Vent-Axia Lo-Carbon Quadra HTP Installation And Wiring Instructions Download Page 5

IMPORTANT 

On first power up, the fan will run through its initialization routine. 
On 

TP

HTP

 & 

TM

 models the fan will switch on and off during this routine 

(Including the LED) 
Once complete after approximately 2 minutes, the fan will run as normal. 

FLUSH MOUNTING (PANEL/CEILING)  

A Flush Mount Kit (439256) is required. 
1. 

Remove the Front Assembly by slackening 2 Cover Screws by 2 turns (

fig.2).

 Lift the front 

assembly away from the bottom edge then the top edge.  

2. 

Mark and cut a rectangular hole 225mm (w) x 255mm (h) through the panel ensuring that 
there is sufficient space for the product to be installed and that the optional Filter (

fig.3

) can 

be removed for maintenance.  

3. 

Remove the Back Box by removing the 4 screws. Replace it with the Frame from the 
Accessory Kit 439256. (

Fig 5

). 

4. 

Slide each Panel Clip in to the Chassis then pass each of the long Panel Clip Screws 
(supplied in the kit) fully through the flange of the Chassis and screw in to the Panel Clips 

(fig.6.) 

allowing enough space between the Panel Clip and the flange for the thickness of the 

panel (so that the clips can spring open behind the panel).

 

 

5. 

Set-up the appropriate speed selection and other features as outlined in 

Section B SETUP.

 

6. 

Remove the Internal Terminal Block Cover that covers the Terminal Block in the top right 
corner (

fig 3 & 4

). 

7. 

Attach the ducting to the Spigot and locate into the hole in the panel, ensuring the cable is 
fed into the Fan Chassis (

fig.

4) and the Panel Clips spring out behind the panel.  

8. 

Secure into position by carefully tightening the 4 Panel Clip Screws. 

IMPORTANT: If power 

tools are used, set them to the minimum torque setting or preferably use a manual 
screwdriver. Do not over tighten.

 

9. 

Select and follow the appropriate wiring diagram in 

Section C WIRING.

 

10.  Replace the Internal Cover over the Terminal Block. 
11.  Ensure the Impeller rotates freely (

fig.3

). 

12.  Replace the Front Cover Assembly and tighten the two screws. 
13.  Switch the mains power supply on and check the fan is operating correctly. 
 

B. SETUP 

 

WARNING: THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE 
ISOLATED FROM THE POWER SUPPLY DURING INSTALLATION OR 
MAINTENANCE. 

 

 
 
 
 
 
 
 

With the Cover removed the humidity adjustment, overrun timer adjustment, speed selection 
switches and installation type switches are accessible in the bottom right corner of the product 
(

figs.4 & 7

). 

 
1. SELECTING THE CONSTANT TRICKLE SPEED (0, 6, 9 or 12 l/s) 

This will determine the speed at which the fan will run most of the time except when boost is 
activated by either the Pullcord, PIR, LS, or Relative Humidity Sensor.  

 

i. 

Slide one 

of the three switches marked as ‘Normal/Trickle Speed’ in 

fig.7

 to the right (on 

position) to select that flow rate for trickle speed.  

ii. 

Setting all of those 3 switches to the left (off positions) will switch off the constant trickle 
option (i.e the fan will normally be off and will switch to boost when the Pullcord, PIR, LS 
or Humidity Sensor are activated). 

 
 

 
 

Summary of Contents for Lo-Carbon Quadra HTP

Page 1: ...Instructions PLEASE READ INSTRUCTIONS IN CONJUNCTION WITH ILLUSTRATIONS PLEASE SAVE THESE INSTRUCTIONS Lo Carbon Quadra Centrifugal Fan 220 240V 50Hz Stock Ref N Quadra TP 439251A Quadra TM 439253A Q...

Page 2: ...n accessory 439927 Option to boost from constant trickle or from off Three trickle speed options available selectable during installation 6 9 or 12 l s Three boost speed options available selectable d...

Page 3: ...adequate for both the fan and the fuel burning appliance G The Fan should not be used where it is liable to be subject to direct water spray for prolonged periods of time H Where ducted Fans are used...

Page 4: ...mains power supply on and check the fan is operating correctly SURFACE MOUNTING WALL For through the wall installations a Wall Kit 25 41 02 White 25 41 00 Brown can be used 1 Remove the Front Cover A...

Page 5: ...the hole in the panel ensuring the cable is fed into the Fan Chassis fig 4 and the Panel Clips spring out behind the panel 8 Secure into position by carefully tightening the 4 Panel Clip Screws IMPOR...

Page 6: ...t rate use the integral pullcord or remote switch via the LS connection i To LOWER the Set Point turn the Humidity Adjuster figs 4 7 ANTI CLOCKWISE This makes the fan more sensitive to RH i e the fan...

Page 7: ...wet cloth until clean 6 Wash the Filter Cover Assembly and Impeller in warm soapy water if they are dirty Do not use abrasive cleaners Dry the parts before replacing them 7 Turn the power to the Fan...

Page 8: ...Terminal Block Cover Spigot Cover Assembly Chassis Assembly Impeller Optional Filter Fig 4 Internal Terminal Block Cover Cable Clamp Terminal Block Timer and Humidity Adjustment Speed and Installation...

Page 9: ...Fig 5 Frame from optional Flush Mount Kit Back Box Fig 6 Panel Clip Screw 4 off Panel Clip 4 off...

Page 10: ...Speed Selection Switches Factory setting shown is boost speed of 15 l s and normal trickle speed of 6 l s Installation Type Selection Switches Through the wall installation 1 5m 100mm ducting with one...

Page 11: ...Fig 10 Wiring diagram with LS connection N L Ls 1 Phase Supply 220 240V 50 Hz 3A Fuse Pull Cord Lamp 3 Pole Isolator Switch Ceiling Junction Pull Cord if applicable Fan N L L N 1 Phase Supply 220 240...

Page 12: ...tor CTRL 0 65 0 65 0 65 Control Typology Clock Control Local Demand Control Local Demand Control Declared Max Internal External Leakage Rates for BVUs or carry over for regenerative heat exchangers on...

Page 13: ......