Step 8:

 Connect the electrical box on 

the condensing unit to a power source 

as shown in the attached figure.  The 

condensing unit is rated for    

208/230V-1-60. 

VDPTCU005 = 21.6A MCA 

VDPTCU006 = 14.9A MCA 

 

Step 9:

 

a.) Confirm that the unit is free of leaks using pressurized nitrogen at approximately 150 psig and then 

pull a vacuum down to 200 microns for at least 30 minutes. 

b.) Charge the unit with 3 lbs. of R404a into the receiver. Break the vacuum on the low side prior to 

starting the unit.   

c.)

Turn ‘ON’ the power to the condensing unit and the display case.  Turn the display case ‘ON’.  The 
high side pressure should be approximately 30°F above the ambient temperature.  Add refrigerant if 
needed. 

d.) Set the low pressure switch to 40 PSIG with a differential of 30 PSIG.   
e.) Wait for at least 1 hour prior to placing product in the unit. 