Vent-Axia FAN7200 Installation Instructions Manual Download Page 2

Page 2 

                                                        

Specifications are subject to change without notice.      

Installation Instructions

 

Distributed by Simx Limited                                                                                                                

[email protected] | www.manrose.co.nz 

Installation Instructions

     

Specifications are subject to change without notice. 

Page 3

[email protected] | www.manrose.co.nz 

Distributed by Simx Limited

 

MultiVent Continuous Extract Ventilation

MultiVent Continuous Extract Ventilation

MULTIVENT CONTINUOUS EXTRACT VENTILATION SYSTEM INSTALLATION

AND ELECTRICAL CONNECTION MUST BE CARRIED OUT BY A REGISTERED ELECTRICIAN

BEFORE INSTALLING THE MULTIVENT CONTINUOUS EXTRACT VENTILATION SYSTEM, MAKE SURE YOU 

HAVE TURNED OFF THE MAIN ELECTRICITY SUPPLY. DO NOT TURN IT BACK ON UNTIL THE MULTIVENT 

CONTINUOUS EXTRACT VENTILATION SYSTEM IS FULLY

INSTALLED AND READY TO USE.

ALL ELECTRICAL WORK MUST BE CARRIED OUT BY A REGISTERED ELECTRICIAN IN ACCORDANCE

WITH THE LATEST WIRING RULES AS/NZS3000.

CAUTION

•  Do not install this product where excessive oil or a grease laden atmosphere is or may be, present

•  Do not install this product where corrosive or flammable gases, liquids or vapours are, or may be, present

•  Do not install this product where it may be subject to direct water spray from hoses

•  Do not install this product where access to, or removal, of the unit may be obstructed

•  Before use, please check that the supply voltage and that of the appliance are the same (see product rating label).
•  All wiring and wiring connections must comply with all current national wiring rules and regulations including AS/NZS3000:2017, 

 

 

or latest edition thereof.

•  Any changes or modifications made or attempted to this product, without the prior written approval of the manufacturer, 

 

 

 

will void any and all stated warranties.

•  This MultiVent continuous extract ventilation system is not intended for use by persons (including children) with reduced physical, sensory or  
 

mental capabilities, or lack of experience and knowledge, unless they are capable of, and have been given supervision or instruction concerning  

 

use of the appliance by a person responsible for their safety.

•  Children should be supervised to ensure that they do not play with the MultiVent continuous extract ventilation system.
•  In case of damage to the supply cord, switch off the device and do not tamper with it. Damaged supply cords must only be repaired or  

 

 

replaced exclusively by the manufacturer or by an appointed representative. Failure to comply with the above may endanger the safety of    

 

people and cause possible damage to the whole system.

•  The unit must not be connected directly to a tumble drier.
•  Precautions must be taken to avoid the back-flow of gases into the room from the open flue of gas or other fuel-burning appliances.
•  The exhaust grille should be located at least 600mm away from any flue outlet.

IMPORTANT

•  This MultiVent continuous extract ventilation system is hot when in use. To avoid burns, do not let bare skin touch hot surfaces.   

 

 

Keep combustible materials away from the unit and keep them away from the sides and rear.

•  Do not use near or in the immediate vicinity of a bath or swimming pool or any wet areas.
•  When installing fan through an external wall, an external wall grille must be fitted at all times.
•  This appliance incorporates an earth connection for functional purposes only.
•  To protect against electric shock, do not immerse cord or plug in water or any other liquids.
•  Do not insert or allow foreign objects to enter any ventilation openings, as this may cause an electric shock, fire or damage to the fan.
•  Do not put fingers or foreign objects into the grille while in operation.
•  Any changes or modifications made or attempted to this product, without the prior written approval of the manufacturer, will void any 

 

 

and all stated warranties.

•  To prevent overheating of this fan, keep the air inlets and outlets clean and free of anything that may cause blockage.   

 

 

 

Check all inlets and outlets from time to time to ensure it is clear of any dirt or dust accumulation. DO NOT COVER.

•  Do not use it in areas where gasoline, paint, or flammable liquids are used or stored.
•  This product contains recyclable materials. Do not dispose of this product as unsorted council waste. Please contact your local council for   
 

the nearest collection point. 

INSTALLATION

Position the unit, taking into consideration the position of the rooms to be ventilated, the exhaust position and the electrical services.  
Ensure there is adequate access for installation and maintenance.

If the unit is sited in the heated void of the dwelling a condensate drain should not be necessary. When sited in a roof cavity, consideration should 
be given to fitment of a condensate drain. Alternatively the unit and ducting can be externally insulated to minimize condensation within 

 

the units housing.

To reduce the system resistance in your duct system, and therefore lower the speed, power consumption and noise of the fan, 

 

follow these guidelines:
•  Keep the length of duct runs to a minimum, particularly the exhaust duct run.
•  If you need to use flexible ducting, make sure that it is fully extended and not crushed, sagging or torn.
•  Try to minimize the use of diffusers/valves by having similar length duct runs to the inlets.
•  The bend radius (measured to the inside of the bend), should be at least 1x the duct diameter.
•  Avoid having any bends, filters or other obstructions within 250mm of the fan inlets and outlet.

Securely mount the unit through the mounting holes on the casing using appropriate fixings (not supplied) for the mounting substrate. 
Fixings to be capable of securing 4x the weight of the unit. Unit weight: 4.1kg. Anti-vibration mounts, acoustic mats or rubber bushes 

 

can also be used. Installation example shown below.

To maintain the IPx2 rating of the unit, the unit must not be mounted with the cover removal slots facing upwards (as indicated by the red arrows), 
or at an angle where they are visible from above. All other orientations are acceptable.

Duct Supports

Exterior Grille

Airflow

Airflow

Interior Grille

Sealant

Cavity

Sleeve

Maximum length of
flexible ducting

Minimum radius =

diameter of ducting

Preferred flexible 

ducting route

Peaks and troughs

Restrictions

Main power
connections

Low voltage
connections

Summary of Contents for FAN7200

Page 1: ...2016 The MultiVent continuous extract ventilation is designed for the simultaneous ventilation of separate areas in the home and as a multipoint extraction system for a wide range of commercial applications The units can be wall ceiling or loft mounted Where the ambient air has a high humidity content condensate drains are provided SEC Control Max Leakage Rates Annual Electricity Consumption kWh a...

Page 2: ...the sides and rear Do not use near or in the immediate vicinity of a bath or swimming pool or any wet areas When installing fan through an external wall an external wall grille must be fitted at all times This appliance incorporates an earth connection for functional purposes only To protect against electric shock do not immerse cord or plug in water or any other liquids Do not insert or allow for...

Page 3: ...firmly all the way down the spigot clamping the aluminium foil ducting in place on the spigot To prevent the spigot being pushed out have another person pushing up from below Complete the other two rooms following the same instructions Cut a 126mm minimum hole in the required locations in the kitchen minimum 2m away from the stove top bathroom and toilet Disassemble the 125mm diffusers DCT0186 and...

Page 4: ...d to the LS terminal instead of connecting to a lighting circuit Terminal Description Connection Terminal Description Connection 1 L Live 220 240V AC L3 Brown 4 LS1 Live Switched 1 220 240V AC isolated L2 Black 2 N Neutral N Blue 5 LS2 Live Switched 2 220 240V AC isolated L1 Grey 3 Protective Earth E Green Yellow 6 NS Neutral Switched isolated Link to N NOTE LS1 LS2 and NS terminals are electrical...

Page 5: ... time if over run is enabled UNIT ADJUSTMENT 1 Commissioning and configuration on all products is supported by the 3 digit user interface and associated push buttons 2 When powered on the unit will display the firmware revision number after a few seconds the unit will display the first option in the menu structure see below 3 The display will enter standby mode after 30 seconds press the Mode butt...

Page 6: ...le of how to wire and control an MultiVent system hardwired to a Bathroom Kitchen and Toilet The MultiVent will utilize Humidity Rapid Rise in its response and the 2 larger rooms Bathroom and Kitchen will also provide a PURGE speed function if these 2 rooms are switched on together Before commencing please ensure that all power is OFF and ensure that it is electrically safe before starting Wire th...

Page 7: ...exity of assembly Only the full scroll assembly is replaceable 2 To remove the scroll assembly isolate the power then use a coin or similar to depress the cover retention clips and remove the cover 3 Disconnect and remove the power supply and signal leads 4 Remove the scroll assembly by unscrewing the two screws and unclipping the clips in the opposite two corners and lift the scroll assembly out ...

Reviews: