Attention!

Automatically restart after a power failure or mains disconnection!

2.7 Modi

cations / interventions in the device

Attention!

For reasons of safety, no unauthorized interventions or modi

cations may be made on the device. All

planned modi

cations must be authorized by the manufacturer in writing.

Only use the manufacturer

s original spare parts / wearing parts / accessories. These parts are

specially designed for this device. If parts from other sources are used, there is no guarantee that they

are designed and produced for the proper loads and with the required level of safety.

Parts and special equipment not supplied by the manufacturer are not approved for use.

2.8 Operator

s obligation of diligence

The contractor or owner must also ensure that the electric systems and equipment are operated

and maintained in accordance with electro-technical regulations.

The owner is obliged to ensure that the device are operated in perfect working order only.

The device may only be used as intended (

F

Application

).

You must periodically examine the safety equipment for their properly functioning condition.

The assembly instructions and/or operating instructions are always readily available at the

location where the device is being used, are complete and are in legible condition.

These persons are regularly instructed in all applicable questions regarding occupational safety

and environmental protection and are knowledgeable regarding the assembly instructions

and/or operating instructions and, especially, are familiar with the safety instructions contained

therein.

All safety and warning notices attached to the frequency inverter are never removed and remain

legible.

2.9 Employment of external personnel

Maintenance and service work are frequently carried out by external employees who often do not

recognize the speci

c situations and the thus resulting dangers.These persons must be comprehen-

sively informed about the hazards in their area of activity.

You must monitor their working methods in order to intervene in good time if necessary.

3 Product overview

3.1 Operational area

The controller described is used for continuous speed adjustment on variable voltage 1~ motors used

to drive ventilators or pumps.

3.2 Maintenance

The device must be checked for soiling and, if necessary, cleaned in periodic intervals.

3.3 Transport

The device is packed ex works to suit the transport method previously agreed.

Always use the original packaging materials when transporting the device.

Avoid shocks and impacts to the device during the transport.

During manual handling the human lifting and carrying restrictions must be observed and

adhered to.

3.4 Storage

The device must be stored in its original packaging in a dry and weather-proof room.

Avoid exposure to extreme heat and cold.

Avoid over-long storage periods (we recommend a maximum of one year).

Installation and Wiring Instructions

Speed controller

Product overview

L-BAL-E097-GB 1002 Index 001

Part.-No. 00163342-GB

5/18

Summary of Contents for 103 14 120

Page 1: ...Speed controller For variable voltage 1 fans Installation and Wiring Instructions Software version D1349A from Version 1 00 L BAL E097 GB 1002 Index 001 Part No 00163342 GB english...

Page 2: ...6 4 4 Installation location for agriculture 7 4 5 Temperature in uences during commissioning 7 5 Electrical installation 7 5 1 Safety precautions 7 5 2 EMC compatible installation 7 5 2 1 Motor feede...

Page 3: ...signal and speed 14 9 3 Operation with two variable output voltages two steps 14 10 Diagnostics Faults 15 10 1 If controller doesn t work correctly 15 11 Enclosure 16 11 1 Technical data 16 11 2 Conn...

Page 4: ...ept no liability for damage caused by misuse incorrect use improper use or as a consequence of unauthorized repairs or modi cations 1 4 Copyright These operating instructions contain copyright protect...

Page 5: ...n of accidents and the corresponding national as well as regional and in house regulations Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supe...

Page 6: ...nmental protection and are knowledgeable regarding the assembly instructions and or operating instructions and especially are familiar with the safety instructions contained therein All safety and war...

Page 7: ...ing model use supplied stoppers for cable inlets cut off necessary cable inlets respectively to the cable diameter Or alternative use cable inlet for cable glands Any cable ducts openings not used mus...

Page 8: ...s ing parts in metal terminal space covers and housing casings Commissioning is only permissible after these screws have been properly attached Metal screwed connections are not permitted in plastic h...

Page 9: ...low level of air noise this noise may be dominant in the lower speed range due to the occurrence of resonance 5 5 Motor protection The motor can be protected by connecting thermostats TB When multipl...

Page 10: ...sible to connect outputs of several devices to each other The function of the signal output A1 Analog Out 1 can be determined by DIP8 DIP 8 OFF Constant voltage 10 V for external potentiometer factory...

Page 11: ...ostics faults Fault indicated for line fault blown internal semiconductor fuse broken controller internal voltage supply overheating by the motor thermostats TB connected When switching off via enable...

Page 12: ...ng Potentiometer Pband without function Potentiometer n min Minimal output voltage basic speed Setting range 0 100 n min takes priority if over n max Potentiometer n max Maximal output voltage speed l...

Page 13: ...e goes continuously with reduction of the regulating variable down to 0 cutoff below approx 2 regulating variable Without minimum speed cut OFF DIP 5 OFF factory setting If minimal speed n min is adju...

Page 14: ...etting range Output voltage from approx 0 100 of connected line voltage or in range of settings n min up to n max Signal to E1 E1 GND 14 02 2008 v_signal_e1 vsd alternatively Control by external signa...

Page 15: ...teps DIP2 OFF for setting via external signall Switchover between two steps via external potential free contact possible Step 1 low speed When there is no input signal connected to the input terminal...

Page 16: ...rminals 11 12 bridged Motor fault Tripping of connected thermostat or break between terminals TB The unit cuts out and does not switch on again Check motor and connection then reset F Motor protection...

Page 17: ...approx 0 2 A Voltage supply e g for sensors 24 V 20 Imax 80 mA Output 0 10 V Imax 10 mA short circuit proof Max permissible ambient temperature 55 C Min permissible ambient temperature 0 C if mains v...

Page 18: ...tern with internal thermostats M 1 PE U2 U1 TB TB 2 14 01 2010 v_p et20sd VSD E1 10k 1 Line 1 120 277 V 50 60 Hz 2 1 Motor with internal thermostats 3 Input 0 10 V potentiometer outside connected at f...