MA-SE-HE00-01-11 Manual HEMA eng rev11 

 

Page 

6

 of 

8

 

 

 

 

Diagram 1 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONNECTION and SETTINGS 

 

DIP SWITCHES SETTING 

DIP switches can be moved only within the first 12 hours after the board is powered. After this period, DIP switches settings 
will be stored and any further switching will be useless.  
By disconnecting battery and power supply, DIP switches will return to active for another 12 hours. 

 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

 
 

 
 
 
 

 

 

HEMA LS DIP3 in ON position 

Angle 

dB (A) @1m 

15° 

100.8 

45° 

104.5 

75° 

110.4 

105° 

110.7 

135° 

104.7 

165° 

100.8 

 

HEMA L DIP3 in ON position 

Angle 

dB (A) @1m 

15° 

100.9 

45° 

103.4 

75° 

109.3 

105° 

110.1 

135° 

104.0 

165° 

101.2 

Chart 3: wiring 

Terminals 

Connections 

-RIC (1) 

Negative supplying 0 Vdc GND 

+RIC (2) 

Positive sup13.8 Vdc 

+C (3) 

Sounder control chart 5 

STI (4) 

ON/OFF indication of alarm system status 

Input for sound block 

OUT ANM (6)  Fault output. Open collector, 0 Vdc = no anomaly 

RES (7) 

Flash reset 

TAMPER (8) 

Self-protection N.C. 

TAMPER (9) 

Self-protection N.C. 

Chart 2: dipswitches and jumpers 

DIP 1 

Alarm timing 

DIP 2 

Polarity of alarm input +C 

DIP 3 

Tone selection 

DIP 4 

Alarm system STI (ON/OFF) notice setting 

DIP 5 

Flash reset mode 

DIP 6 

Alarm trigger mode +C 

JUMPER 

Max daily alarms 

Chart 4: alarm timing 

DIP 1 

Alarm duration 

OFF (default) 

3 minutes 

ON 

8 minutes 

Chart 5: Voltage reference for alarm input +C 

DIP 2 

TeC 

OFF (default) 

Positive (12 Vdc) reference for Alarm [see DIP 6] 

ON 

Negative (0 Vdc) reference for Alarm [see DIP 6] 

Chart 6: tone selection 

DIP 3 

Tone 

Frequency limits (Hz) 

OFF (default) 

Increasing-continuous-decreasing 

1,200 ÷ 1,750 

ON 

Increasing-decreasing (NFC 48-265)  

1,400 ÷ 1,600 

110.4 dB (LS) 
109.3 dB (L) 

Summary of Contents for HEMA L

Page 1: ...ty inversion and tropicalized through a special resin tropicalization process against bad weather conditions and moisture External cover and sounder base are in ABS while the internal cover is made of...

Page 2: ...from 20 to 100 of RH Size 330x210x110 H x L x W Weight 1 957 gr Standards compliance T031 2014 EN50131 4 2009 Security L and LS models Grade 3 LSP model Grade 4 MOUNTING 1 Use the 6mm plugs to fix the...

Page 3: ...positive missing trigger RES negative trigger for flash reset Note by default DIPSWITCH N 2 is set in OFF position POSITIVE MISSING TRIGGER LEFT FLASH RIGHT FLASH ANTI DRILLING ANTI DRILLING TAMPER T...

Page 4: ...ered to terminal M10 TAMPER A P 4 OPTICAL INDICATION OF SYSTEM STATUS MOMENTARY OR PERMANENT ON OFF If a positive is given to terminal STI System status all LEDs of the flashing light make 3 flashes O...

Page 5: ...lts too At the first sounder supplying 13 8 Vdc or battery anomalies automatically reset once the cause disappears this makes the installation easier After the first activation of the sounder anomalie...

Page 6: ...Vdc C 3 Sounder control chart 5 STI 4 ON OFF indication of alarm system status 5 Input for sound block OUT ANM 6 Fault output Open collector 0 Vdc no anomaly RES 7 Flash reset TAMPER 8 Self protection...

Page 7: ...on for 4 seconds then switch off ON 12 Vdc All LEDs flash 3 times and 1 LED keeps on flashing Not connected or 0 Vdc All LEDs remain steady on for 4 seconds then switch off Chart 8 flash reset mode D...

Page 8: ...01 11 Manual HEMA eng rev11 Page 8 of 8 Product manufactured in Italy Venitem s r l via del Lavoro 10 30030 Salzano VE ITALY Tel 39 0415740374 Fax 39 0415740388 E mail info venitem com website www ve...

Reviews: