Installation Instructions
Distributed by Simx Limited
[email protected] | www.manrose.co.nz
Installation Instructions
Specifications are subject to change without notice.
Page 5
[email protected] | www.manrose.co.nz
Distributed by Simx Limited
MultiVent Continuous Extract Ventilation
MultiVent Continuous Extract Ventilation
INSTALLATION
INSTALLATION
As per the picture above try to position the MultiVent fan housing in a location central to all of the rooms that you are planning to extract from.
Also remember that the unit could create noise and should be mounted away from bedrooms. Mount the MultiVent using the 4 mounting points.
Bear in mind that the exhaust (main extraction) is using 150mm aluminium foil ducting and a 150mm weather proof cowl.
Each kit contains 3 x 4m lengths of 125mm aluminium foil ducting for the extraction points.
• Extend the 125mm aluminium foil ducting and slide the spigot collar over the ducting by approximately 150mm.
• Slide the 125mm aluminium foil ducting over the spigot.
• Slide the spigot collar over the ducting pressing it firmly all the way down the spigot clamping the aluminium foil ducting in place on the spigot.
To prevent the spigot being pushed out, have another person pushing up from below. Complete the other two rooms following the same instructions.
• Cut a 126mm (minimum) hole in the required locations in the kitchen (minimum 2m away from the stove top), bathroom and toilet.
• Disassemble the 125mm diffusers (DCT0186) and mount the 125mm spigots to the ceiling in each location using the four screws supplied.
• Fit the diffuser escutcheon by pushing it into the spigot.
• Mount the 125mm duct joiner (DCT0037) to the exhaust port of the MultiVent.
• Fit the 150mm to 125mm reducer (DCT3239) to the 125mm duct joiner and tape both joints using the supplied duct tape.
• Fit the 150mm aluminium foil ducting (DCT0214) to the 150mm waterproof cowl (DCT3535) and tape it to the spigot.
• From outside of the building cut a 150mm (minimum) hole in the outside cladding of the home and push the 150mm ducting through the hole.
• Fit the waterproof cowl to the building exterior and then from the roof space pull the ducting taut and tape it off at the 150mm to 125mm reducer.
• Extend each length of the 125mm aluminium foil ducting pulling it taut and tape off the three extraction points to the MultiVent unit.
• Install electrical wiring as per page 3 of the instruction manual.