7 Base setup

7.1 Function of dipswitches for operation as Speed controller (DIP

|

1

|

=

|

OFF

|

)

For operation as a speed controller, the output voltage is set manually by adjusting the built-in

potentiometer, by an external potentiometer or external signal.

The desired function is determined with dipswitch

S1

.

Position factory setting for all dipswitches =

|

OFF

|

DIP

Function

OFF

ON

1

Selection:

Speed controller

prohibited

2

Signal source of control

Setting of the output voltage by the potenti-

ometer mounted in the cover.

alternatively

Setting of output voltage by external signal

to

E1

.

(internal potentiometer

set

without func-

tion)

Setting the output voltage by internal po-

tentiometer

set

3

Type of Signal

0 - 10 V, 0 - 20 mA

2 - 10 V, 4 - 20 mA

4

Inverting signal input

0 - 10 V, 2 - 10 V, 0 - 20 mA, 4 - 20 mA

10 - 0 V, 10 - 2 V, 20 - 0 mA, 20 - 4 mA

5

Minimum speed cut off

OFF

ON

6

Hardstart function

OFF

ON

7

without function

-

-

8

Function signal output

Analog

Out 1

Constant voltage

+ 10 V

for external po-

tentiometer

0 - 10 V

modulation 0 - 100 %

9

without function

-

-

10

without function

-

-

7.2 Minimum speed cut off DIP 5

I f no

n-min

is adjusted,output voltage goes continuously with reduction of the regulating variable

down to

0

(cutoff below approx. 2 % regulating variable).

Without minimum speed cut OFF (DIP 5 =

|

OFF

|

= factory setting)

If minimal speed

n-min

is adjusted (e.g. 20%), then no disconnection of the fan takes place.

I.e. always a minimum ventilation is ensured (fan does not go under setting

n-min

).

With minimum speed cut off (DIP 5 =

|

ON

|

)

Cutoff below approx. 2 % regulating variable from sestting

n-min

to

0

.

Switch on again for a regulating variable above 5 % (to setting

n-min

).

Functional diagram

F

setting for operation as Speed controller

7.3 Hardstart function DIP 6

Special function for motorstart with maximum output voltage.

DIP 6 =

|

OFF

|

Hardstart

function = OFF (factory setting).

After switching the mains voltage on the output voltage rises during the

rmly programmed

run-up time to the given value.

DIP 6 =

|

ON

|

Hardstart

function = ON.

For a safe starting of the connected fans the function

Hard start

can be activated.

After switching the mains voltage on the controller generates for approx. 10 seconds max.

voltage

100 %

ignoring any control or sensor signal.

Afterwards the output voltage adjusts itself to the given or over the control ampli

er calculated

value.

Installation and Wiring Instructions

Speed controller

Base setup

L-BAL-E097-GB 1002 Index 001

Part.-No. 00163342-GB

12/18

Summary of Contents for 103 14 120

Page 1: ...Speed controller For variable voltage 1 fans Installation and Wiring Instructions Software version D1349A from Version 1 00 L BAL E097 GB 1002 Index 001 Part No 00163342 GB english...

Page 2: ...6 4 4 Installation location for agriculture 7 4 5 Temperature in uences during commissioning 7 5 Electrical installation 7 5 1 Safety precautions 7 5 2 EMC compatible installation 7 5 2 1 Motor feede...

Page 3: ...signal and speed 14 9 3 Operation with two variable output voltages two steps 14 10 Diagnostics Faults 15 10 1 If controller doesn t work correctly 15 11 Enclosure 16 11 1 Technical data 16 11 2 Conn...

Page 4: ...ept no liability for damage caused by misuse incorrect use improper use or as a consequence of unauthorized repairs or modi cations 1 4 Copyright These operating instructions contain copyright protect...

Page 5: ...n of accidents and the corresponding national as well as regional and in house regulations Personnel to be trained or instructed and apprentices are only permitted to work on the device under the supe...

Page 6: ...nmental protection and are knowledgeable regarding the assembly instructions and or operating instructions and especially are familiar with the safety instructions contained therein All safety and war...

Page 7: ...ing model use supplied stoppers for cable inlets cut off necessary cable inlets respectively to the cable diameter Or alternative use cable inlet for cable glands Any cable ducts openings not used mus...

Page 8: ...s ing parts in metal terminal space covers and housing casings Commissioning is only permissible after these screws have been properly attached Metal screwed connections are not permitted in plastic h...

Page 9: ...low level of air noise this noise may be dominant in the lower speed range due to the occurrence of resonance 5 5 Motor protection The motor can be protected by connecting thermostats TB When multipl...

Page 10: ...sible to connect outputs of several devices to each other The function of the signal output A1 Analog Out 1 can be determined by DIP8 DIP 8 OFF Constant voltage 10 V for external potentiometer factory...

Page 11: ...ostics faults Fault indicated for line fault blown internal semiconductor fuse broken controller internal voltage supply overheating by the motor thermostats TB connected When switching off via enable...

Page 12: ...ng Potentiometer Pband without function Potentiometer n min Minimal output voltage basic speed Setting range 0 100 n min takes priority if over n max Potentiometer n max Maximal output voltage speed l...

Page 13: ...e goes continuously with reduction of the regulating variable down to 0 cutoff below approx 2 regulating variable Without minimum speed cut OFF DIP 5 OFF factory setting If minimal speed n min is adju...

Page 14: ...etting range Output voltage from approx 0 100 of connected line voltage or in range of settings n min up to n max Signal to E1 E1 GND 14 02 2008 v_signal_e1 vsd alternatively Control by external signa...

Page 15: ...teps DIP2 OFF for setting via external signall Switchover between two steps via external potential free contact possible Step 1 low speed When there is no input signal connected to the input terminal...

Page 16: ...rminals 11 12 bridged Motor fault Tripping of connected thermostat or break between terminals TB The unit cuts out and does not switch on again Check motor and connection then reset F Motor protection...

Page 17: ...approx 0 2 A Voltage supply e g for sensors 24 V 20 Imax 80 mA Output 0 10 V Imax 10 mA short circuit proof Max permissible ambient temperature 55 C Min permissible ambient temperature 0 C if mains v...

Page 18: ...tern with internal thermostats M 1 PE U2 U1 TB TB 2 14 01 2010 v_p et20sd VSD E1 10k 1 Line 1 120 277 V 50 60 Hz 2 1 Motor with internal thermostats 3 Input 0 10 V potentiometer outside connected at f...

Page 19: ...IF CLAIMING UNDER TERMS OF GUARANTEE Please return the complete product carriage paid to your original supplier or nearest Vent Axia Centre by post or personal visit Please ensure that it is adequate...

Reviews: