Vent-Axia EKF355E1 Installation And Wiring Instructions Download Page 4

 

 

 
 
 

4

The EKF EC kitchen extract fan is supplied with 3 x optional discharge positions. Before installation, 
consideration needs to be given to which discharge outlet is required. The discharge panel and 2 x 
access panels are interchangeable to suit the installation. 

                                            

 

It is recommended that duct connections to the unit are made via flexible connectors, (see accessories 
list). 
 

Mounting the unit 

If mounting the unit outdoors: 

  the unit MUST be installed with a weather roof fitted (see accessories list); 

  it is suggested that the unit is mounted at least 150mm off the floor surface. 

 
If suspending the unit, it is recommended that the unit is supported underneath. The M6 nutserts that are 
fitted to the framework can be used to fix supports. Take care not to obstruct the access panel. Vent-
Axia supplies a mounting feet kit, (see accessories list). 

 

 

Floor mounted on mounting feet and anti-
vibration mounts 

Suspended from 
ceiling with 
mounting feet and 
rod

Summary of Contents for EKF355E1

Page 1: ...EKF EC kitchen extract fan range Stock Ref N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3 Installation and Wiring Instructions...

Page 2: ...S OF HEAT AMBIENT TEMPERATURE RANGE IS 20 C TO 40 C OUTSIDE OF FAN AND DUCTWORK MAX 120 C IN DUCT 6 WHEN INSTALLING UNIT TAKE CARE NOT TO DAMAGE ELECTRICAL OR OTHER HIDDEN UTILITIES 7 CHECK THE DETAIL...

Page 3: ...lengths of ducting Short duct runs terminating close to the fan i e within 1 5m must incorporate suitable guards unless the fan is mounted higher than 2 1m above the floor Position the fan at the hig...

Page 4: ...Mounting the unit If mounting the unit outdoors the unit MUST be installed with a weather roof fitted see accessories list it is suggested that the unit is mounted at least 150mm off the floor surface...

Page 5: ...tened 4 The cable entry must be made using the knockouts provided 5 Replace isolator cover terminal box cover 6 Ensure the impeller rotates and is free from obstructions Notes 1 24V D1 should always b...

Page 6: ...KF450E1 Controls box Isolator Variable speed 230V 1Ph 50Hz Applies to EKF450E3 EKF500E3 EKF560E3 Controls box Isolator Full speed 400V 3Ph 50Hz Applies to EKF450E3 EKF500E3 EKF560E3 Controls box Isola...

Page 7: ...for more information should this occur Servicing Maintenance WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE 1 At intervals appropriate to th...

Page 8: ...ing Way Crawley RH10 9YX 405570 B 1015 The Guarantee Applicable only to products installed and used in the United Kingdom For details of guarantee outside the United Kingdom contact your local supplie...