MA-AL-T272-01-01 Manual TUL272 eng rev1 

 

   Rev.1 Page 2 of 4 

 
MECHANICAL FEATURES 

 
Dimensions (mm) :  width 280 ;   height 373   ;   depth 125     Weigth :  6,2  Kg 
 

ENVIRONMENTAL FEATURES 

 
Operating temperature: from  -5  

°

C   to   +40   

°

Relative humidity: from 5%  to  93%  

±

 

2 %

 

Cooling: air cooling 
Installation place: sheltered from atmospheric agents 
 

SECURITY INSTRUCTION 

 
 

1.  Utilize different fairlead holes on the bottom of the box, to pass cables for tension input and dc 

 alarms. Moreover, materials for pipe/box fitting must have HB inflammability class or 
better. 

2.   

“GUASTO” and “RETE RIT” relay contacts, must be connected only to circuits working with 

SELV tension. 

3.  For AC power supply, use a differential magneto-termic bipolar protection switch, easily 

accessible. 

4.  Conductors must have cross section suitable to tension and equipped with adequate cable 

terminals on contact pressure points. 

5. 

Installation of unit must be executed by qualified personnel who Know security requirements 
EN60950 and concerning power supply units CEI 64-8.

 

 

 

INSTALLATION 

 

Mechanical mounting 

 
This unit has to be installed on vertical solid walls able to support the power supply unit using 4 plugs 
of 6 mm, 4 washers and screws coming out from the 4 holes on the bottom of the box. 
 

Electrical connection 

 
Connect unit to power 230 Vac through a differential magneto-termic bipolar switch to protect line 
against short circuit and operator from current leakage.  
 
IMPORTANT: Utilize separated fairlead and tubes for input ac power supply (230 Vac) and dc 
o alarms (SELV). 
For connection please refer to Pict 1. In this picture are indicated the following important topics:

 

 
 

Output terminals (Power supply) 

 
BAT +      

Battery positive pole 

BAT -       

Battery negative pole 

OUT 1 +      Positive output to load 1 
OUT 1 -     

Negative output to load 1 

OUT 2 +      Positive output to load 2 
OUT 2 -     

Negative output to load 2 

 
 
 

Fuses 

 
F1     Input fuse power supply 230 Vac (T 1,6 AL) 
F2     Fuse for over tension protection (T 4 AL) 
F3     Battery fuse (T 4 AL) 
F4     Relative output fuse OUT 1 (T 1,6 AL) 
F5     Relative output fuse OUT 2 (T 1,6 AL) 
 

 