Vent-Axia EKF355E1 Installation And Wiring Instructions Download Page 3

 

 

 
 
 

3

Product description 

The EKF EC kitchen extract fan is suitable for continuous running at 120°C in-duct air temperature. It 
can be mounted indoors or outdoors and controlled using the 0-10V potentiometer included. 
 

 

 

 
Installation 

 
The EKF EC kitchen extract fan is designed as a kitchen extract fan to be positioned between lengths of 
ducting. 
 
Short duct runs terminating close to the fan (i.e. within 1.5m) must incorporate suitable guards unless the 
fan is mounted higher than 2.1m above the floor. 
 
Position the fan at the highest point on the system with both ducting runs sloping downwards from this 
point. 
 
In circumstances where an excessive amount of moisture is present in the air then a condensation trap 
should be installed. 
 
When siting the appliance, ensure that there is sufficient space to allow access for any servicing and 
maintenance. 
 
 

Summary of Contents for EKF355E1

Page 1: ...EKF EC kitchen extract fan range Stock Ref N EKF355E1 EKF400E1 EKF450E1 EKF450E3 EKF500E3 EKF560E3 Installation and Wiring Instructions...

Page 2: ...S OF HEAT AMBIENT TEMPERATURE RANGE IS 20 C TO 40 C OUTSIDE OF FAN AND DUCTWORK MAX 120 C IN DUCT 6 WHEN INSTALLING UNIT TAKE CARE NOT TO DAMAGE ELECTRICAL OR OTHER HIDDEN UTILITIES 7 CHECK THE DETAIL...

Page 3: ...lengths of ducting Short duct runs terminating close to the fan i e within 1 5m must incorporate suitable guards unless the fan is mounted higher than 2 1m above the floor Position the fan at the hig...

Page 4: ...Mounting the unit If mounting the unit outdoors the unit MUST be installed with a weather roof fitted see accessories list it is suggested that the unit is mounted at least 150mm off the floor surface...

Page 5: ...tened 4 The cable entry must be made using the knockouts provided 5 Replace isolator cover terminal box cover 6 Ensure the impeller rotates and is free from obstructions Notes 1 24V D1 should always b...

Page 6: ...KF450E1 Controls box Isolator Variable speed 230V 1Ph 50Hz Applies to EKF450E3 EKF500E3 EKF560E3 Controls box Isolator Full speed 400V 3Ph 50Hz Applies to EKF450E3 EKF500E3 EKF560E3 Controls box Isola...

Page 7: ...for more information should this occur Servicing Maintenance WARNING THE FAN AND ANCILLARY CONTROL EQUIPMENT MUST BE ISOLATED FROM THE POWER SUPPLY DURING MAINTENANCE 1 At intervals appropriate to th...

Page 8: ...ing Way Crawley RH10 9YX 405570 B 1015 The Guarantee Applicable only to products installed and used in the United Kingdom For details of guarantee outside the United Kingdom contact your local supplie...