7 Base setup
7.1 Function of dipswitches for operation as Speed controller (DIP
|
1
|
=
|
OFF
|
)
For operation as a speed controller, the output voltage is set manually by adjusting the built-in
potentiometer, by an external potentiometer or external signal.
The desired function is determined with dipswitch
S1
.
Position factory setting for all dipswitches =
|
OFF
|
DIP
Function
OFF
ON
1
Selection:
Speed controller
prohibited
2
Signal source of control
Setting of the output voltage by the potenti-
ometer mounted in the cover.
alternatively
Setting of output voltage by external signal
to
“
E1
”
.
(internal potentiometer
“
set
”
without func-
tion)
Setting the output voltage by internal po-
tentiometer
“
set
”
3
Type of Signal
0 - 10 V, 0 - 20 mA
2 - 10 V, 4 - 20 mA
4
Inverting signal input
0 - 10 V, 2 - 10 V, 0 - 20 mA, 4 - 20 mA
10 - 0 V, 10 - 2 V, 20 - 0 mA, 20 - 4 mA
5
Minimum speed cut off
OFF
ON
6
Hardstart function
OFF
ON
7
without function
-
-
8
Function signal output
“
Analog
Out 1
”
Constant voltage
“
+ 10 V
”
for external po-
tentiometer
0 - 10 V
≙
modulation 0 - 100 %
9
without function
-
-
10
without function
-
-
7.2 Minimum speed cut off DIP 5
I f no
“
n-min
”
is adjusted,output voltage goes continuously with reduction of the regulating variable
down to
“
0
”
(cutoff below approx. 2 % regulating variable).
Without minimum speed cut OFF (DIP 5 =
|
OFF
|
= factory setting)
•
If minimal speed
“
n-min
”
is adjusted (e.g. 20%), then no disconnection of the fan takes place.
I.e. always a minimum ventilation is ensured (fan does not go under setting
“
n-min
”
).
With minimum speed cut off (DIP 5 =
|
ON
|
)
•
Cutoff below approx. 2 % regulating variable from sestting
“
n-min
”
to
“
0
”
.
•
Switch on again for a regulating variable above 5 % (to setting
“
n-min
”
).
Functional diagram
F
setting for operation as Speed controller
7.3 Hardstart function DIP 6
Special function for motorstart with maximum output voltage.
DIP 6 =
|
OFF
|
“
Hardstart
”
function = OFF (factory setting).
After switching the mains voltage on the output voltage rises during the
rmly programmed
run-up time to the given value.
DIP 6 =
|
ON
|
“
Hardstart
”
function = ON.
For a safe starting of the connected fans the function
“
Hard start
”
can be activated.
After switching the mains voltage on the controller generates for approx. 10 seconds max.
voltage
“
100 %
”
ignoring any control or sensor signal.
Afterwards the output voltage adjusts itself to the given or over the control ampli
er calculated
value.