MA-SE-HE00-01-11 Manual HEMA eng rev11 

 

Page 

5

 of 

8

 

 

 
 

6.

 

TERMINAL 5 - NEGATIVE SOUND-BLOCK INPUT  

It gives a 0V signal to terminal 5 thus activating the sound interruption trigger. 

 

7.

 

TERMINAL OUT ANM AND FAULTS LED 

The microcontroller managing the sounder is able to check if recharge, battery, loudspeaker and drivers are working properly. In case of faults, the open 
collector output OUT ANM opens while the LED located on the sounder board shows the type of fault by making a certain number of flashes followed 
by a short pause (please see chart here below for FAULTS LED signalisation). 

 

The microcontroller automatically performs every 4 hours the battery current test. Moreover, other tests are performed on regular basis. Usually, if the 
sounder is properly supplied, the faults output (terminal 7) remains at 0 Vdc (max consumption 50 mA). In case any of the tests performed fails, the 
faults  output  disconnects  from  the  ground  and  becomes  free.  Moreover,  the  microprocessor  is  always  under  self-test  and  in  case  of  failure  or 
malfunctioning, it gives a free output with sound interruption.

 

To reset the fault appeared: eliminate the fault cause. Then:

 

-

 

(see scheme below): wait 10 seconds, let terminal n°4 (STI) free, take it to 12 Vdc, wait 10 seconds and let terminal n°4 free again. This procedure resets 
all faults; 

 

 

 

 

-

 

all faults are anyway reset after every alarm (+C), with the exception of those concerning the battery that are reset after 12 hours from battery restore 
(replacement). The sounder performs all tests again and therefore updates battery faults too.      
 
At the first sounder supplying (13.8 Vdc or battery), anomalies automatically reset once the cause disappears; this makes the installation easier. After 
the first activation of the sounder, anomalies reset through a command to STI terminal or tC. 
To launch the remote test, see scheme here above. This action launches the test that lasts 60 seconds. During the test, the sounder verifies if it is 
working properly and provides signalization of any faults through the faults output (OUT ANM) and the faults LED as shown in CHART 1: FAULTS below. 
 
In case a fault occurs, the LEDs of the flashing light flash faster. 

 
 
 

 

CHART 1: FAULTS 

FAULT TYPE 

LED 
LD1 

Output 

OUT ANM 

Speaker interruption (test performed every 10 s) 

1 FLASH 

OPEN 

No recharge voltage  (recharge V < 12 Vdc) (test performed every 10 s) 

2 FLASHES  

OPEN 

Battery not connected (test performed every 12 hours) 

3 FLASHES 

OPEN 

Low battery (battery V < 10.5V) (test performed every 12 hours) 

4 FLASHES 

OPEN 

Damaged battery – internal resistor over 3.5 Ohm (test performed every 12 hours) 

5 FLASHES 

OPEN 

Speaker drivers failure   (test performed every 10 s) 

6 FLASHES 

OPEN 

No anomaly  

OFF 

0V 

 

 

 

8.

 

CONNECTION OF MICRO SWITCH ANTI-OPENING AND ANTI-REMOVAL TAMPER 

Connect the tamper line coming from control panel in series to the two wires of micro switch located on the sounder using the dedicated terminals 
TAMPER 8 and 9.  

 

9.

 

CONNECTION OF ANTI-FOAM (LS model) 

Connect the two wires of the antifoam device in series to the micro switch and the tamper line coming from control panel.  

 

10.

 

CONNECTION OF ANTI-DRILLING (LSP model) 

Connect TAMPER A.P. terminals in series to the anti-foam, the micro switch and the tamper line coming from control panel.  
 
 
 
 
 
 
 
 
 

FREE 

ELIMINATE FAULT CAUSE – 10 SEC – FREE  

12 Vdc 

+12 Vdc 

10 SEC 

Summary of Contents for HEMA L

Page 1: ...ty inversion and tropicalized through a special resin tropicalization process against bad weather conditions and moisture External cover and sounder base are in ABS while the internal cover is made of...

Page 2: ...from 20 to 100 of RH Size 330x210x110 H x L x W Weight 1 957 gr Standards compliance T031 2014 EN50131 4 2009 Security L and LS models Grade 3 LSP model Grade 4 MOUNTING 1 Use the 6mm plugs to fix the...

Page 3: ...positive missing trigger RES negative trigger for flash reset Note by default DIPSWITCH N 2 is set in OFF position POSITIVE MISSING TRIGGER LEFT FLASH RIGHT FLASH ANTI DRILLING ANTI DRILLING TAMPER T...

Page 4: ...ered to terminal M10 TAMPER A P 4 OPTICAL INDICATION OF SYSTEM STATUS MOMENTARY OR PERMANENT ON OFF If a positive is given to terminal STI System status all LEDs of the flashing light make 3 flashes O...

Page 5: ...lts too At the first sounder supplying 13 8 Vdc or battery anomalies automatically reset once the cause disappears this makes the installation easier After the first activation of the sounder anomalie...

Page 6: ...Vdc C 3 Sounder control chart 5 STI 4 ON OFF indication of alarm system status 5 Input for sound block OUT ANM 6 Fault output Open collector 0 Vdc no anomaly RES 7 Flash reset TAMPER 8 Self protection...

Page 7: ...on for 4 seconds then switch off ON 12 Vdc All LEDs flash 3 times and 1 LED keeps on flashing Not connected or 0 Vdc All LEDs remain steady on for 4 seconds then switch off Chart 8 flash reset mode D...

Page 8: ...01 11 Manual HEMA eng rev11 Page 8 of 8 Product manufactured in Italy Venitem s r l via del Lavoro 10 30030 Salzano VE ITALY Tel 39 0415740374 Fax 39 0415740388 E mail info venitem com website www ve...

Reviews: