Normal/Trickle Speed’ in 

fig.7

 to the right (on 

position) to select that flow rate for trickle speed.  

Summary of Contents for Lo-Carbon Quadra SELV Series

Page 1: ...Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Lo Carbon Quadra SELV IPX7 Safety Extra Low Voltage Stock Ref N Quadra SVTP 442865 Quadra SVHTP 4...

Page 2: ...hin reach of a person using a fixed bath or shower i e in a nearby wall However the fan must not be placed where it could be submerged in water or regularly exposed to direct water spray e g from a sh...

Page 3: ...installed and that the optional Filter fig 3 could be removed for cleaning The cardboard fitment in the packaging can be used as a template 3 Set up the appropriate speed selection and other features...

Page 4: ...and the flange for the thickness of the panel so that the clips can spring open behind the panel 5 Set up the appropriate speed selection and other features as outlined in Section B SETUP 6 Remove th...

Page 5: ...r RH ii To RAISE the Set Point turn the Humidity Adjuster figs 4 7 CLOCKWISE This makes the fan less sensitive to RH i e the fan will come on at a higher RH C WIRING WARNING THE FAN AND ANCILLARY CONT...

Page 6: ...embly and Impeller in warm soapy water if they are dirty Do not use abrasive cleaners Dry the parts before replacing them 7 Turn the power to the Fan back on The fan has sealed for life bearings which...

Page 7: ...Terminal Block Cover Spigot Cover Assembly Chassis Assembly Impeller Optional Filter Fig 4 Internal Terminal Block Cover Cable Clamp Terminal Block Timer and Humidity Adjustment Speed and Installation...

Page 8: ...Fig 5 Frame from optional Flush Mount Kit Back Box Fig 6 Panel Clip Screw 4 off Panel Clip 4 off...

Page 9: ...e set point Speed Selection Switches Example shown is boost speed of 15 l s and normal trickle speed of 6 l s Installation Type Selection Switches Through the wall installation 1 5m 100mm ducting with...

Page 10: ...Fig 9 Wiring diagram without LS connection Fig 10 Wiring diagram with LS connection N Ls 0V Fan Controller LS L N SELV Supply 24V DC 3A UK 24V LS 24V 0V N Ls 0V Fan Controller LS L N SELV Supply 24V...

Page 11: ...l Factor CTRL 0 65 0 65 0 65 Control Typology Clock Control Local Demand ControlLocal Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchanger...

Page 12: ...e repaired or at the Company s option replaced without charge provided that the product Has been installed and used in accordance with the instructions given with each unit Has not been connected to a...

Reviews: